Checks to the refrigeration equipment 
Where electrical components are being changed, they shall be fit for the purpose
and to the correct specification. At all times the manufacturer s maintenance and
service guidelines shall be followed. If in doubt consult the manufacturer s technical
department  for  assistance.  The  following  checks  shall  be  applied  to  installations
using flammable refrigerants:
The  charge  size  is  in  accordance  with  the  room  size  within  which  the  refrigerant
containing parts are installed; The ventilation machinery and outlets are operating
adequately and are not obstructed;
If  an  indirect  refrigerating  circuit  is  being  used,  the  secondary  circuits  shall  be
checked for the presence of refrigerant; marking to the equipment continues to be
visible and legible. 
Marking and signs that are illegible shall be corrected;
Refrigeration pipe or components are installed in a position where they are unlikely
to  be  exposed  to  any  substance  which  may  corrode  refrigerant  containing
components,  unless  the  components  are  constructed  of  materials  which  are
inherently  resistant  to  being  corroded  or  are  suitably  protected  against  being  so 
corroded.
9)
Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks
and  component  inspection  procedures.  If  a  fault  exists  that  could  compromise
safety,  then  no  electrical  supply  shall  be  connected  to  the  circuit  until  it  is
satisfactorily  dealt  with.  If  the  fault  cannot  be  corrected  immediately  but  it  is 
necessary to continue operation, and adequate temporary solution shall be used. 
This shall be reported to the owner of the equipment so all parties are advised. 
Initial safety checks shall include:
That  capacitors  are  discharged:  this  shall  be  done  in  a  safe  manner  to  avoid
possibility of sparking;
That  there  no  live  electrical  components  and  wiring  are  exposed  while  charging,
recovering or purging the system; That there is continuity of earth bonding. 
10)
Repairs to sealed components
a)
During repairs to sealed components, all electrical supplies shall be disconnected
from the equipment being worked upon prior to any removal of sealed covers, 
etc. If it is absolutely necessary to have an electrical supply to equipment during
servicing, then a permanently operating form of leak detection shall be located
at the most critical point to warn of a potentially hazardous situation.
b)
articular attention shall be paid to the following to ensure that by working on 
electrical components, the casing is not altered in such a way that the level of
protection is affected. This shall include damage to cables, excessive number of 
connections,  terminals  not  made  to  original  specification,  damage  to  seals, 
incorrect fitting of glands, etc.