ERROR CODE 
Low pressure protection 
Pe<0.6) occured 3 
times in an hour 
Low pressure protection 
High pressure protection 
Compressor overcurrent 
protection 
MALFUNCTION OR 
PROTECTION 
FAILURE CAUSE AND CORRECTIVE ACTION 
Refer to P0 
1. System is lack of refrigerant volume. Charge the
refrigerant in right volume. 
2. When  at  heating  mode  or  DHW  mode,  the
outdoor heating exchanger is dirty or something
is  block  on  the  surface.  Clean  the  outdoor
heating exchanger or remove the obstruction. 
3. The  water  flow  is  too  low  in  cooling
mode.increase the water flow. 
4.  Electrical  expansion  valve  locked  or  winding
connector is loosen. Tap‐tap the valve body and
plug in/ plug off the connector for several times
to make sure the valve is working correctly. 
Heating mode, DHW mode: 
1. The  water  flow  is  low;  water  temp  is  high,
whether  there  is  air  in  the  water  system.
Release the air. 
2. Water  pressure  is  lower  than  0.1Mpa,  charge
the  water  to  let  the  pressure  in  the  range  of
0.15~0.2Mpa. 
3. Over  charge  the  refrigerant  volume.  Recharge
the refrigerant in right volume. 
4. Electrical  expansion  valve  locked  or  winding
connector is loosen. Tap‐tap the valve body and 
plug in/ plug off the connector for several times
to make sure the valve is working correctly. And
install  the  winding  in  the  right  location  DHW 
mode: Water tank heat exchanger is smaller 
Cooling mode:  
1.  Heat  exchanger  cover  is  not  removed.
Remove it. 
2. Heat exchanger is dirty or something is block 
on  the  surface.  Clean  the  heat  exchanger  or 
remove the obstruction 
1. The same reason to P1.
2. Power supply voltage of the unit is low, increase
the power voltage to the required range 
39 
-