ERROR CODE 
Transducer module 
temperature too high 
protect 
DC generatrix voltage is 
too low 
MALFUNCTION OR 
PROTECTION 
FAILURE CAUSE AND CORRECTIVE ACTION 
1. Power supply voltage of the unit is low, increase
the power voltage to the required range. 
2. The space between the units is too narrow for 
heat exchange. Increase the space between the
units. 
3. Heat exchanger is dirty or something is block on 
the  surface.  Clean  the  heat  exchanger  or 
remove the obstruction. 
4. Fan is not running. Fan motor or fan is broken,
Change a new fan or fan motor. 
5. Water flow rate is low, there is air in system, or
pump head is not enough. Release the air and 
reselect the pump. 
6. Water outlet temp.sensor is loosen or broken,
reconnect it or change a new one. 
1. Check the power supply. 
2. If the power supply is OK,and check if LED light
is  OK,  check  the  voltage  PN,  if  it  is  380V,  the
problem  usually  comes  from  the  main  board. 
And  if  the  light  is  OFF,  disconnect  the  power,
check  the  IGBT,  check  those  dioxides,  if  the 
voltage  is  not  correct,  the  inverter  board  is
damaged, change it. 
3. And  if  those  IGBT  are  OK,  which  means  the
inverter board is OK, power form rectifier bridge
is not correct, check the bridge. (Same method 
as  IGBT,  disconnect  the  power,  check  those
dioxides are damaged or not). 
4. Usually  if  F1  exist  when  compressor  start,  the
possible reason is main board. If F1 exist when
fan start, it may be because of inverter board 