Networking Configuration Submenu (Oncuer Plus Password) - Kohler 48RCLB Operation

Residential/light commercial generator sets
Hide thumbs Also See for 48RCLB:
Table of Contents

Advertisement

3.17.2 Networking Configuration
Submenu (OnCuer Plus
Password)
The networking Configuration menu includes settings
used for communication with the Kohlerr OnCuer Plus
Generator Management System.
For most applications, DHCP is enabled and the IP
settings cannot be changed from the controller keypad.
If DHCP is enabled, IP parameters are not displayed.
If DHCP is disabled (i.e., if a static IP address is
required), then the IP parameters can be modified. For
applications that require static IP addresses, press and
hold the select button to enable editing, disable DHCP,
and then step to the next parameters and enter the
information.
If an error occurs while setting a parameter, an error
message is displayed and then the controller exits the
edit mode. Previous settings are preserved.
Networking- - >
Information
Figure 3-19 Network Configuration Submenu
44
Section 3 RDC2 Controller Operation
Networking- - >
Status
Networking
Reset OnCue
Configuration
Password
<- - Return
Note: Use the OnCue password shown on the
controller display for OnCue Plus applications.
For the initial OnCue Plus setup, you will be required to
reset the OnCue password on the RDC2 controller, and
then enter it into the OnCue Plus software. To reset the
password, follow the instructions in Figure 3-19.
Note: The password is displayed for only 10 seconds.
Be sure to write down the password and serial
number.
A new password is generated each time the reset
password procedure is performed. If the password is
reset after the OnCue Plus system has been set up, the
connection will be lost. Disconnect the battery power to
the controller, wait a minute, then reconnect power.
HOLD
DHCP:
Enabled
Reset OnCue
Password? No
UP arrow for YES,
Down arrow for NO.
Reset OnCue
Password? Yes
Press Select to enter YES
or NO as displayed. New
password is displayed for
approximately 10 seconds.
S/N: 1234567
New PW: 12345
TP-7102 3/20
tp6804

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

60rclaRdc2