4.3 Lubrication System

4.3.1

Oil Specifications

Kohler recommends KOHLERr Genuine Oil, 10W- 40
or equivalent.
KOHLERr Genuine Oil is fully synthetic and engineered
specifically for gaseous-fueled (NG / LPG) engines
requiring SAE 10W- 40 oil.
Note: The oil must meet the specifications for zinc,
phospohorous, and ash content shown in
Figure 4-1.
Oil Specifications
Oil Type
Zinc Content
Phosphorous
Sulfated Ash Content
Figure 4-1 Engine Oil Specifications
4.3.2

Oil Check

Check the oil level in the crankcase every 24 hours of
operation or before the engine is started each day. Do
not check the oil level while operating the unit. Stop the
generator set and keep the generator set level to get an
accurate reading. To check the oil level, remove the
dipstick and wipe the end clean. Reinsert the dipstick
and wait at least 30 seconds. Remove the dipstick and
check the level. Maintain the oil level between the Full
and Add marks on the dipstick, as shown in Figure 4-2.
See Section 1, Service Views for the dipstick location.
Note: Do not operate the set if the oil level is below the
Add mark or above the Full mark on the dipstick.
1. Full mark
2. Add mark
Figure 4-2 Oil Level Check
52
Section 4 Scheduled Maintenance
SAE 10W-40
1000- 1200 ppm
1000- 1200 ppm
1% or lower
1
2
TP-5586-3
4.3.3

Oil Additions

Adding some oil between oil changes is normal. The
amount varies with generator set usage. Open the oil fill
cap and pour in a small amount of oil using a funnel or
other suitable pouring device. See Section 1, Service
Views, for the oil check and oil fill locations.
4.3.4

Oil and Filter Change

WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working
on
Remove the negative (- ) lead first
when disconnecting the battery.
Reconnect the negative (- ) lead last
when reconnecting the battery.
Disabling the generator set.
cause severe injury or death.
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (- ) lead first. Reconnect the negative
(- ) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
Change the oil every 150 hours of engine operation, as
shown in the service schedule, or before generator set
storage. Change the oil more frequently if the generator
set operates under dirty, dusty conditions. Change the
oil while the engine is still warm. See Section 1, Service
Views, for oil fill, oil check, and oil filter locations.
Note: The engine is shipped from the factory with
break-in oil. Run the engine for a minimum of 40
hours with the break-in oil. Change the break-in
oil according to the normal service schedule,
after 150 hours of engine operation.
Dispose of all waste materials (engine oil, fuel, filter,
etc.) in an environmentally safe manner.
Note: Reset the maintenance timer on the RDC2
controller after changing the oil.
the
generator
set.
Accidental starting can
Before working on the
TP-7102 3/20