Multistage or modulating mode with
actuator
11.1
Relevant parameters
Parameter
Meaning
123
Minimum output control step
259
Opening time of actuator (timeout)
260
Closing time of actuator (timeout)
654
Analog input (feedback potentiometer ASZxx.3x required)
0 = 3-position step input
1 = DC 0...10 V
2 = 0...135
3 = 0...20 mA
4: 4...20 mA with a non-alterable lockout at I <4 mA (AZL2: Loc: 60)
5 = 4...20 mA
11.1.1 Connection diagram for feedback potentiometer
ASZ12.33
Note!
The connection diagram shown is merely an example which must be verified in the
individual case depending on the application!
PME7
X66
Type
SQNx1...
SQMx1...
SQNx0...
SQMx0...
a b c
ASZ12.33
Figure 16: Connection diagram for feedback potentiometer ASZ12.33
Basic Documentation LME7...
11 Multistage or modulating mode with actuator
Terminal X66
on the LME7...
Rotation
direction
a
b
c
---
X
c
---
a
b
X
c
a
---
b
X
c
b
a
---
X
Terminal potentiometer
(1 kOhm conductive
plastik 90°) ASZxx30
7105d39e/1009
56/116
CC1P7105en