Siemens LME71 Series Basic Documentation page 105

Burner control
Hide thumbs Also See for LME71 Series:
Table of Contents

Advertisement

A
Alternately
>3 s
A
and
+
or
-
Alternately
-
and
+
Smart Infrastructure
Basic Documentation LME7...
15 Operation via internal LED
A
Press
for >3 seconds to display alternately LoA and
41.
The relative value 41 of the current position or current
speed is displayed.
Actuator position 0°
0  potentiometer value =
0% display
Actuator position high-fire
>0°
<90° = potentiometer value
>0  <1000  = 100%
display
The actual value (example 41%) is displayed and the signal
lamp blinks green.
Example: Position of actuator or the current speed 41%
(based on range between high-fire and 0° or 0 rpm)
A
Press
simultaneously with
actuator position or the fan speed between low-fire (x%) and
high-fire (100%).
Release the buttons when the required position or speed is
reached.
Signal lamp blinks s green.
Example: Value 43
Display shows alternately LoA and 43.
Signal lamp blinks green.
Example: Required position of actuator or current speed
43%
-
+
Press
and
simultaneously (Escape) to return to
normal operation.
Display: oP
When manual adjustment is completed, the actuator or the
PWM fan returns to the analog preset output!
Current speed
0 rpm = 0
display
%
Current speed corresponds
to the rated load speed =
100% display
+
-
or
to adjust the
105/116
CC1P7105en
24.07.2020