Technical Data; Basic Unit Lme7 - Siemens LME71 Series Basic Documentation

Burner control
Hide thumbs Also See for LME71 Series:
Table of Contents

Advertisement

Smart Infrastructure
4

Technical data

4.1 Basic unit LME7

Mains voltage
Mains frequency
External primary fuse
Caution!
Risk of damage to the switching contacts!
If the external primary fuse (Si) is blown due to overload or short-circuit at the
terminals, the LME7 must be replaced.
Power consumption
Safety class
Degree of protection
Rated surge voltage category III (DIN EN 60664)
LME7
Creepage distances or air gaps
Degree of contamination
Software class
Reaction time in the event of loss of
flame
Perm. mounting position
Weight
Basic Documentation LME7...
4 Technical data
AC 120 V
50/60 Hz
Max. 6.3 A (slow)
<10 W, typical
I with parts according to II and III in
accordance with DIN EN 60730-1
IP00
Note
The burner or boiler manufacturer must
ensure degree of protection IP40 in
accordance with DIN EN 60529 for
burner controls through adequate
installation of the LME7.
4 kV
2.5 kV due to voltage limitation
measures
2 in accordance with DIN EN 60730-1
Class C in accordance with DIN EN
60730-2-5:2011
2-channel structure
Max. 1 s
Optional
Approx. 490 g
AC 230 V
50/60 Hz
Max. 6.3 A (slow)
<10 W, typical
28/116
CC1P7105enr
24.07.2020