Lifetime; Disposal Notes - Siemens LME71 Series Basic Documentation

Burner control
Hide thumbs Also See for LME71 Series:
Table of Contents

Advertisement

1.7 Lifetime

The LME7 has a designed lifetime* of 250,000 burner startup cycles which, under
normal operating conditions in heating mode, corresponds to approx. 10 years of
service (starting from the date of manufacture on the unit type plate). This lifetime is
based on the endurance tests in the standard EN 298. A summary of the conditions has
been published by the European Control Manufacturers Association (Afecor)
(www.afecor.org).
The designed lifetime is based on use of the LME7 according to the manufacturer's data
sheet and the basic documentation. After reaching the designed lifetime in terms of the
number of burner startup cycles, or after the corresponding usage time, the LME7 must
be replaced by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
1.8

Disposal notes

The unit contains electrical and electronic components and must not be disposed of
together with domestic waste. Local and currently valid legislation must be observed.
14/116
Smart Infrastructure
Basic Documentation LME7...
CC1P7105enr
1 Safety notes
24.07.2020

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents