and
+
>1 s
-
or
+
Alternately
Alternately
nfo
>1 s
Smart Infrastructure
15.8

Manual restore

After 2 minutes, the LME7 changes to Loc 138
Basic Documentation LME7...
15 Operation via internal LED
-
+
Press
and
simultaneously for >1 second (Escape)
for starting the manual restore process.
Parameter PrC appears.
Display: PrC
-
+
Press
or
for parameter rSt.
Display: rSt
nfo
1...3 s
run appears during download (restore process) of program
sequence.
Display shows alternately End and rSt.
Display shows the end of data exchange.
Signal lamp blinks red.
After the restore process, the LME7 is automatically in the
lockout position (Loc 138) and must be reset for operation.
nfo
Press
(for > 1 second) to reset the LME7.
Display OFF