<3 s
It will now be displayed for 2 minutes, or can be finished by pressing the
<2
min
or
/reset
Note
During the restore process, all settings and parameters are written from the PME7 to the
internal memory of the LME7. As part of this process, it is possible that previous program
sequences, parameters, and settings in the internal memory of the LME7 will be overwritten.
Warning!
For initial commissioning or replacement of the PME7, the function sequence and
parameter settings must be checked on completion of the restore process. Failure to
observe this information poses a risk of the safety functions being impaired.
 See chapter Operation via AZL2 / first startup, restore
 See chapter Operation via internal LED / first startup, restore
Smart Infrastructure
Basic Documentation LME7...
13 Operation via AZL2
/reset
Press
to activate the restore process.
/reset
Display shows run
After approx. 3 seconds (depending on the duration of the
program sequence), the displays shows rSt End and
signaled the end of the restore process.
Display: rSt End
Display shows OFF when the restore process is finished.
button
/reset
86/116
CC1P7105en
24.07.2020