Fan Replacement (Procedure H) - YASKAWA GA800 Installation Manual

Hide thumbs Also See for GA800:
Table of Contents

Advertisement

3.
Connect the fan cable to the fan connectors.
A - Fan connectors
B - Fan cable
4.
Install the drive cover.
5.
Energize the drive and set o4-03 = 0 [Fan Operation Time Setting = 0 h] to reset the fan operation time.

Fan Replacement (Procedure H)

DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before servicing,
disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal capacitor
stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage decreases below 50
Vdc. When all indicators are OFF, remove the covers before measuring for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock.
CAUTION
Burn Hazard. Do not touch a hot drive heatsink. De-energize the drive, wait for a minimum of 15 minutes, then
make sure that the heatsink is cool before you replace the cooling fans. If you touch a hot drive heatsink, it can burn you.
NOTICE
Use the instructions in this manual to replace the cooling fans. When you do maintenance on the fans, replace all
the fans to increase product life. If you install the fans incorrectly, it can cause damage to the drive.
YASKAWA TOEPC71061779D GA800 Drive Installation Manual
Figure 4.64 Install the Circuit Board Cooling Fan Unit
Figure 4.65 Fan Connect Cooling Fan Connectors
C - Circuit board cooling fan units
4 Maintenance
57