3 Mechanical Installation

No.
4
Rated output current
Note:
Refer to the rated output current list for more information.
5
EMC noise filter
A: No built-in EMC filter
B: built-in C3 filter
6
Protection design
A: IP00/UL Open Type
B: IP20/UL Open Type
F: IP20/UL Type 1
T: IP55/UL Type 12
W: IP55/UL Type 12 Heatsink External Mounting
7
Environmental specification
M: Resistant to dust/humidity
3
Mechanical Installation
This section gives information about the standard environment for correct installation.

Installation Environment

The installation environment is important for the lifespan of the product and to make sure that the drive performance
is correct. Make sure that the installation environment agrees with these specifications.
Environment
Indoors
Area of Use
Overvoltage Category III
Power Supply
IP00/UL Open Type: -10 °C to +50 °C (14 °F to 122 °F)
IP20/UL Open Type/Heatsink External Mounting: -10 °C to +50 °C (14 °F to 122 °F)
IP20/UL Type 1: -10 °C to +40 °C (14 °F to 104 °F)
IP55/UL Type 12 Heatsink External Mounting; front side: -10°C to +50 °C (14 °F to 122 °F)
Ambient Temperature Setting
IP55/UL Type 12 Heatsink External Mounting; back side: -10°C to +40 °C (14 °F to 104 °F)
• When installing the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in the permitted range.
• Do not let the drive freeze.
• You can use IP20/UL Open Type drives at a maximum of 60 °C (140 °F) when you derate the output current.
• You can use IP20/UL Type 1 drives at a maximum of 50 °C (122 °F) when you derate the output current.
95%RH or less
Humidity
Do not let condensation form on the drive.
-20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Storage Temperature
Pollution degree 2 or less
Install the drive in an area without:
• Oil mist, corrosive or flammable gas, or dust
• Metal powder, oil, water, or other unwanted materials
Surrounding Area
• Radioactive or flammable materials.
• Harmful gas or fluids
• Salt
• Direct sunlight
Keep wood and other flammable materials away from the drive.
1000 m (3281 ft) maximum
Note:
Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes between 1000 m to 4000 m (3281 ft to 13123 ft).
Altitude
It is not necessary to derate the rated voltage in these conditions:
• Installing the drive at 2000 m (6562 ft) or lower
• Installing the drive between 2000 m to 4000 m (6562 ft to 13123 ft) and grounding the neutral point on the power supply.
Contact Yaskawa or your nearest sales representative when not grounding the neutral point.