Replace Gasket; Specifications; Common Drive Specifications - YASKAWA GA800 Installation Manual

Hide thumbs Also See for GA800:
Table of Contents

Advertisement

4.
Install the drive cover.
5.
Energize the drive and set o4-03 = 0 [Fan Operation Time Setting = 0 h] to reset the fan operation time.

Replace Gasket

If there is damage to the gasket, replace it with the replacement gasket.
1.
Use a plastic scraper to remove the damaged gasket.
Note:
Do not scratch the mounting surfaces.
2.
Remove the adhesive cover from the replacement gasket.
3.
Install the replacement gasket.
Align the screw holes on the replacement gasket with the holes on the enclosure panel or a fan replacement
service panel.
5

Specifications

Common Drive Specifications

Note:
• To get the OLV, CLV, and AOLV specifications, do Rotational Auto-Tuning.
• To get the longest product life, install the drive in an environment that meets the necessary specifications.
Item
• V/f Control (V/f)
• V/f Control with Encoder (CL-V/f)
• Open Loop Vector (OLV)
• Closed Loop Vector (CLV)
Control Methods
• Advanced Open Loop Vector (AOLV)
• PM Open Loop Vector (OLV/PM)
• PM Advanced Open Loop Vector (AOLV/PM)
• PM Closed Loop Vector (CLV/PM)
• EZ Vector Control (EZOLV)
• Models 2004 to 2138, 4002 to 4103, and T103
HD: 8 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
• Models 2169 to 2415, 4140 to 4414, and T140 to T414
HD: 5 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Carrier Frequency
Derate the drive capacity to use values to 10 kHz maximum.
• Models 4477 to 4720, and T477 to T720
HD: 2 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 5 kHz maximum.
• Models 5289 to 5472
2 kHz without derating the drive capacity.
• 200 V Class: Three-Phase 200 V to 240 V
• 400 V Class: Three-Phase 380 V to 480 V
Maximum Output
• 600 V Class: Three-Phase 500 V to 600 V
Voltage
Note:
The maximum output voltage is proportional to the input voltage.
• AOLV and EZOLV: 0.01 Hz to 120 Hz
Frequency Control
• CL-V/f, CLV, AOLV/PM, and CLV/PM: 0.01 Hz to 400 Hz
Range
• V/f, OLV, and OLV/PM: 0.01 Hz to 590 Hz
Frequency Accuracy
Digital inputs: Within ±0.01% of the maximum output frequency (-10 °C to +40 °C (14 °F to 104 °F))
(Temperature
Analog inputs: Within ±0.1% of the maximum output frequency (25 °C ±10 °C (77 °F ±18 °F))
Fluctuation)
Digital inputs: 0.01 Hz
Frequency Setting
Resolution
Analog inputs: 1/2048 of the maximum output frequency (11-bit signed)
Output Frequency
0.001 Hz
Resolution
YASKAWA TOEPC71061779D GA800 Drive Installation Manual
Table 5.1 Control Characteristics
*1
*1
*1
*1
Specification
5 Specifications
65

Advertisement

Table of Contents
loading

Table of Contents