7.17 Server Board Replacement

Before performing this procedure, review all the safety and ESD precautions found in the Safety Warnings
section at the beginning of this document.
Note: All components removed from the module must be kept on an ESD safe work surface or into an ESD
safe bin or bag while full module/system disassembly and reassembly is in progress
Required Tools and Supplies
Anti-static wrist strap and conductive workbench pad (recommended)
Phillips* head screwdriver #2
1. Remove the module from the chassis (see
2. For air-cooled modules, remove the air duct (see Section 7.2.1).
3. Remove riser card assemblies (see
4. Remove all options installed onto the server board including (if installed) the Intel® VROC 7.5 key
(see
Section
3.11).
5. Remove all DIMMs (see
6. For liquid-cooled module, remove the liquid-cooling loop (see
7. Remove processors (see
8. Remove 15 screws used to secure the server board to the module tray (see Letter A).
9. Slide the server board slightly towards the back of the module tray. Then, carefully lift the server board
from the module tray (see Letter B) and place it in an anti-static bag.
178
Intel® Server D50TNP Family Integration and Service Guide

Figure 264. Server Board Removal

Section
Section
7.8).
Section
7.5).
Section
7.4).
7.1.1).
Section
7.9)