Low Hz High Pressure Limit - Daikin 4MXS-R Series Service Manual

Multi-split type air conditioners
Table of Contents

Advertisement

Control Specification
A (minutes)
B (°C)
C (°F)
D (Hz)
E (Hz)
F (seconds)
G (seconds)
H (seconds)
J (seconds)
K (pulse)
L (pulse)
M (pulse)
N (pulse)
P (pulse)
Q (pulse)

4.12 Low Hz High Pressure Limit

Outline
The system controls the upper limit of the frequency to prevent abnormal high pressure while the
frequency is low. Control is carried out according to three zones.
Details
103
18 class
24/36 class
33
26
4 ~ 12
4 ~ 12
39.2 ~ 53.6
39.2 ~ 53.6
58
58
74
42
60
90
120
60
650
590
80
40
320
400
300
250
300
300
320
400
160
50
160
0
A
Reset zone
Highest indoor
heat exchanger
temperature
among
operating rooms
18 class
A
60°C (140°F)
B
59°C (138.2°F)
C
56°C (132.8°F)
Dropping zone
B
Keep
zone
C
(R14587)
24/36 class
38.5°C (101.3°F)
37.5°C (99.5°F)
34.5°C (94.1°F)
Functions and Control
SiUS121736EA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents