DIP Switch Settings
All DIP switches are turned OFF at shipment.
DIP Switch 1
DIP switch S1 is used to set the input signal range, hysteresis, contact operation (delay time), and contact drive method.
SWITCH
ON ● ↑
OFF ❍ ↓
Input signal
0 to 10 V
0 to 20 mA
Hysteresis
0.1%
1.0%
2.5%
5.0%
Contact operation (delay time)
0 s
1 s
2 s
3 s
4 s
6 s
8 s
10 s
Contact drive method
NO
NC
Connections
■ Internal Block Diagram
+
Input signal
DIP switch S1
1
2
3
4
5
5
6
6
7
8
K3FP-1
Limit Value Switch
1
Not connected
2
14
3
11
4
12
7
+
Supply voltage
8
K3FP-SL-UI