Omron K3FP Series Manual page 34

Ultra-slim signal converter
Table of Contents

Advertisement

Safety standards
UL 508
EMC
EMI:
Radiated EMI:
EMS:
ESD immunity:
Rated electromagnetic field immunity:
Burst immunity:
Surge immunity:
Conducted disturbance immunity:
■ Input Specifications
Input signal
0 to 20 mA DC
Item
Approx. 50 Ω
Input impedance
Max. input signal
100 mA
Alarm output setting Using 25-speed potentiometer
Nomenclature
34
Limit Value Switch
EN 55011
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
0 to 10 V DC
Approx. 110 k Ω
30 V
Status indicator (yellow)
Error indicator (red)
Potentiometer for adjustment
5 6 Input signals
7 8 Supply voltage
K3FP-SL-UI
■ Output Specifications
Output signal
Item
Contact output
Yellow indicator (LED)
status display
Applicable load
250 V AC, 2 A
Contact material
AgSnO
Max. contact voltage 250 V AC
Max. contact current 2 A
Max. switching
500 VA (250 V AC)
capacity
Mechanical life
20 million operations
Electrical life
200,000 operations
Hysteresis
0.1%, 1% 2.5%, 5% (can be set using the
DIP switch)
Contact drive
NO, NC (can be set using the DIP switch)
method
Contact operation
0 s, 1 s, 2 s, 3 s, 4 s, 6 s, 8 s, 10 s
(delay time)
(can be set using the DIP switch)
Translucent cover
1 Not connected
2 3 4 Output: SPDT
DIP switch S1
Snap for mounting DIN rail
DIN rail bus connection
SPDT
2