Ultra-slim signal converter
Table of Contents

Advertisement

Output Status for Errors
SWITCH DIP switch S2
7
8
ON ● ↑
OFF ❍ ↓
Output status
for errors
A
B
C
D
Relationship between Output Signal Range Selection and Output Status for Errors
Output Signal Ranges 0 to 20 mA or 20 to 0 mA
Output status
DIP switch S2
for errors
7
8
A
B
C
D
Output Signal Ranges 4 to 20 mA or 20 to 4 mA
Output status
DIP switch S2
for errors
7
8
A
B
C
D
Output Signal Ranges 0 to 10 V or 10 to 0 V
Output status
DIP switch S2
for errors
7
8
A
B
C
D
Output Signal Range 0 to 5 V
Output status
DIP switch S2
for errors
7
8
A
B
C
D
When disconnected on
Above measurement
platinum resistance
thermometer side
Held at 5% of maximum
Held at 2.5% of maximum
rated output.
rated output.
Held at 5% of maximum
Held at 2.5% of maximum
rated output.
rated output.
Held at 5% of maximum
Held at maximum rated
rated output.
output.
Held at minimum rated
Held at maximum rated
output.
output.
When disconnected on
Above measurement
platinum resistance
thermometer side
21 mA
20.5 mA
21 mA
20.5 mA
21 mA
20 mA
0 mA
20 mA
When disconnected on
Above measurement
platinum resistance
thermometer side
21 mA
20.5 mA
21 mA
20.5 mA
21 mA
20 mA
4 mA
20 mA
When disconnected on
Above measurement
platinum resistance
thermometer side
10.5 V
10.25 V
10.5 V
10.25 V
10.5 V
10 V
0 V
10 V
When disconnected on
Above measurement
platinum resistance
thermometer side
5.25 V
5.125 V
5.25 V
5.125 V
5.25 V
5 V
0 V
5 V
Below measurement
range
range
Held at minimum rated
output.
Held at − 12.5% of
minimum rated output.
Held at minimum rated
output.
Held at minimum rated
output.
Below measurement
range
range
0 mA
0 mA
0 mA
0 mA
Below measurement
range
range
4 mA
3.5 mA
4 mA
4 mA
Below measurement
range
range
0 V
0 V
0 V
0 V
Below measurement
range
range
0 V
0 V
0 V
0 V
RTD Transducer
When short-circuited on
platinum resistance
thermometer side
Held at minimum rated
output.
Held at − 25% of minimum
rated output.
Held at 5% of maximum
rated output.
Held at minimum rated
output.
When short-circuited on
platinum resistance
thermometer side
0 mA
0 mA
21 mA
0 mA
When short-circuited on
platinum resistance
thermometer side
4 mA
3mA
21 mA
4 mA
When short-circuited on
platinum resistance
thermometer side
0 V
0 V
10.5 V
0 V
When short-circuited on
platinum resistance
thermometer side
0 V
0 V
5.25 V
0 V