DIP Switch Settings
All DIP switches are turned OFF at shipment.
DIP Switch S1
DIP switch S1 is used to set the thermocouple type, cold junction
compensation enable/disable, output signal range, and the start of
the measurement range.
SWITCH
1
ON ● ↑
OFF ❍ ↓
Thermocouple type
Type J
Type K
Cold junction
compensation
enable/disable
Enabled
Disabled
Output signal range
0 to 20 mA
20 to 0 mA
4 to 20 mA
20 to 4 mA
0 to 10 V
10 to 0 V
0 to 5 V
1 to 5 V
Start temperature
[ ° C]
[ ° F]
0
32
− 10
14
− 20
− 4
− 30
− 22
− 40
− 40
− 50
− 58
− 100
− 148
− 150
− 238
DIP switch S1
2
3
4
5
6
7
DIP Switch S3
DIP switch S3 is used to select the current output and voltage output
for output signals.
SWITCH DIP switch S3
ON ● ↑
8
OFF ❍ ↓
Output signal
0 to 20 mA
20 to 0 mA
4 to 20 mA
20 to 4 mA
0 to 10 V
10 to 0 V
0 to 5 V
1 to 5 V
Thermocouple Transducer
1
2
K3FP-TS-UI
19