Operation - Omron K3FP Series Manual

Ultra-slim signal converter
Table of Contents

Advertisement

Dimensions
Note: All units are in millimeters unless otherwise indicated.
K3FP-SN1-I-I
K3FP-SN2-I-I
Precautions
Refer to pages 38 and 39 for common precautions.
■ Precautions for Correct Use

Operation

Passive Loop-powered Isolators draw the power required for isolation
from the input signal.
Here, you must confirm that the current sourcing voltage of the
measuring transducer U
is sufficient to drive the maximum current
B
of 20 mA via the Loop-powered Isolator with a voltage drop U
1.7 V and a load R
.
B
Thus:
≥ U
= 1.7 V + 20 mA × R
U
B
E
16
Loop-powered Isolator
102.5
V
B
U
= 1.7 V
V
K3FP-SN1-I-I
K3FP-SN1-I-I/K3FP-SN2-I-I
93.1
6.2
of
Note: 1. Use solid wire with a diameter
2
of 2.5 mm
max. or bar
terminals with insulation
sleeves for terminal
connections.
To preserve dielectric strength
after connection, the length of
the exposed conductive part
inserted into the terminal must
be 12 mm max.
2
For 2.5-mm
(max.)
For bar terminals with
solid wire:
insulation sleeves:
12 mm max.
2. Screw Tightening Torque
Recommended torque:
0.5 N·m
12 mm max.