E3X-DA-N
Nomenclature
J DIGITAL FIBER-OPTIC AMPLIFIER
Level Display
Lock Button
Operation Indicator (orange)
ON when output is ON.
OFF when output is OFF.
J DISPLAY AND SPECIAL FUNCTION SETTINGS
Display Setting
The E3X-DA-N offers three display modes, which are Digital Incident Level display, Digital Percent display and Analog display.
Digital Incident Level Display: the incident level is digitally displayed.
Digital Percent Display: the threshold-based excess gain is displayed in percentage.
Analog Display: threshold and excess gain is displayed by two-color (red and green) bar graph.
Special Function Setting
The E3X-DA-N series has various functions that give users more flexibility in meeting a variety of application requirements.
Sensing Function: Enables users to choose either standard sensing distance mode, long sensing distance mode
or high speed mode
Timer Function: Enables users to select various OFF-delay timer settings from 0 to 20 ms (set in 1 ms increments) and from 20 to
200 ms (set in 5 ms increments). OFF-delay timer lengthens the duration of a short, high-speed signal so that it can be recognized as
input to Programmable Controllers during a scan cycle.
Flashing Function: Flashing red LED allows easier optical axis adjustment.
Display Hold Setting: This function provides easy data reading during optical axis adjustment and high-speed detection by holding
the displayed value for a period of time. Displayed data gets updated every 2 seconds. Within the 2-second time frame, the maximum
or minimum value is displayed (data will be flashing).
Display Orientation Setting: Reversible digital display provides easy data reading from any mounting orientation.
Zero reset: When activated, this function sets the incident
level digital display to zero. This enables operators to easily
monitor the difference between the maximum incident level
and the minimum incident level.
Initial reset: Enables users to easily program the amplifier
back to the default (factory) settings.
Monitor focus: This feature is available on analog/digital
output models. Without "monitor focus", the E3X-DA-N has to
analyze an incident level range of 0 to 4095 to process a 1 to
5 VDC analog output. With the "monitor focus" function, the
E3X-DA-N can narrow the range of the incident level to pro-
cess a 1 to 5 VDC analog input by defining an upper and
lower limit of the incident level. As as result, the sensor's
resolution is increased.
Example: Monitor focus increases resolution over a narrow range Upper limit = 2400 and lower limit = 1000
Conventional monitor output
Monitor
output
Digital value
Setting Buttons
TEACH
MODE
Operation Mode Selector
Selectable between Light-ON and Dark-ON modes.
Mode Selector
Selectable among SET, ADJ, and RUN modes.
Example: Zero reset used to calculate threshold setting
At maximum incident level
1200
Shift
700
Incident level
difference = 700
350
Threshold level is auto-
matically calculated: 350
Output with E3X-DA-N's monitor focus
Monitor
output
Digital value
E3X-DA-N
At minimum incident level
500
Zero reset
0
5