Trane TRACER SUMMIT Hardware And Software Installation page 98

Hide thumbs Also See for TRACER SUMMIT:
Table of Contents

Advertisement

Chapter 6 UCMs supported by Tracer Summit systems
86
Device addressing
Each UCM must have a unique address on each link. Voyagers can have
an address from 50 through 81. The Voyager address is set using DIP
switches on the TCI-3 board and must match the address set in Site Con-
figuration for Tracer Summit. Refer to the TCI-3 literature for more
details about setting the address. For Voyager address DIP switch set-
tings, refer to Table 24.
Table 24. Voyager rooftop unit UCM address settings
UCM
address
SW1-2
50
OFF
51
OFF
52
OFF
53
OFF
54
OFF
55
OFF
56
OFF
57
OFF
58
OFF
59
OFF
60
OFF
61
OFF
62
OFF
63
OFF
64
OFF
65
OFF
66
on
67
on
68
on
68
on
70
on
71
on
72
on
73
on
74
on
75
on
76
on
TCI Board DIP switch settings
SW1-3
SW1-4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
on
OFF
on
OFF
on
OFF
on
on
OFF
on
OFF
on
OFF
on
OFF
on
on
on
on
on
on
on
on
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
on
OFF
on
OFF
on
OFF
on
on
OFF
on
OFF
on
OFF
SW1-5
SW1-6
OFF
OFF
OFF
on
on
OFF
on
on
OFF
OFF
OFF
on
on
OFF
on
on
OFF
OFF
OFF
on
on
OFF
on
on
OFF
OFF
OFF
on
on
OFF
on
on
OFF
OFF
OFF
on
on
OFF
on
on
OFF
OFF
OFF
on
on
OFF
on
on
OFF
OFF
OFF
on
on
OFF