Trane TRACER SUMMIT Hardware And Software Installation page 71

Hide thumbs Also See for TRACER SUMMIT:
Table of Contents

Advertisement

BMTX-SVN01C-EN
The CCP IIs software version is shown on the label of the chip at loca-
tion U-27 on the board. The revision level of the board determines
whether previous software versions of the CCP can be upgraded to be
compatible with a Tracer Summit system.
Wiring requirements
To establish wiring connections between the CCP II and the BMTX BCU,
refer to the specifications on wire type, topology, and wire procedures in ""
on page 34. Attach the communication link wiring to the CCP II at TB3-4
and TB3-5
Device addressing
Each CCP II must have a unique address on each link. CCPs can have an
address from 1 through 32. The address is set with the S2 DIP switches
and must match the address that was set in Site Configuration for Tracer
Summit.
For details about setting the address, refer to the CCP II literature.
For CCP II DIP switch settings, refer to Table 9.
Table 9. CCP II DIP switch settings
UCM address
1
1
on
2
OFF
3
on
4
OFF
5
on
6
OFF
7
on
8
OFF
9
on
10
OFF
11
on
12
OFF
13
on
14
OFF
15
on
16
OFF
17
on
18
OFF
19
on
Description of UCM types
CCP II
S2 DIP switch settings
2
3
OFF
OFF
OFF
on
OFF
OFF
on
OFF
OFF
OFF
on
OFF
OFF
on
OFF
on
on
OFF
on
on
OFF
OFF
OFF
OFF
OFF
on
on
OFF
on
OFF
on
OFF
on
OFF
on
on
on
on
on
OFF
OFF
OFF
OFF
OFF
OFF
on
OFF
OFF
on
OFF
OFF
4
5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
on
OFF
OFF
on
OFF
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
on
on
on
59