Table 30. Reset level descriptions for the BMTX BCU
BCU reset/restore command
Reset (same as power cycle)
Resets the processor on the selected
BCU
Clear RAM and reset
Clears the RAM from the BCU and resets
the BCU processor
If the BCU has a database intact, it auto-
matically reconstructs the RAM as
needed and resumed processing
Clear database, RAM, and reset
Clears both the database and RAM from
the selected BCU and resets the BCU
processor.
Note: To prevent download of database
from secondary workstations, discon-
nect them from LAN before proceeding.
Clear the BCU database using the BCU
reset/restore command or using DIP
switch method.
Then disconnect BCU from the LAN
either by removing the LAN cable or
using the Disconnect button on the Tool-
bar.
Restore the new database to the PC
workstation.
Reconnect the BCU.
Database will be automatically sent to
the BCU.
Clear code, database, RAM, and reset
Clears all memory—code (image), data-
base, and RAM—from the BCU and
resets the BCU processor.
If the PC workstation is online, it auto-
matically downloads the code.
Once the code is successfully down-
loaded, the PC workstation automati-
cally downloads a new database.
Clear Comm5 database
Happens automatically when site name
in BCU changes or BCU address
changes.
If the PC workstation is online, it auto-
matically downloads the code.
Once the code is successfully down-
loaded, the PC workstation automati-
cally downloads a new database.
Note: For detailed instructions for the DIP switch method, refer to "BCU reset procedures" on page 120.
BMTX-SVN01C-EN
Reasons to reset
Initialize modem
Initialize communication links
Update members in VAS (not applicable
for Comm5 VAS)
Restore a backup database from the PC
workstation to the BCU.
Replace a database in the BCU.
Required when upgrading Tracer Sum-
mit BCU image
Used for troubleshooting problem links
LEDs for operation status
Notes
Temporary loss of communication with
the BCU
Same as reset plus:
Loss of operator overrides. Values
return to Tracer Summit defaults
Loss of pending alarms
No loss of Comm5 database
Same as Clear RAM and Reset plus:
Takes longer to regain communication
with the BCU and UCMs than a clear
RAM or reset does.
If database is restoring from a backup of
the site, current trend and calculation
information is lost and reverts to infor-
mation stored in backup.
Same as Clear Database, RAM, and Reset
plus:
Code will load to a BCU that does not
have an address.
If a database with a different address or
site name is loaded to the BCU, the BCU
Comm5 database will be cleared.
Cannot be done from a PC Workstation
BCU Reset/Restore menu.
123