Chapter 6 UCMs supported by Tracer Summit systems
82
in "Comm3/Comm4 wiring" on page 35. Attach the communication link
wiring to the VAV communication link terminals. Refer to the VAV UCM
literature for connection points.
Device addressing
Each UCM must have a unique address on each link. On the UCM, the
address is set with the S1 DIP switch. For VAV II,VAV III, and VAV IV
DIP settings, see Table 22.
Table 22. VAV II, III, and IV address settings
UCM address
DIP 1
65
OFF
66
on
67
OFF
68
on
69
OFF
70
on
71
OFF
72
on
73
OFF
74
on
75
OFF
76
on
77
OFF
78
on
79
OFF
80
on
81
OFF
82
on
83
OFF
84
on
85
OFF
86
on
87
OFF
88
on
89
OFF
90
on
91
OFF
92
on
93
OFF
VAV II, III, and IV DIP switch settings
DIP 2
DIP 3
DIP 4
on
on
on
OFF
on
on
OFF
on
on
on
OFF
on
on
OFF
on
OFF
OFF
on
OFF
OFF
on
on
on
OFF
on
on
OFF
OFF
on
OFF
OFF
on
OFF
on
OFF
OFF
on
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
on
on
on
on
on
on
OFF
on
on
OFF
on
on
on
OFF
on
on
OFF
on
OFF
OFF
on
OFF
OFF
on
on
on
OFF
on
on
OFF
OFF
on
OFF
OFF
on
OFF
on
OFF
OFF
on
OFF
OFF
DIP 5
DIP 6
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
OFF
on
BMTX-SVN01C-EN