[ I Safety Precaution ]
[5] Service tools
Use the below service tools as exclusive tools for R32/R410A refrigerant.
Refer to the spec name plate on outdoor unit for the type of refrigerant being used.
No.
Tool name
1.
Gauge manifold
2.
Charge hose
3.
Electronic weighing scale
4.
Gas leak detector
5.
Adaptor for reverse flow check
6.
Refrigerant charge base
7.
Refrigerant cylinder
8.
Refrigerant recovery equipment
HWE20020
Electronic weighing scale
Specifications
· Use the existing fitting specifications. (UNF1/2)
· Use high-tension side pressure of 5.3MPa·G or over.
· Use pressure performance of 5.09MPa·G or over.
· Use the detector for R410A or R32.
· Attach on vacuum pump.
· R32 or R410A refrigerant
· Cylinder with syphon