[ IX Troubleshooting ]
• For description of each check code, refer to the following table.
1
C
h
e
k c
c
o
d
e
P1
Intake sensor error
P2
Pipe (TH2) sensor error
P9
Pipe (TH5) sensor error
E6,E7
Indoor/outdoor unit communication error
P4
Drain sensor error
P5
Drain pump error
PA
Forced compressor error
PB
Fan motor error
P6
Freezing/Overheating safeguard operation
EE
Communication error between indoor and outdoor units
P8
Pipe temperature error
E4
Remote controller signal receiving error
Fb
Indoor unit control system error (memory error, etc.)
E0, E3
Remote controller transmission error
E1, E2
Remote controller control board error
E9
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
UP
Compressor overcurrent interruption
U3,U4
Open/short of outdoor unit thermistors
UF
Compressor overcurrent interruption (When compressor locked)
U2
Abnormal high discharging temperature/49C worked/insufficient refrigerant
U1,Ud
Abnormal high pressure (63H worked)/Overheating protection operation
U5
Abnormal temperature of heat sink
U8
Outdoor unit fan safeguard stop
U6
Compressor overcurrent interruption/Abnormal of power module
U7
Abnormality of super heat due to low discharge temperature
U9,UH
Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/
Current sensor error
Others
Other errors (Refer to the technical manual for the outdoor unit.)
• On wired remote controller.
1
Check code displayed in the LCD.
Wireless remote controller
(1) Turn on the power to the unit at least 12 hours before the test run.
(2) Press the TEST RUN button
(Start this operation from the status of remote controller display turned off.)
and current operation mode are displayed.
TEST RUN
(3) Press the MODE button
(4) Press the MODE button
(5) Press the FAN button
(6) Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver while following steps (2) to (6).
• It is not possible to run the in FAN, DRY or AUTO mode.
HWE20020
S
y
twice continuously.
A
to activate COOL mode, then check whether cool air is blown out from the unit.
B
to activate HEAT mode, then check whether warm air is blown out from the unit.
B
and check whether fan speed changes.
C
m
p
o t
m
- 26 -
R
e
m
a
k r
Each unit has two each of the
following: intake sensors, liquid
pipe sensors, 2-phase pipe
sensors, and fan motors. When
a problem occurs with one of
any of the items above, an error
code (P1, P2, P8, P9, or PB)
will appear. When an error code
appears, check both of the items.
For details, check the LED display
of the outdoor controller board.
As for outdoor unit, refer to
service manual.