Ground Coil - IVT 495 TWIN Manual To Installation, Commissioning And Maintenance

Table of Contents

Advertisement

INSTALLER

Ground coil

Ground coil
The collector hose is a thin-walled hose PEM 40 x 2.4 PN 6.3 or PEM 40 PN 10. It is important that the
filling around the ground coil does not contain stones or other objects that could damage the hose. The
final filling is best carried out after the ground collector has been tested. Avoid fillings or dirt getting into
the coil when cutting.
Installation and filling around the collector hose must comply with local regulations.
Bending diameter
Minimum permitted bending diameter is 1 metre. Always use an elbow coupling for sharper bends. If you
damage the hose by bending it too much you can repair it with a straight coupling.
Heat pump
IVT 495 TWIN
*) The hose length must be increased for exhaust airflows less than 120m³/h,
contact IVT for further information. Max hose length is 400m.
IVT 495 TWIN 9518799
Ground coil
150 metres
Finished ground level
Collector hose 150 m
Type PEM 40 x 2.4 PN 6.3.
Minimum distance between hose and house: 1.5m
The hoses must be insulated over the final 1.5m towards the
house foundation to avoid frost movements.
Filling must be carried out according to local regulations.
The filling must not contain stones or other objects that could
damage the hoses.
Refilling with
existing soil
40
Bore depth
50 metres