Burner identification
(burner ID)

Makeup of burner ID

Languages

Real time clock
and calendar

S / W changeover

Siemens Building Technologies
HVAC Products
Burner ID offers the OEM the opportunity - which may also be the OEM's duty - to store
an individual burner ID in each LMV51... system by means of the OEM password, prior
to delivery.
Burner ID is then used to enable or disable the data transfer between the basic unit and
the AZL51... backup storage. Parameters can be loaded to the AZL51... at any time, if
the burner ID in the basic unit is not in the «as supplied» status.
The burner ID itself is part of the data transfer in both directions (if that is possible).
In addition, for the burner, the burner ID represents one of a number of start
prerequisites. In other words, the burner cannot be started up as long as the burner ID is
in the «as supplied» status.
So, it is possible to have data transmission between the basic unit and the AZL51... of
one plant (burner IDs are identical) and between an AZL51... and a new basic unit
(burner ID «as supplied» by Siemens).
Data transmission between AZL51... and basic units of different plants (burner IDs not
identical) is not possible (no «cloning»!).
Invalid characters for the burner ID are all vowels (ä, ö, ü and ß).
Minimum length of burner ID = 4 characters
Maximum length of burner ID = 15 characters
The AZL51... can output the display texts in different languages.
Changeover to another language takes place via menu «Params & Display»
® «AZL51...» ® «Language».
In addition to English as the basic language, the AZL51... provides German and French.
Using the program update function of the PC tool, additional language groups can be
loaded to the AZL51... together with the relevant program version.
Hence, direct exchange of the language without loading a new program version is not
possible.
The LMV51... system is equipped with a real time clock with a calendar and backup,
which is accommodated in the AZL51... .
The clock features automatic summer- / wintertime changeover.
The following parameter setting choices are available:
Parameter1
summer- / wintertime changeover:
Parameter2
summer- / wintertime changeover:
EU version
start:
end:
US version
start:
end:
Changeover takes place on the dates given above in the night between 02:00 and 03:00
hrs. The time shift is always 1 hour.
Changeover takes place only if the AZL51... receives power at that moment in time.
Basic Documentation LMV51...
6 Display and operating unit AZL51...
last Sunday in March
last Sunday in October
first Sunday in April
like EU version
on / off
EU version / US version