ACS450
AGG5.110
AGG5.220
AGG5.630
AGG5.631
AGG5.640
AGG5.641
AZL51.00A1
KF8893
LMV51.000A2
LMV51.100A2
QRI2A2...
QRI2B2...
SQM45.291A9
SQM45.295A9
SQM48.497A9
SQM48.697A9
12/157
Siemens Building Technologies
HVAC Products

1.2 Product range overview

PC tool for convenient programming and burner settings, process visualization, data
recording, selection of AZL51... language, software update AZL51...
CAN bracket for connecting the CAN bus to the basic unit.
Power transformer for CAN bus users with power characteristics matched to the
requirements of the LMV51... .
CAN bus connecting cable between basic unit and AZL51... and for short distances to
the SQM4x. Shielded 5-core cable, 500 m.
CAN bus connecting cable between basic unit and AZL51... and for short distances to
the SQM4x. Shielded 5-core cable, 100 m.
CAN bus connecting cable between basic unit and actuators or between actuators.
Shielded 5-core cable, 500 m.
CAN bus connecting cable between basic unit and actuators or between actuators.
Shielded 5-core cable, 100 m.
Display and operating unit. Detached unit for front panel mounting with text display,
4 x 16 characters, 4 silicon buttons. Real time clock and e-bus interface for BMS.
Demo case including LMV51.100A2, AZL51.00A1, 2 x SQM45.295A9, and AGG5.220.
Operating buttons for simulation. Electronic simulation of controlled system, burner
graphics and LEDs.
Microprocessor-based burner control for single- and dual-fuel burners of any capacity.
Electronic fuel / air ratio control system on CAN bus basis with up to 4 actuators.
Integrated gas valve proving system.
Same as LMV51.000A2, plus load controller. Integrated digital PID boiler temperature or
pressure controller (LC), limit sensor conforming to TRD (Technische Richtlinien Dampf
= Technical Directives for Steam). Automatic adaption of the controller characteristics
depending on operating mode (modulating or multistage).
Infrared flame detector. Universal flame detector for oil or gas flames. Suited for
intermittent or continuous operation, with integrated flame amplifier and prefabricated
connecting cable 180 cm. Front illumination.
Infrared flame detector. Universal flame detector for oil or gas flames. Suited for
intermittent or continuous operation, with integrated flame amplifier and prefabricated
connecting cable 180 cm. Lateral illumination.
Actuator. Nominal torque 3 Nm, running time 10...120 seconds. Control and feedback
via CAN bus. Stepper motor, flush panel mounting, Woodruff key.
Actuator. Nominal torque 3 Nm, running time 10...120 seconds. Control and feedback
via CAN bus. Stepper motor, flush panel mounting, D-shaft.
Actuator. Nominal torque 20 Nm, running time 30...120 seconds. Control and feedback
via CAN bus. Stepper motor, flush panel mounting, parallel key.
Actuator. Nominal torque 35 Nm, running time 60...120 seconds. Control and feedback
via CAN bus. Stepper motor, flush panel mounting, parallel key.
Basic Documentation LMV51...