Burner control with integrated fuel / air ratio control and load control for forced-draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Direct gas ignition

Gas pilot ignition 1

Gas pilot ignition 2

Fuel valve
control program
ts 1
ts 2
Operation
Siemens Building Technologies
HVAC Products
2

Fuel train applications (examples)

Program
SV
Gp1
Program
SV
Gp2
Program
SV
Gas
(always modulating)
Direct trafo ignition
Pilot ignition 1
G
Gp1
*)
PV
V1
V2
PV
V1
Basic Documentation LMV51...
2 Fuel train applications (examples)
G
Direct ignition
V1
PS
PS
min
VP
Gas pilot
V1
PS
PS
min
VP
Gas-Pilot
V1
PS
PS
min
VP
Pilot ignition 2
Gp2
PV
V1
V2
V2
V2
PS
ACT
max
7550s01E/0202
V2
PS
ACT
max
PV
7550s02E/0202
V2
PS
ACT
max
PV
7550s17E/0202
Legend to fuel trains:
*)
Not used
1)
Series connection of two 115 V
valves (each requiring approx. 25 VA
control power)
2)
Preheating device
V
Fuel valve
VP
Gas valve proving
PS
Pressure switch
HE
Heating element
HO
Heavy oil
LO
Light oil
ACT Actuator
NO
N ormally O pen
SV
Shutoff valve (outside the building)
PV
Pilot valve