Siemens LMV51 Series Basic Documentation page 152

Burner control with integrated fuel / air ratio control and load control for forced-draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

5E
#
BU
Internal Fault Basic Unit
5F
-
BU
Param eter Set damaged
60
#
BU
Internal Fault Basic Unit
61
#
BU
Internal Fault Basic Unit
70
#
BU
Internal Fault Basic Unit
71
-
BU
Manual Lockout
72
#
BU
Internal Fault Basic Unit
81
#
ACT
Fault Feedback Air Actuator
82
#
ACT
Fault Feedback Gas (Oil) Actuator
83
#
ACT
Fault Feedback Oil Actuator
84
#
ACT
Fault Feedback Aux Actuator
86
#
LC
Fault Feedback Load Controller
87
#
AZL
Fault Feedback AZL
88
#
All
1
All
Fault Feedback Actuator
2
All
Fault Feedback Load Controller
3
All
Fault Feedback AZL
91
-
ACT
Fault Feedback Air Actuator
92
-
ACT
Fault Feedback Gas (Oil) Actuator
93
-
ACT
Fault Feedback Oil Actuator
94
-
ACT
Fault Feedback Aux Actuator
152/157
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
13 Addendum 1: List of error messages of LMV51... system
Page has an undefined status
Last backup restore invalid (was interrupted)
Fault when copying a parameter page
Fault in connection with EEPROM initialization
Fault when restoring the lockout information
Lockout was made manually via contact
Plausibility fault during fault entry
Basic unit has detected a wrong status of the air
actuator
Basic unit has detected a wrong status of the gas
actuator
Basic unit has detected a wrong status of the oil
actuator
Basic unit has detected a wrong status of the
auxiliary actuator
Basic unit has detected a wrong status of the
internal load controller
Basic unit has detected a wrong status of the
AZL51...
Plausibility fault network managem ent
Undefined fault class of ACT
Undefined fault class of LC
Undefined fault class of AZL51...
Basic unit has detected a ROM-CRC fault in the
air actuator when checking the actuator's
feedback signal
Basic unit has detected a ROM-CRC fault in the
gas actuator when checking the actuator's
feedback signal
Basic unit has detected a ROM-CRC fault in the
oil actuator when checking the actuator's
feedback signal
Basic unit has detected a ROM-CRC fault in the
auxiliary actuator when checking the actuator's
feedback signal
Reset the unit.
!Caution! If this fault occurred while setting the parameters: Check the
parameters changed last to ensure they are correct.
If resetting does not solve the problem: Restore the parameters of the AZL51...
Otherwise, replace the basic unit
Repeat backup restore
1. Make a reset
2. Restore data with the AZL51...
1. Make a reset
2. Restore data with the AZL51...
Lockout by external reset / lockout contact can be negated by pressing the
button again
*1)
If fault occurs sporadically: Improve EMC
If fault occurs permanently: Replace the faulty air actuator
If fault occurs sporadically: Im prove EMC
If fault occurs permanently: Replace the faulty gas actuator
If fault occurs sporadically: Im prove EMC
If fault occurs permanently: Replace the faulty oil actuator
If fault occurs sporadically: Im prove EMC
If fault occurs perm anently:Replace the faulty auxiliary actuator
*1)
If fault occurs sporadically: Im prove EMC
If fault occurs permanently: Replace the faulty AZL51...
If fault occurs sporadically: Im prove EMC
If fault occurs perm anently: Replace the faulty unit (see diagnostic code) or the
basic unit
If fault occurs sporadically: Im prove EMC
If fault occurs permanently: Replace the faulty air actuator
If fault occurs sporadically: Im prove EMC
If fault occurs permanently: Replace the faulty gas actuator
If fault occurs sporadically: Improve EMC
If fault occurs permanently:Replace the faulty oil actuator
If fault occurs sporadically: Improve EMC
If fault occurs perm anently: Replace the faulty auxiliary actuator
CC1P7550en