Siemens LMV51 Series Basic Documentation page 115

Burner control with integrated fuel / air ratio control and load control for forced-draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

ProductID
SW Version
SystemConfig
LC_OptgMode
Inp3Config_C/V
TempLimiter
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
6 Display and operating unit AZL51...
1 AirActuator
ASN
ProductionDate
SerialNumber
ParamSatz Code
ParamSatz Vers
2 GasActuat(Oil)
ASN
ProductionDate
SerialNumber
ParamSatz Code
ParamSatz Vers
3 OilActuator
ASN
ProductionDate
SerialNumber
ParamSatz Code
ParamSatz Vers
4 AuxActuator
ASN
ProductionDate
SerialNumber
ParamSatz Code
ParamSatz Vers
1 AirActuator
2 GasActuat(Oil)
3 OilActuator
4 AuxActuator
TL_Thresh_Off
TL_SD_On
Inp1/2/4Sel
Inp1/4/MaxValue
Displaying the actuators' HW version
Type reference
Date of production
Serial number
Preselected parameter set: customer code
Preselected parameter set: version
Type reference
Date of production
Serial number
Preselected parameter set: customer code
Preselected parameter set: version
Type reference
Date of production
Serial number
Preselected parameter set: customer code
Preselected parameter set: version
Type reference
Date of production
Serial number
Preselected parameter set: customer code
Preselected parameter set: version
Displaying the actuators' SW version
SW version of actuator
SW version of actuator
SW version of actuator
SW version of actuator
Settings for LMV51 system configuration
Operating mode with load controller
Configuration of input 3
Temperature limiter OFF threshold, in degrees Celsius
Temperature limiter switching differential ON
Select actual value input
E1-> Pt100, TL act.
E4-> Pt1000, TL act.
E4-> Ni1000, TL act.
E2-> Temp, TL inact.
E2-> Pressure, TL inact.
E1-> Pt100 for controller + TL and E4-> Pt1000 for TL
E1-> Pt100 for controller + TL and E4-> Ni1000 for TL
No input
End of measurement range for sensor at inputs 1 and 4
User
User
1..15 characters
User
«SQM45.29»
01.01.00..31.12.99
User
-
01-01-00..12-31-99
0..65535
User
-
0..255
User
0
0..65535
User
0
User
1..15 characters
User
«SQM45.29»
01.01.00..31.12.99
User
-
01-01-00..12-31-99
0..65535
User
-
0..255
User
0
0..65535
User
0
User
1..15 characters
User
«SQM45.29»
01.01.00..31.12.99
User
-
01-01-00..12-31-99
0..65535
User
-
0..255
User
0
0..65535
User
0
User
1..15 characters
User
«SQM45.29»
01.01.00..31.12.99
User
-
01-01-00..12-31-99
0..65535
User
-
0..255
User
0
0..65535
User
0
User
0..65535
User
-
0..65535
User
-
0..65535
User
-
0..65535
User
-
User
ExtLC
User
IntLC
IntLC
IntLC o.DDC
IntLC DDCan
ExtLCanalg
ExtLC o.DDC
4..20 mA
Service
4..20 mA
0/2..10 V
Service
0..2000 °C
Service
95 °C
-50..0 % TL_Thresh_Off
Service
-5 %
Service
Pt100
Pt100
Pt1000
Ni1000
TempSensor
PressSensor
Pt100Pt1000
Pt100Ni1000
NoSensor
150 °C / 302 °F
Service
150 °C / 302 °F
400 °C / 752 °F
CC1P7550en
29.05.2002
115/157

Advertisement

Table of Contents
loading

Table of Contents