Siemens LMV51 Series Basic Documentation page 109

Burner control with integrated fuel / air ratio control and load control for forced-draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

OptgModeSelect
InterfacePC
GatewayDDCon
GatewayDDCoff
ManualOperation
SetLoad
Autom/Manual/Off
Params & Display
BurnerControl
Times
Configuration
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
6 Display and operating unit AZL51...
TimesStartup1
MinTmeStartRel
FanRunupTme
PrepurgeTmeGas
PrepurgeTmeOil
MinT_PrepurgeGas
MinT_PrepurgeOil
PrepurgeSafeGas
PrepurgeSafeOil
PreIgnitionTGas
PreIgnitionTOil
MinOnTmeOilPump
TimesStartup2
SafetyTme1Gas
SafetyTme1Oil
Interval1Gas
Interval1Oil
SafetyTme2Gas
SafetyTme2Oil
Interval2Gas
Interval2Oil
PressReacTme
TimesShutdown
MaxTmeLowFire
AfterburnTme
PostpurgeT1Gas
PostpurgeT1Oil
PostpurgeT3Gas
PostpurgeT3Oil
MinTmeHomeRun
DelayLackGas
TimesGeneral
AlarmDelay
DelayStartPrev
PostpurgeLockout
ConfigGeneral
AlarmStartPrev
NormDirectStart
IgnOilPumpStart
Operating mode selection of AZL for serial port and eBus
Setting the serial port (RS-232) of the AZL to interface
operation for PC tool
Activating the eBus port on the AZL for DDC
Deactivating the eBus port on the AZL
Menu level for activating manual operation with the
preselected load
Set target load
Selection of m anual or automatic operation
Menu level for making the parameter settings
Setting the burner control parameters
Burner control startup times 1
Minimum time for start release
Fan runup time
Prepurge time gas
Prepurge time oil
Minimum prepurge time gas
Minimum prepurge time oil
Prepurge time after safety shutdown gas
Prepurge time after safety shutdown oil
Preignition time gas
Preignition time oil
Minimum on time of oil pump
Burner control startup times 2
Safety time 1 gas
Safety time 1 oil
Interval 1 (ts1-ts2) gas
Interval 1 (ts1-ts2) oil
Safety time 2 gas
Safety time 2 oil
Interval 2 (ts2 operation) gas
Interval 2 (ts2 operation) oil
Reaction time to lack of pressure in ts1 and ts2
Burner control shutdown times
Maximum time to low-fire in operation 2
Afterburn time
Postpurge time 1 gas
Postpurge time 1 oil
Postpurge time 3 gas
Postpurge time 3 oil
Minimum time in home run phase
Basic waiting time in the event of lack of gas
General times of burner control
Time to alarm in the event of start prevention and heat
demand
Time until message on start prevention and heat demand
is delivered
Postpurge in lockout position
General parameters of burner control
W ith / without alarm in the event of start prevention and
heat demand
Normal / direct start in the event of heat demand in
phase 78
Switch-on time of ignition and oil pump
User
User
User
User
User
0..100 %, S1, S2, S3
User
Automatic
User
Automatic
Burner on
Burner off
User
User
Service
Service
t21
0.2..63 s
OEM
t22
0.2..63 s
OEM
tv
MinT_PrepurgeGas..63 min
Service
tv
MinT_PrepurgeOil..63 min
Service
tvmin
0.2..63 min
OEM
tvmin
0.2..63 min
OEM
----
MinT_PrepurgeGas..63 min
OEM
----
MinT_PrepurgeOil..63 min
OEM
t38
0.2..63 s
OEM
t38
0.2..44 s
OEM
t36
0.2..63 s
OEM
Service
ts1
1 s..MaxSafetyTGas
OEM
ts1
1 s..MaxSafetyTOil
OEM
t44
0.2..63 s
Service
t44
0.2..63 s
Service
t50
1 s..MaxSafetyTGas
OEM
t50
1 s..MaxSafetyTOil
OEM
t52
0.2..63 s
Service
t52
0.2..63 s
Service
----
0.2 s..MaxSafetyTGas
OEM
Service
t62
0.2..630 s
Service
t70
0.2..63 s
OEM
t74
0.2..63 min
OEM
t74
0.2..63 min
OEM
t78
0.2..63 min
Service
t78
0.2..63 min
Service
t10
0.2..63 s
OEM
----
MinTmeHomeRun ..63 s
OEM
Service
0.4..630 s
Service
0.4..630 s
Service
0.2..63 min
OEM
Service
Service
deactivated
Service
deactivated
activated
NormalStart
OEM
NormalStart
DirectStart
on in Ph38
OEM
on in Ph38
on in Ph22
-
1 s
2 s
20 s
15 s
20 s
15 s
20 s
15 s
2 s
2 s
1 s
2 s
2 s
2 s
2 s
2 s
2 s
2 s
2 s
1 s
45 s
8 s
0.2 s
0.2 s
5 s
5 s
1 s
10 s
35 s
35 s
0.2 s
109/157
CC1P7550en
29.05.2002