7550d09E
Change of load / position with several points
Using this method, up to 15 points can be defined.
6. Shutdown
On the menu: «Params & Display» ® «Ratio Control» ® «Settings Gas / Oil»
® «Special Positions» ® «Autom / Manual / Off»
«Manual Operation» à «Autom / Manual / Off» to «Burner off»
or on:
and confirm
7. Setting the postpurge positions
The system shuts down and stops in phase «Driving to postpurge 72».
Now, the postpurge positions on menu «Special positions» can be set.
Then, on «Program Stop», set to «deactivated».
The system continues the shutdown sequence and stops in phase «Standby 12».
Basic Documentation LMV51...
6 Display and operating unit AZL51...