Table 4A Electrical Specifications H**A Series; Table 4B Electrical Specifications H**L Series - Bard H24A4-A Installation Instructions Manual

Wall mounted packaged air conditioner
Table of Contents

Advertisement

No.
Rated
Field
MODEL
Volts &
Power
Phase
Circuits
H24A2-A00, A0Z
1
A04
1
A05
230/208-1
1
A08
1
A10
1
H36A2-A00*,
1
A0Z*
1
A05*
230/208-1
1
A08
1
A10*
1 or 2
A15
H42A2-A00, A0Z
1
A05
1
A10
230/208-1
1
A15
1 or 2
A20
1 or 2
H48A2-A00, A0Z
1
A05
1
A10
230/208-1
1
A15
1 or 2
A20
1 or 2
H60A2-A00, A0Z
1
A05
1
A10
230/208-1
1
A15
1 or 2
A20
1 or 2
 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
 Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.
Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity
Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
* Top outlet supply option is available only factory installed and only on the selected models.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National
Electrical Code and all local codes.
No.
Rated
Field
MODEL
Volts &
Power
Phase
Circuits
H24L2-A00, A0Z
1
A05
1
230/208-1
A08
1
A10
1
H36L2-A00*,
1
A0Z*
1
A05*
230/208-1
1
A10*
1 or 2
A15
H42L2-A00, A0Z
1
A05
1
230/208-1
A10
1
A15
1 or 2
H48L2-A00, A0Z
1
A05
1
230/208-1
A10
1
A15
1 or 2
H60L2-A00, A0Z
1
A05
1
230/208-1
A10
1
A15
1 or 2
 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
 Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.
Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity
Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
* Top outlet supply option is available only factory installed and only on the selected models.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National
Electrical Code and all local codes.
Manual 2100-639A
Page
20 of 28
TABLE 4A
Electrical Specifications H**A Series
Single Circuit
Maximum
Minimum
Field
External
Circuit
Power
Fuse or Ckt.
Ampacity
Wire Size
Brkr.
21
30
10
25
30
10
30
30
10
46
50
8
56
60
6
29
35
8
32
35
8
47
50
8
58
60
6
84
90
4
32
50
8
32
50
8
58
60
6
84
90
4
110
125
2
39
50
8
39
50
8
58
60
6
84
90
4
110
125
2
42
60
8
42
60
8
60
60
6
86
90
3
112
125
2
TABLE 4B
Electrical Specifications H**L Series
Single Circuit
Maximum
Minimum
Field
External
Circuit
Power
Fuse or Ckt.
Ampacity
Wire Size
Brkr.
21
30
10
30
30
10
46
50
8
56
60
6
29
35
8
32
35
8
58
60
6
84
90
4
32
50
8
32
50
8
58
60
6
84
90
4
39
50
8
39
50
8
58
60
6
84
90
4
42
60
8
42
60
8
60
60
6
86
90
3
 Minimum
 Maximum
Circuit
External Fuse or
Ground
Ampacity
Ckt. Breaker
Wire
Ckt. A
Ckt. B
Ckt. A
10
10
10
10
10
10
10
10
10
8
58
26
60
10
10
10
8
58
26
60
6
58
52
60
10
10
10
8
58
26
60
6
58
52
60
10
10
10
8
60
26
60
6
60
52
60
 Minimum
 Maximum
Circuit
External Fuse or
Ground
Ampacity
Ckt. Breaker
Wire
Ckt. A
Ckt. B
Ckt. A
10
10
10
10
10
10
10
8
58
26
60
10
10
10
8
58
26
60
10
10
10
8
58
26
60
10
10
10
8
60
26
60
Dual Circuit
Field Power
Ground
Wire Size
Wire Size
Ckt. B
Ckt. A
Ckt. B
Ckt. A
30
6
10
10
30
6
10
10
60
6
6
10
30
6
10
10
60
6
6
10
30
6
10
10
60
6
6
10
Dual Circuit
Field Power
Ground
Wire Size
Wire Size
Ckt. B
Ckt. A
Ckt. B
Ckt. A
30
6
10
10
30
6
10
10
30
6
10
10
30
6
10
10
Ckt. B
10
10
10
10
10
10
10
Ckt. B
10
10
10
10