a48-7910
LEGEND
IAQ — Indoor Air Quality
LA
— Low Ambient Lockout Device
POT — Potentiometer
OAT — Outdoor-Air Temperature
RAT — Return-Air Temperature
NOTE 1
RUN
NOTE 2
50HJ540573
ACTUATOR
ASSEMBLY
DIRECT DRIVE
ACTUATOR
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
TYPICAL WIRING SCHEMATICS — 580F036-151 (cont)
NOTE:
Potentiometer Defaults Settings:
Power Exhaust
Middle
Minimum Pos.
Fully Closed
DCV Max.
Middle
DCV Set
Middle
Enthalpy
C Setting
EconoMi$er IV Wiring — 580F036-151 Units
500 OHM
RESISTOR
-
+
OPTIONAL CO
2
SENSOR 4 - 20 mA
OUTPUT
EconoMi$er2 Wiring — 580F036-151 Units
ECONOMIZER NOTES:
1. 620 ohm, 1 watt 5% resister should be removed only when using differential
enthalpy or dry bulb.
2. If a separate field supplied 24v transformer is used for the IAQ sensor
power supply, it cannot have the secondary of the transformer grounded.
3. For field installed remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT to the minimum
position.
VIOLET
PINK
a48-8209
84
BLACK
4
3
5
BLUE
2
8
6
7
RED
1
10
11
9
WHITE
12
ECONOMISER2 PLUG