Bryant 579F User Manual page 157

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

581C024 (2Tons)
AIRFLOW
0.1
(Cfm)
Rpm
Bhp
Rpm
600
490
0.08
700
519
0.09
800
537
0.1
900
560
0.13
1000
589
0.15
LEGEND
Bhp
— Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field-
supplied drive.
581C036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)*
Airflow
0.2
(Cfm)
Rpm
Bhp
900
553
0.14
1000
582
0.16
1100
612
0.20
1200
643
0.23
1300
675
0.28
1400
707
0.33
1500
740
0.38
581C036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
Airflow
1.2
(Cfm)
Rpm
Bhp
900
1019
0.64
1000
1042
0.70
1100
1065
0.77
1200
1089
0.84
1300
1113
0.92
1400
1138
1.01
1500
1163
1.10
LEGEND
Bhp
— Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field-
plied drive.
581C036 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Airflow
0.2
(Cfm)
Rpm
Bhp
900
553
0.14
1000
582
0.16
1100
612
0.20
1200
643
0.23
1300
675
0.28
1400
707
0.33
1500
740
0.38
PERFORMANCE DATA — 581C
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS
EXTERNALSTATIC PRESSURE (in. wg)
0.2
0.4
Bhp
Rpm
Bhp
521
0.08
597
0.14
557
0.09
623
0.16
582
0.12
650
0.19
610
0.14
681
0.22
640
0.16
707
0.26
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS
0.4
Watts
Rpm
Bhp
Watts
134
681
0.22
221
163
707
0.26
257
196
734
0.30
297
234
762
0.34
343
277
790
0.40
394
326
819
0.45
452
382
849
0.52
515
1.4
Watts
Rpm
Bhp
Watts
640
1084
0.76
760
700
1107
0.83
825
765
1130
0.90
896
837
1153
0.98
974
915
1177
1.06
1058
1000
1201
1.15
1149
1092
0.4
Watts
Rpm
Bhp
Watts
134
681
0.22
221
163
707
0.26
257
196
734
0.30
297
234
762
0.34
343
277
790
0.40
394
326
819
0.45
452
382
849
0.52
515
0.6
0.8
Rpm
Bhp
Rpm
703
0.21
788
729
0.24
816
751
0.27
845
783
0.32
870
808
0.36
894
See page 107 for general fan performance notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
External Static Pressure (in. wg)
0.6
Rpm
Bhp
Watts
782
0.32
316
807
0.36
358
833
0.41
405
859
0.46
458
886
0.52
517
913
0.58
581
941
0.66
653
External Static Pressure (in. wg)
1.6
Rpm
Bhp
Watts
1146
0.89
885
1168
0.96
956
1190
1.04
1032
1213
1.12
1115
See page 107 for general fan performance notes.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
sup-
External Static Pressure (in. wg)
0.6
Rpm
Bhp
Watts
782
0.32
316
807
0.36
358
833
0.41
405
859
0.46
458
886
0.52
517
913
0.58
581
941
0.66
653
157
1.0
Bhp
Rpm
Bhp
0.29
868
0.37
0.32
892
0.41
0.37
927
0.47
0.42
947
0.53
0.47
971
0.58
0.8
Rpm
Bhp
Watts
Rpm
870
0.42
417
948
894
0.47
466
971
919
0.52
519
995
944
0.58
579
1020
969
0.65
644
1044
996
0.72
716
1070
1023
0.80
795
1096
1.8
Rpm
Bhp
Watts
Rpm
1203
1.02
1016
1258
1225
1.10
1091
1247
1.18
1173
0.8
Rpm
Bhp
Watts
Rpm
870
0.42
417
948
894
0.47
466
971
919
0.52
519
995
944
0.58
579
1020
969
0.65
644
1044
996
0.72
716
1070
1023
0.80
795
1096
1.0
Bhp
Watts
0.53
526
0.58
580
0.64
639
0.71
705
0.78
777
0.86
855
0.95
941
2.0
Bhp
Watts
1.16
1152
1.0
Bhp
Watts
0.53
526
0.58
580
0.64
639
0.71
705
0.78
777
0.86
855
0.95
941