Bryant 579F User Manual page 132

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

SOUND
UNIT
RATING
581B
(dB)
036,048
76
060,072
80
090,102
82
120
84
150
86
LEGEND
dB
— Sound Levels (decibels)
COMPONENT
Vertical EconoMi$er IV and EconoMi$er2
Horizontal EconoMi$er IV and EconoMi$er2
LEGEND
FIOP —
Factory-Installed Option
COMPONENT
Vertical EconoMi$er IV and EconoMi$er2
Horizontal EconoMi$er IV and EconoMi$er2
LEGEND
FIOP — Factory-Installed Option
PERFORMANCE DATA (cont)
OUTDOOR SOUND POWER (TOTAL UNIT)
63
125
250
55.9
66.0
64.0
59.1
68.9
68.7
62.2
69.3
71.5
64.6
71.1
73.3
63.7
69.9
72.5
EVAPORATOR-FAN MOTOR EFFICIENCY
UNIT SIZE 581B
036,048
060
072
090,102
120
150
*Single phase/3 phase.
NOTES:
1. Convert bhp to watts using the following formula:
bhp (746)
watts =
motor efficiency
2.
The EPACT (Energy Policy Act of 1992) regulates energy requirements
for specific types of indoor fan motors. Motors regulated by EPACT
include any general purpose, T-frame (three-digit, 143 and larger),
single-speed, foot mounted, polyphase, squirrel cage induction motors
of NEMA (National Electrical Manufacturers Association) design A and
B, manufactured for use in the United States. Ranging from 1 to 200
Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz
power. If a motor does not fit into these specifications, the motor does
not have to be replaced by an EPACT-compliant energy-efficient motor.
Variable-speed motors are exempt from EPACT compliance require-
ments. Therefore, the indoor fan motors for Bryant 581B036-150 units
are exempt from these requirements.
ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 581B036-072
600
800
0.10
0.20
ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 581B090-150
2250
2500
2750
0.06
0.075
0.09
0.1
0.125
OCTAVE BANDS
500
1000
66.2
68.4
71.9
74.0
74.7
76.2
76.9
77.6
78.2
81.1
NOTE: The indoor sound power is available in Bryant's Electronic Catalog
program (ECAT) for specific operating parameters.
EFFICIENCY%
75
74/84*
84
80
85
87
CFM
1000
1250
1500
1750
0.35
0.045
0.065
0.08
0.1
*The static pressure must be added to external static pressure. The sum and the
evaporator entering-air cfm should be used in conjunction with the Fan Perfor-
mance tables to determine indoor blower rpm and watts.
CFM
3000
3250
3500
3750
4000
0.115
0.13
0.15
0.17
0.195
0.15
0.18
0.21
0.25
0.275
*The static pressure must be added to external static pressure. The sum and the
evaporator entering-air cfm should be used in conjunction with the Fan Perfor-
mance tables to determine indoor blower rpm and watts.
132
2000
4000
64.5
61.7
68.9
65.7
72.9
68.7
73.7
70.6
77.3
73.3
2000
2250
2500
2750
0.12
0.145
0.175
0.22
0.125
0.15
0.18
0.225
4250
4500
4750
5000
5250
0.22
0.25
0.285
0.325
0.36
0.3
0.34
0.388
8000
57.3
59.0
61.5
63.7
66.8
3000
0.255
0.275
6250

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

581a581b581c580f