Bryant 579F User Manual page 193

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

579F216360 and 240360 (18 AND 20 TONS) *
Airflow
0.2
(Cfm)
Rpm
Bhp
Watts
5,500
795
2.43
6,000
854
2.92
6,500
914
3.46
7,000
975
4.06
7,500
1037
4.72
8,000
1099
5.44
8,500
1161
6.22
9,000
1223
7.07
9,500
1286
7.98
10,000
1349
8.95
579F216360 and 240360 (18 AND 20 TONS) * (cont)
Airflow
1.4
(Cfm)
Rpm
Bhp
Watts
5,500
1173
4.44
6,000
1211
4.95
6,500
1252
5.53
7,000
1295
6.16
7,500
1340
6.85
8,000
1388
7.60
8,500
1436
8.41
9,000
1486
9.28
9,500
1538
10.22
10,000
LEGEND
Bhp
— Brake Horsepower
Watts — Input Watts to Motor
*Standard low-medium static drive range for the 216 size is 910 to 1095 rpm.
Standard low-medium static drive range for the 240 size is 1002 to 1225 rpm.
Alternate high-static drive range for the 216 size is 1069 to 1287. Alternate high-
static drive range for the 240 size is 1193 to 1458 rpm. Other rpms require a field-
supplied drive.
579F300360 (25 TONS) *
Airflow
0.2
(Cfm)
Rpm
Bhp
Watts
7,000
992
4.05
7,500
1055
4.77
8,000
1118
5.58
8,500
1182
6.46
9,000
1246
7.42
9,500
1310
8.47
10,000
1374
9.61
10,500
1439
10.84
11,000
1503
12.17 10,059
11,250
1536
12.86 10,636
579F300360 (25 TONS) * (cont)
Available External Static Pressure (in. wg)
Airflow
1.4
(Cfm)
Rpm
Bhp
Watts
7,000
1311
6.51
7,500
1358
7.30
8,000
1406
8.17
8,500
1456
9.12
9,000
1507
10.15
9,500
10,000
10,500
11,000
11,250
LEGEND
Bhp
— Brake Horsepower
Watts — Input Watts to Motor
*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high-
static drive range is 1332 to 1550. Other rpms require a field-supplied drive.
1. Static pressure losses (i.e., EconoMi$er IV) must be added to external static
pressure before entering Fan Performance table.
2. Interpolation is permissible. Do not extrapolate.
3. Fan performance is based on wet coils, clean filters, and casing losses. See
Accessory/FIOP Static Pressure table on page 193.
PERFORMANCE DATA — 579F (cont)
FAN PERFORMANCE — 579F180-300 UNITS (cont)
Available External Static Pressure (in. wg)
0.4
Rpm
Bhp
Watts
Rpm
2043
866
2.74
2306
934
2452
921
3.24
2722
984
2909
977
3.79
3184
1036
3414
1034
4.39
3695
1090
3969
1092
5.06
4255
1145
4575
1150
5.79
4866
1201
5232
1210
6.57
5529
1258
5943
1270
7.43
6245
1315
6708
1331
8.34
7014
1374
7528
1392
9.32
7839
1433
Available External Static Pressure (in. wg)
1.6
Rpm
Bhp
Watts
Rpm
3732
1227
4.80
4036
1279
4165
1263
5.32
4471
1313
4646
1302
5.89
4954
1350
5176
1343
6.52
5487
1389
5756
1386
7.22
6070
1431
6388
1431
7.97
6704
1474
7071
1478
8.79
7390
1520
7807
1527
9.67
8130
8597
Available External Static Pressure (in. wg)
0.4
Rpm
Bhp
Watts
Rpm
3,348
1051
4.44
3,668
1106
3,947
1110
5.17
4,277
1162
4,610
1170
5.99
4,950
1220
5,339
1231
6.88
5,690
1278
6,136
1292
7.86
6,498
1337
7,005
1354
8.92
7,377
1397
7,947
1416
10.07
8,329
1457
8,964
1479
11.32
9,356
1518
1542
12.65 10,460
1.6
Rpm
Bhp
Watts
Rpm
5385
1359
6.96
5751
1405
6039
1403
7.76
6412
1448
6767
1560
8.63
7137
1492
7541
1498
9.59
7929
1539
8393
1548
10.63
8790
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
0.6
0.8
Bhp
Watts
Rpm
Bhp
Watts
3.07
2578
998
3.40
2856
3.57
3998
1044
3.90
3281
4.12
3465
1093
4.46
3752
4.73
3981
1144
5.08
4272
5.41
4546
1196
5.76
4842
6.14
5162
1249
6.50
5462
6.93
5829
1304
7.29
6134
7.79
6550
1360
8.16
6869
8.71
7324
1416
9.08
7638
9.70
8154
1473
10.07
8471
1.8
1.9
Bhp
Watts
Rpm
Bhp
Watts
5.17
4345
1304
5.35
4502
5.69
4782
1337
5.87
4939
6.26
5267
1373
6.56
5425
6.90
5802
1412
7.09
5961
7.60
6387
1452
7.79
6547
8.35
7240
1495
8.54
7186
9.17
7713
1540
9.37
7876
Refer to this page for general Fan Performance Data notes.
NOTE: Maximum continuous bhp for the 216 size is 5.90. Maximum continuous
bhp for the 240 size is 8.70 (208/230 and 575 v) or 9.50 (460 v). The maximum
continuous watts for the 216 size is 5180. The maximum continuous watts for the
240 size is 7915 (208/230 and 575 v) or 8640 (460 v). Do not adjust motor rpm
such that motor maximum bhp and/or watts is exceeded at the maximum operat-
ing cfm.
0.6
0.8
Bhp
Watts
Rpm
Bhp
Watts
4.83
3995
1160
5.24
4331
5.58
4615
1214
6.00
4960
6.41
5298
1268
6.84
5653
7.31
6047
1324
7.75
6411
8.30
6865
1381
8.75
7239
9.38
7754
1439
9.84
8137
10.54
8715
1497
11.02
9107
11.79
9752
1.8
Bhp
Watts
6.00
6124
6.84
6792
7.75
7524
8.75
8323
Refer to this page for general Fan Performance Data notes.
NOTE: Maximum continuous bhp is 10.20 (208/230 and 575 v) or 11.80 (460 v)
and the maximum continuous watts are 9510 (208/230 and 575 v) or 11,000
(460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is
exceeded at the maximum operating cfm.
4. Extensive motor and drive testing on these units ensures that the full horse-
power and watts range of the motor can be utilized with confidence. Using
fan motors up to the watts or bhp rating shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
5. Use of a field-supplied motor may affect wire sizing. Contact your Bryant
representative for details.
193
1.0
Rpm
Bhp
Watts
Rpm
1059
3.74
3142
1117
1102
4.25
3570
1158
1148
4.81
4045
1201
1196
5.43
4569
1246
1256
6.12
5142
1294
1297
6.86
5766
1343
1349
7.66
6443
1393
1403
8.53
7171
1445
1457
9.46
7954
1498
2.0
Rpm
Bhp
Watts
1329
5.54
4629
1361
6.06
5097
1396
6.64
5584
1434
7.28
6121
1474
7.98
6709
1516
8.74
7348
1.0
Rpm
Bhp
Watts
Rpm
1212
5.65
4675
1262
1263
6.43
5312
1311
1315
7.27
6014
1361
1369
8.20
6782
1413
1424
9.21
7618
1466
1480
10.31
8525
1520
1537
11.50
9504
1.2
Bhp
Watts
4.08
3434
4.60
3865
5.16
4343
5.79
4870
6.48
5447
7.22
6075
8.03
6755
8.90
7487
9.84
8274
1.2
Bhp
Watts
6.08
5026
6.86
5672
7.72
6382
8.66
7158
9.68
8003
10.79
8918

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

581a581b581c580f

Table of Contents