Bryant 579F User Manual page 244

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

581A181 (15 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE
Temp (F)
4500/0.02
Air Entering
Condenser
(Edb)
57
62
67
TC
166
179
193
75
SHC
165
152
129
kW
10.4
10.6
10.7
TC
162
174
189
85
SHC
162
150
127
kW
11.7
11.9
12.1
TC
158
169
182
95
SHC
158
148
126
kW
12.7
12.9
13.1
TC
153
163
178
105
SHC
153
145
123
kW
14.1
14.2
14.4
TC
148
156
171
115
SHC
148
141
120
kW
15.5
15.6
15.8
TC
143
149
163
125
SHC
143
138
117
kW
17.0
17.1
17.4
581A181 (15 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B AND C OFF
Temp (F)
4500/0.12
Air Entering
Condenser
(Edb)
50
55
TC
55
57
65
SHC
34
32
kW
4.4
4.5
TC
42
44
75
SHC
22
19
kW
4.8
4.8
TC
29
30
85
SHC
9
6
kW
5.2
5.2
TC
15
16
95
SHC
–3
–7
kW
5.6
5.6
581A181 (15 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C OFF
Temp (F)
4500/0.12
Air Entering
Condenser
(Edb)
50
55
TC
81
84
65
SHC
34
32
kW
7.8
7.9
TC
62
64
75
SHC
22
19
kW
8.5
8.5
TC
42
44
85
SHC
10
6
kW
9.2
9.2
TC
23
24
95
SHC
–2
–7
kW
9.9
9.9
LEGEND
BF
— Bypass Factor
Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW
— Compressor Motor Power Input
ldb
— Leaving Dry-Bulb
lwb — Leaving Wet-Bulb
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC
— Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
t
= t
ldb
edb
1.10 x cfm
t
= Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
lwb
rator coil (h
)
lwb
total capacity (Btuh)
h
= h
lwb
ewb
4.5 x cfm
Where: h
= Enthalpy of air entering evaporator coil
ewb
PERFORMANCE DATA (cont)
COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION
Air Entering Evaporator — Cfm/BF
5250/0.03
Air Entering Evaporator — Ewb (F)
72
57
62
67
72
214
175
186
202
221
108
175
166
140
115
10.9
10.5
10.6
10.8
11.0
209
171
180
195
216
106
171
163
137
113
12.3
11.8
12.0
12.1
12.4
202
166
174
187
209
104
166
160
134
110
13.3
12.9
13.0
13.2
13.4
195
162
168
181
201
101
162
157
133
107
14.7
14.2
14.3
14.5
14.8
188
157
161
176
193
98
157
153
130
104
16.1
15.6
15.7
15.9
16.2
179
151
153
168
184
95
151
149
126
101
17.7
17.2
17.2
17.5
17.8
5250/0.14
Evaporator Air — Relative Humidity (%)
60
50
55
60
59
56
58
59
30
36
34
32
4.5
4.4
4.5
4.5
45
43
44
46
17
23
21
18
4.8
4.8
4.8
4.8
31
29
31
32
3
11
8
5
5.3
5.2
5.2
5.3
17
16
17
18
–11
–1
–5
–9
5.6
5.6
5.6
5.6
5250/0.14
Evaporator Air — Relative Humidity (%)
60
50
55
60
86
82
85
87
30
36
33
31
7.9
7.8
7.9
7.9
66
62
65
67
16
24
21
18
8.5
8.5
8.5
8.5
46
43
45
46
2
12
8
4
9.3
9.2
9.2
9.3
26
23
25
26
–11
0
–5
–9
9.9
9.9
9.9
9.9
6000/0.04
57
62
67
72
57
183
191
208
227
190
183
178
150
121
190
10.6
10.7
10.9
11.1
10.7
179
185
200
222
186
179
175
147
119
186
11.9
12.0
12.2
12.5
12.0
174
179
194
214
181
174
172
145
116
181
13.0
13.0
13.2
13.5
13.1
169
172
188
206
175
169
167
142
113
175
14.3
14.3
14.6
14.8
14.4
163
165
180
197
169
163
162
139
110
169
15.7
15.8
16.0
16.3
15.8
157
158
171
188
163
157
156
136
107
163
17.3
17.3
17.6
17.8
17.4
Evaporator Air Quantity — Cfm/BF
6000/.015
50
55
60
56
58
60
37
35
33
4.4
4.5
4.5
43
45
46
25
22
20
4.8
4.8
4.8
30
31
32
13
10
7
5.2
5.2
5.3
16
18
18
1
–3
–7
5.6
5.6
5.6
Evaporator Air Quantity — Cfm/BF
6000/.015
50
55
60
83
86
88
37
35
33
7.8
7.9
7.9
63
66
68
25
22
20
8.5
8.5
8.5
43
45
47
14
10
6
9.2
9.2
9.3
24
25
27
2
–3
–7
9.9
9.9
9.9
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
BYPASS
79
FACTOR
81
(BF)
.05
1.04
.10
.98
.20
.87
.30
.76
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
244
6750/0.04
62
67
72
57
195
212
232
197
189
159
127
197
10.7
10.9
11.2
10.8
189
205
226
192
185
156
125
192
12.1
12.3
12.5
12.1
183
198
218
187
180
154
122
187
13.1
13.3
13.6
13.1
177
191
209
181
175
151
119
181
14.4
14.6
14.9
14.5
170
183
201
174
169
148
116
174
15.8
16.1
16.3
15.9
163
174
190
167
163
144
112
167
17.4
17.6
17.9
17.5
6750/0.18
50
55
60
50
57
59
60
57
38
36
35
40
4.4
4.5
4.5
4.4
43
45
46
44
26
24
21
28
4.8
4.8
4.8
4.8
30
32
33
31
14
11
8
16
5.2
5.2
5.3
5.2
17
18
19
17
2
–2
–5
4
5.6
5.6
5.6
5.6
6750/0.18
50
55
60
50
84
87
89
85
39
36
34
40
7.8
7.9
7.9
7.8
64
66
68
64
27
24
21
28
8.5
8.5
8.5
8.5
44
46
48
44
15
11
8
16
9.2
9.2
9.3
9.2
24
26
27
24
3
–1
–6
5
9.9
9.9
9.9
9.9
ENTERING AIR DRY-BULB TEMP (F)
78
77
76
82
83
84
Correction Factor
2.07
3.11
4.14
1.96
2.94
3.92
1.74
2.62
3.49
1.53
2.29
3.05
7500/0.05
62
67
72
199
216
236
196
168
133
10.8
11.0
11.2
194
208
230
192
164
131
12.1
12.3
12.6
188
201
221
187
163
128
13.2
13.4
13.6
181
194
213
181
160
125
14.5
14.7
14.9
175
185
203
174
156
122
15.9
16.1
16.4
167
176
192
167
153
118
17.5
17.6
17.9
7500/0.18
55
60
59
61
38
36
4.5
4.5
45
47
25
23
4.8
4.8
32
33
12
9
5.2
5.3
18
19
0
–4
5.6
5.6
7500/0.18
55
60
87
90
38
36
7.9
7.9
67
69
25
22
8.5
8.5
46
48
13
9
9.2
9.3
26
27
0
–4
9.9
9.9
75
under 75
85
over 85
Use for-
5.18
mula
4.90
shown
4.36
below.
3.82

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

581a581b581c580f

Table of Contents