UNIT
UNIT
579F
VOLTAGE
208/230
180
460
575
208/230
216
460
575
208/230
240
460
575
208/230
300
460
575
LEGEND
BHP — Brake Horsepower
BkW — Brake Kilowatts
*Extensive motor and electrical testing on these units ensures that the full horsepower (brake kilowatt) range
of the motors can be utilized with confidence. Using fan motors up to the horsepower (brake kilowatt) ratings
shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected.
NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the
Energy Policy Act of 1992 (EPACT) effective October 24, 1997.
PERFORMANCE DATA — 579F (cont)
EVAPORATOR-FAN MOTOR DATA
MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
4.25
4.25
3.45
5.90
8.70
9.50
8.70
10.20
11.80
10.20
EVAPORATOR-FAN MOTOR EFFICIENCY
UNIT
579F
180 (3.0 Hp)
180 (3.7 Hp)
216 (5 Hp)
240 (7.5 Hp)
300 (10 Hp)
NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
MAXIMUM
ACCEPTABLE
ACCEPTABLE
CONTINUOUS
OPERATING
BkW*
3.17
3.17
2.59
4.40
6.49
7.08
6.49
7.61
8.80
7.61
MOTOR EFFICIENCY
(%)
81.7
85.8
87.5
88.5
89.5
196
MAXIMUM
MAXIMUM
AMP DRAW
WATTS
3,775
10.5
3,775
4.8
3,065
3.9
15.8
5,180
7.9
6.0
7,915
22.0
8,640
13.0
7,915
10.0
9,510
28.0
11,000
14.6
9,510
13.0