579F216 (18 Tons)
Temp (F)
Air Entering
Condenser
(Edb)
54/0.49
58/0.31
TC
194
198
75
SHC
194
178
kW
13.6
13.7
TC
189
192
85
SHC
189
176
kW
15.1
15.2
TC
183
184
95
SHC
183
181
kW
16.8
16.8
TC
177
178
105
SHC
177
178
kW
18.6
18.6
TC
171
171
115
SHC
171
171
kW
20.5
20.5
TC
170
170
117
SHC
170
170
kW
20.9
20.9
TC
168
168
120
SHC
168
168
kW
21.5
21.5
579F216 (18 Tons) (cont)
Temp (F)
Air Entering
Condenser
(Edb)
54/0.58
58/0.42
TC
209
209
75
SHC
209
209
kW
13.9
13.9
TC
203
204
85
SHC
203
204
kW
15.5
15.5
TC
197
197
95
SHC
197
197
kW
17.2
17.2
TC
191
191
105
SHC
191
191
kW
19.0
19.0
TC
184
184
115
SHC
184
184
kW
21.0
21.0
TC
183
183
117
SHC
183
183
kW
21.3
21.4
TC
180
180
120
SHC
180
180
kW
21.9
22.0
LEGEND
BF
Bypass Factor
Edb
Entering Dry-Bulb
Ewb —
Entering Wet-Bulb
kW
Compressor Motor Power Input
ldb
Leaving Dry-Bulb
lwb
Leaving Wet-Bulb
SHC —
Sensible Heat Capacity (1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
t
=
t
ldb
edb
1.10 x cfm
Wet-bulb temperature corresponding to enthalpy of air
t
=
lwb
leaving evaporator coil (h
total capacity (Btuh)
h
= h
lwb
ewb
4.5 x cfm
Where: h
= Enthalpy of air entering evaporator coil
ewb
PERFORMANCE DATA — 579F (cont)
COOLING CAPACITIES (cont)
5400
62/0.20
67/0.18
72/0.16
76/0.19
206
223
243
169
146
121
13.9
14.2
14.6
200
217
235
166
143
118
15.4
15.9
16.3
193
209
227
162
140
115
17.1
17.6
18.0
185
201
218
159
137
112
18.8
19.3
19.8
177
192
209
154
133
109
20.7
21.2
21.8
176
191
207
154
132
108
21.1
21.6
22.1
173
188
204
152
131
107
21.7
22.2
22.7
7000
62/0.29
67/0.21
72/0.20
76/0.20
215
232
251
189
162
132
14.1
14.5
14.9
209
224
243
185
159
129
15.7
16.1
16.5
202
216
235
180
156
126
17.4
17.8
18.2
195
208
225
175
152
123
19.2
19.5
20.0
188
199
215
168
149
119
21.1
21.5
22.0
187
197
214
166
148
118
21.5
21.8
22.4
185
194
210
163
147
117
22.1
22.4
23.0
)
lwb
Evaporator Air Quantity — Cfm
Evaporator Air — Ewb (F)/BF
80/0.05
54/0.53
58/0.35
260
277
200
203
99
79
200
191
15.0
15.2
13.7
13.8
252
269
195
195
97
76
195
195
16.6
16.9
15.3
15.3
243
189
190
94
189
190
18.4
17.0
17.0
234
183
185
91
183
185
20.2
18.8
18.6
224
176
177
88
176
177
22.1
20.7
20.7
222
175
175
87
175
175
22.5
21.1
21.1
173
173
173
173
21.7
21.7
Evaporator Air Quantity — Cfm
Evaporator Air — Ewb (F)/BF
80/0.05
54/0.62
58/0.48
268
216
217
106
216
217
15.2
14.1
14.1
260
211
211
103
211
211
16.9
15.7
15.7
251
204
204
100
204
204
18.7
17.4
17.4
241
197
197
97
197
197
20.5
19.2
19.2
230
190
190
94
190
190
22.4
21.1
21.1
228
188
188
93
188
188
22.7
21.5
21.5
186
186
186
186
22.1
22.1
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
BYPASS
79
FACTOR
81
(BF)
0.05
1.04
0.10
0.98
0.20
0.87
0.30
0.76
0.40
0.65
0.50
0.55
0.60
0.44
0.70
0.33
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
185
6000
62/0.23
67/0.19
72/0.17
76/0.19
210
227
246
263
177
152
125
102
14.0
14.4
14.7
15.1
204
220
239
255
174
149
123
100
15.7
16.0
16.4
16.8
196
212
230
246
170
146
120
97
17.2
17.6
18.1
18.5
189
204
221
237
166
143
116
94
18.9
19.4
19.9
20.3
181
195
212
226
161
139
113
90
20.8
21.3
21.8
22.2
180
193
210
224
160
138
112
90
21.2
21.7
22.2
22.6
177
191
207
159
137
111
21.8
22.3
22.8
8000
62/0.36
67/0.23
72/0.22
76/0.21
221
236
255
272
198
171
138
109
14.2
14.5
15.0
15.3
215
228
247
263
192
168
135
107
15.8
16.2
16.6
17.0
209
220
238
254
185
165
132
104
17.6
17.9
18.3
18.7
202
211
228
244
177
161
128
100
19.3
19.6
20.1
20.6
194
202
218
170
158
125
21.2
21.6
22.1
192
200
216
171
157
124
21.7
22.0
22.5
190
197
172
156
22.2
22.5
ENTERING AIR DRY-BULB TEMP (F)
78
77
76
75
82
83
84
85
Correction Factor
2.07
3.11
4.14
5.18
1.96
2.94
3.92
4.91
1.74
2.62
3.49
4.36
1.53
2.29
3.05
3.82
1.31
1.96
2.62
3.27
1.09
1.64
2.18
2.73
0.87
1.31
1.74
2.18
0.65
0.98
1.31
1.64
80/0.05
80/0.04
under 75
over 85
Use formula
shown below.