SINGLE-PACKAGED
GAS HEATING/ELECTRIC
COOLING UNITS
UNIT 574B
Single-Packaged Rooftop Products with Energy-Saving Fea-
tures and Puron® refrigerant.
Direct Spark Ignition
Low Sound Levels
Up to 81% AFUE
13 SEER
Variable Speed Blower Standard
Factory Installed TXV

FEATURES/BENEFITS

One-piece heating and cooling units with low sound levels, easy
installation, low maintenance, and dependable performance.
Puron® Environmentally Sound Refrigerant is Bryant's
unique refrigerant designed to help protect the environment.
Puron is an HFC refrigerant which does not contain chlorine that
can harm the ozone layer. The most important advantage of
Puron refrigerant is that it has not been banned in future air con-
ditioning systems as the traditional refrigerant R-22 has been.
Puron refrigerant is in service in thousands of systems proving
highly reliable, environmentally sound performance.
Perfect Heat, Perfect Humidity™ featuring Variable Speed
Blower motors provides better comfort and energy efficiency.
You can expect up to 30 times better dehumidification; economi-
cal constant fan for less than $50 a year, which provides improved
indoor air quality and more even temperatures from room to room;
and reduced indoor noise due to lower air velocity. In addition,
you'll realize improved installation flexibility with 3 different airflow
choices for best overall comfort.
EASY INSTALLATION—Factory-assembled package is a com-
pact, fully self-contained, combination gas heating/electric cool-
ing unit that is pre-wired, pre-piped, and pre-charged for
minimum installation expense.
These units are available in a variety of standard and optional
heating/cooling size combinations with voltage options to meet
residential and light commercial requirements. Units are light-
weight and install easily on a rooftop or at ground level. The high
tech composite unit base eliminates rust problems associated
with ground level applications.
CONVERTIBLE DUCT CONFIGURATION—Unit is designed
for easy use in either downflow or horizontal applications. Each
unit is easily converted from horizontal to downflow.
EFFICIENT OPERATION
High-efficiency design offers SEER (Seasonal Energy Effi-
ciency Ratios) of 13.0 and AFUE (Annual Fuel Utilization Effi-
ciency) ratings as high as 81%.
Energy-saving, direct spark ignition saves gas by operating
only when the room thermostat calls for heating. Standard units
are furnished with natural gas controls. A low-cost field-installed
kit for propane conversion is available for all units.
574B units with an "N" in the thirteenth position of model #
are dedicated Low NOx units designed for California installa-
tions. These models meet the California maximum oxides of ni-
trogen (NOx) emissions requirement of 40 nanograms/joule or
less as shipped from the factory and MUST be installed in Cali-
fornia Air Quality Management Districts where a Low NOx rule
exists.
DURABLE, DEPENDABLE COMPONENTS
Compressors are designed for high efficiency. Each compres-
sor is hermetically sealed against contamination to help promote
longer life and dependable operation. Each compressor also has
vibration isolation to provide quieter operation. All compressors
have internal high pressure and overcurrent protection.
Monoport inshot burners produce precise air-to-gas mixture,
which provides for clean and efficient combustion. The large
monoport on the inshot (or injection type) burners seldom, if
ever, requires cleaning. All gas furnace components are acces-
sible in one compartment.
Turbo-tubular™ heat exchangers are constructed of alumi-
nized steel for corrosion resistance and optimum heat transfer
for improved efficiency. The tubular design permits hot gases to
make multiple passes across the path of the supply air.
In addition, dimples located on the heat exchanger walls force
the hot gases to stay in close contact with the walls, improving
heat transfer.
Direct-drive variable speed (ECM) blower motor is standard
on all 574B models.
Direct-drive, PSC condenser-fan motors are designed to help
reduce energy consumption and provide for cooling operation
down to 55°F outdoor temperature. Motormaster® II low ambient
kit is available as a field-installed accessory.
Form No. PDS 574B.24.1
Model 574B
Sizes 024-060
2 to 5 Nominal Tons
Low NOx Models Available

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 574B

  • Page 1: Features/Benefits

    A low-cost field-installed kit for propane conversion is available for all units. 574B units with an “N” in the thirteenth position of model # are dedicated Low NOx units designed for California installa- tions. These models meet the California maximum oxides of ni-...
  • Page 2: Model Number Nomenclature

    The unit base with integrated drain pan provides easy ground lev- el installation with or without a mounting pad. Convenient rigging 574B Model Number 574B – Single Packaged Gas Heating/Electric Cooling Electrical Supply N –...
  • Page 3: Table Of Contents

    COOLING CAPACITIES AND EFFICIENCIES UNIT 574B NOMINAL TONS 024040 030040 2-1/2 036060 036060 036090 042060 3-1/2 042090 048090 048115 048130 060090 060115 060130 LEGEND — Decibels — Dry Bulb SEER — Seasonal Energy Efficiency Ratio — Wet Bulb * Air Conditioning & Refrigeration Institute.
  • Page 4 HEATING CAPACITIES AND EFFICIENCIES HEATING INPUT UNIT 574B (Btuh) 024040 40,000 030040 030060 036060 60,000 042060 90,000 036090 90,000 042090 048090 90,000 060090 90,000 048115 115,000 060115 048130 130,000 060130 LEGEND AFUE — Annual Fuel Utilization Efficiency NOTE: Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
  • Page 5: Physical Data

    UNIT SIZE 574B NOMINAL CAPACITY (ton) OPERATING WEIGHT (lb) COMPRESSORS Quantity REFRIGERANT (R-410A) Quantity (lb) REFRIGERANT METERING DEVICE Indoor CONDENSER COIL Rows—Fins/in. Face Area (sq ft) CONDENSER FAN Nominal Cfm Diameter (in.) Motor Hp (Rpm) EVAPORATOR COIL Rows—fins/in. Face Area (sq ft) EVAPORATOR BLOWER Nominal Airflow (Cfm)
  • Page 6 UNIT SIZE 574B NOMINAL CAPACITY (ton) OPERATING WEIGHT (lb) COMPRESSORS Quantity REFRIGERANT (R-410A) Quantity (lb) REFRIGERANT METERING DEVICE Indoor CONDENSER COIL Rows—Fins/in. Face Area (sq ft) CONDENSER FAN Nominal Cfm Diameter (in.) Motor Hp (Rpm) EVAPORATOR COIL Rows—fins/in. Face Area (sq ft) EVAPORATOR BLOWER Nominal Airflow (Cfm)
  • Page 7: Options And Accessories

    Factory-installed options Coil options include Tin-Plated* indoor hairpins, copper/copper and vinyl-coated construction for refrigerant coils. Units are shipped standard with copper tube/aluminum fin construction. See model number nomenclature for coil options. *Tin-Plated indoor coils are built with special hairpins that are de- signed to resist both general pitting corrosion and excessive in- door corrosion (Formicary Corrosion).
  • Page 8 Economizer A99314 Filter Rack A99316 17 13/32 (442mm) 11 13/32” (290mm) DOOR LATCH ANGLE 16 1/4” (413mm) HINGED FILTER ACCESS DOOR INSTALL FILTER ACCESS DOOR STICKER Manual Outside Air Damper REPLACEMENT PANEL MANUAL OUTSIDE AIR HOOD DAMPER BLADE —8— FILTER ACCESS DOOR (HORIZONTAL APPLICATION ONLY.) DO NOT REMOVE...
  • Page 9: Base Unit Dimensions

    BASE UNIT DIMENSIONS — 574B024-036 REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm) Evaporator coil access side ....36 (914) Power entry side (except for NEC requirements) ..36 (914) Unit top .
  • Page 10: Base Unit Dimensions

    BASE UNIT DIMENSIONS – 574B042-060 REQUIRED CLEARANCE FOR OPERATION AND SERVICING EVAP. COIL ACCESS SIDE...36.00 [914.0] POWER ENTRY SIDE...36.00 [914.0] (EXCEPT FOR NEC REQUIREMENTS) UNIT TOP ...36.00 [914.0] SIDE OPPOSITE DUCTS ...36.00 [914.0] DUCT PANEL ...12.00 [304.8] * *MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
  • Page 11: Accessory Dimensions

    HVAC unit base Screw (NOTE A) *Gasketing outer flange Flashing field supplied Roofing material field supplied Cant strip field supplied *Provided with roofcurb Roof Curb for Small Cabinet Note A: When unit mounting screw is used, retainer bracket must also be used. B Typ.
  • Page 12: Selection Procedure

    In the Heating Capacities and Efficiencies table on page 4, note that the unit 036090 will provide 70,000 Btuh with an input of 90,000 Btuh. 574B CORNER WEIGHTS DETERMINE FAN SPEED AND POWER REQUIRE- MENTS AT DESIGN CONDITIONS. Before entering the air delivery tables, calculate the total static pressure required.
  • Page 13: Performance Data

    574B024 COOLING PERFORMANCE TABLE Temp (F) 800/0.026 Outdoor Air Entering Condenser 24.0 24.5 21.9 21.3 22.9 23.3 21.4 20.7 21.8 22.2 20.8 20.2 20.5 20.9 20.2 19.5 19.2 19.5 19.4 18.8 17.8 18.0 18.5 18.1 574B030 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser...
  • Page 14 574B036 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser 36.2 33.2 34.6 32.4 33.0 31.6 31.3 30.6 29.6 29.3 27.8 27.5 574B042 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser See Legend and Notes on page 15. PERFORMANCE DATA (cont) STANDARD INDOOR ECM MOTOR COOLING CAPACITIES (cont) Evaporator Air—CFM/BF...
  • Page 15 574B048 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser 45.0 39.3 42.8 38.2 40.6 36.9 38.2 35.7 35.7 34.4 33.4 32.1 574B060 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser 57.2 49.4 54.7 48.2 52.2 47.0 49.4 45.7 46.5 44.3 43.3...
  • Page 16 FILTER SIZE 20 X 20 X 1 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15 20 X 24 X 1 — — — — 24 X 30 X 1 — — — — FILTER PRESSURE DROP (In. wg) 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 —...
  • Page 17 574B COOLING DRY COIL ECM AIRFLOW—SMALL CABINET CFM ADJUST PIN SELECT UNIT SIZE EXTERNAL STATIC 0.0–0.39 PRESSURE RANGE COOLING COOLING DEHUMIDIFY COOLING COOLING DEHUMIDIFY COOLING 1025 COOLING DEHUMIDIFY 574B COOLING DRY COIL ECM AIRFLOW—LARGE CABINET CFM ADJUST PIN SELECT UNIT...
  • Page 18 574B ECM AIR FLOW VS. TEMPERATURE RISE CHART UNIT COOLING SIZE 574B 574B 574B 574B 574B 574B 574B 574B 574B 574B 574B 574B 574B ECONOMIZER/1-IN. FILTER PRESSURE DROP NATURAL GAS ONLY ORIFICE CONVERSION — 3.5 in. wc MANIFOLD PRESSURE* INPUT...
  • Page 19: Typical Piping And Wiring

    TYPICAL PIPING AND WIRING ROOF-MOUNTING CURB SUPPLY-AIR FLEXIBLE DUCT CONCENTRIC DIFFUSER BOX (FIELD-SUPPLIED) RETURN TOP COVER ROOF RETURN-AIR FLEXIBLE DUCT CEILING INDOOR THERMOSTAT FROM GAS LINE *NEC - NATIONAL ELECTRICAL CODE —19— C00023 FROM POWER SOURCE DISCONNECT PER NEC* C00022...
  • Page 20: Application Data

    Condensate trap — A 2-in. condensate trap must be field supplied. 1” MIN. Ductwork — Secure downflow discharge ductwork to roof curb. For horizontal discharge applications, attach ductwork to unit with flanges. To convert a unit to downflow discharge — Units are equipped with factory-installed inserts in the down-flow openings.
  • Page 21: Electrical Data

    574B (STANDARD) ELECTRICAL DATA UNIT SIZE V-PH-Hz 574B 208/230–1–60 208/230–1–60 208/230–1–60 208/230–3–60 208/230–1–60 208/230–3–60 208/230–1–60 208/230–3–60 208/230–1–60 208/230–3–60 LEGEND — Full Load Amps — Locked Rotor Amps — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection — Rated Load Amps *Heater capacity (KW) based on heater voltage of 208v, 240v, &...
  • Page 22: Typical Wiring Schematics

    TYPICAL WIRING SCHEMATIC—208/230-1-60 SHOWN —22— C01035...
  • Page 23: Typical Wiring Schematics

    TYPICAL WIRING SCHEMATIC—208/230-3-60 SHOWN C03025 C99077 —23—...
  • Page 24: Controls

    OPERATING SEQUENCE Heating — On a call for heating, terminal “W” of the thermostat is energized, starting the induced-draft motor. When the hall- effect sensor on the induced-draft motor senses that it has reached the required speed, the burner sequence begins. This function is performed by the integrated gas control (IGC).
  • Page 25 —25—...
  • Page 26 —26—...
  • Page 27: Guide Specifications

    HVAC GUIDE SPECIFICATIONS SIZE RANGE: 2 TO 5 TONS, NOMINAL COOLING 40,000 TO 130,000 BTUH, NOMINAL HEATING INPUT BRYANT MODEL NUMBER: 574B PART 1 — GENERAL 1.01 SYSTEM DESCRIPTION Outdoor rooftop mounted, gas heating/electric cooling unit utilizing a scroll compressor for cooling duty. Unit shall discharge supply air vertically or horizontally as shown on contract drawings.
  • Page 28 Package shall consist of damper, birdscreen, and rain- hood which can be preset to admit outdoor air for year- round ventilation. © 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 GUIDE SPECIFICATIONS continued 5. Thermostat: To provide for one-stage heating and cooling in addition manual or automatic changeover and indoor fan control.