Bryant 579F User Manual

Bryant 579F User Manual

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units

Advertisement

COMMERCIAL
SINGLE PACKAGE ROOFTOP UNITS
GAS HEATING/ELECTRIC COOLING UNITS
SIZES 024-073
48-910df
a48-8207
581A210-300
Standard efficiency units (580F072, 090, 120, 150 and
579F180-300)
are
available.
(580F036-060, 073, 091,103,121,151, and 180-300) that meet
ASHRAE 90.1-04 minimum energy efficiency requirements are
also available. High efficiency units (581C024-060, 581B036-
150 and 581A155-300) well exceed ASHRAE 90.1-04 energy
efficiency requirements and must comply with Energy Star high
efficiency requirements. Gas heating with electric cooling roof-
tops offer:
• Pre-painted galvanized steel cabinet for long life and quality
appearance
• Commercial strength base rails with built-in rigging capability
• Convertible design for vertical or horizontal supply/return
(024-151 field convertible, factory supplied vertical supply/
return and 210-300 discrete configuration only)
• Non-corrosive,
sloped
ASHRAE 62 (IAQ)
• Two-inch return-air filters
• A wide assortment of factory-installed options available,
including high-static drives that provide additional perfor-
mance range
• Factory-installed optional gear driven EconoMi$er IV (vertical
return for sizes 024-151 only) for use with standard rooftop
unit controls (includes CO
• Factory-installed optional gear driven EconoMi$er2 (vertical
return only) for use with third party DDC controls (includes
4 to 20 mA actuator for demand control ventilation)
• Perfect Humidity™ dehumidification package (581C036-060
and 581B036-150 only)
• Hot gas reheat dehumidification package (581A181-300 only)
Heat Options
• Exclusive integrated gas control board with diagnostics
• Alumagard™ heat exchanger coating
50-1242f
580F240
579F240-300
Standard
efficiency
condensate
drain
pan,
sensor control capability)
2
SIZES 090-151
a48-5997
48-831df
• Induced-draft fan for gas combustion
units
• Tubular, dimpled heat exchangers
• Natural gas
• LP conversion kits
• Low NO
(size 024-060 only)
X
• Optional type 409 stainless steel heat exchangers.
Every compact one-piece unit arrives fully assembled,
charged, tested, and ready to run.
GAS HEAT MODELS — All ignition components are contained
in the compact IGC (integrated gas controller) which is easily
accessible for servicing. The IGC control board, designed and
manufactured exclusively for Bryant rooftop units, provides
built-in diagnostic capability. An LED (light-emitting diode) sim-
meets
plifies troubleshooting by providing visual fault notification and
required system status confirmation.
The IGC also contains an exclusive anti-cycle protection for
gas heat operation. After 4 continuous cycles on the unit high-
temperature limit switch, the gas heat operation is disabled,
and an error code is issued. This feature greatly improves reli-
ability of the rooftop unit.
The IGC also contains burner control logic for accurate and
dependable gas ignition. The LED is visible without removing
the unit control box access panel. This LED fault-notification
system reduces service person troubleshooting time and mini-
mizes service costs. The IGC also maximizes heating effi-
ciency by controlling evaporator-fan on and off delays.
Tubular, dimpled gas heat exchangers optimize heat transfer
for improved efficiency. The tubular design permits hot gases
to make multiple passes across the path of the supply air. The
dimpled design creates a turbulent gas flow to maximize heat-
ing efficiency.
580F, 579F, 581A/B/C
DuraPac and
DuraPac Plus Series
Sizes 024-300
50-1214df
580F300
FEATURES/BENEFITS
Form No. PDS580F-36-4
2 to 25 Tons
579F180-216
581A155,180
580F180,210

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 579F

  • Page 1 GAS HEAT MODELS — All ignition components are contained in the compact IGC (integrated gas controller) which is easily accessible for servicing. The IGC control board, designed and manufactured exclusively for Bryant rooftop units, provides built-in diagnostic capability. An LED (light-emitting diode) sim- drain...
  • Page 2: Table Of Contents

    IGC board locks out the gas heat cycle to prevent any fur- ther short cycles. This safety feature is provided exclusively on Bryant rooftop units. The rollout switch also deenergizes the gas valve in the event of a flame rollout.
  • Page 3: Features/Benefits

    Bryant-specified hermetic compres- sors are equipped with compressor overcurrent and overtem- perature protection to ensure dependability. All units have Bryant’s exclusive Acutrol™ (024-151) or TXV (thermostatic expansion valve) metering device (155-300) which precisely controls refrigerant flow, preventing slugging and flood-back, while maintaining optimum unit performance.
  • Page 4 EXCLUSIVE HOT GAS REHEAT DEHUMIDIFICATION PACK- AGE (581A181-300) — The hot gas reheat dehumidification package is a result of recent advances by Bryant in controlling comfort levels. This factory-installed option significantly improves the dehumidification capability of the rooftop unit and helps control humidity levels in the building.
  • Page 5: Model Number Nomenclature

    NOTE: The example model number 580FEV090180KV designates a 7 1/2 ton 460-3-60 volt gas/electric rooftop unit with 180,000 Btuh natural gas heat, EconoMi$er IV and Alternate Drive. 580F036-151 (Stainless Steel and Low NOx) 3 to 12 NOTE: The example model number 580FEV060120NKV designates a 5 ton 460-3-60 volt low NOx gas/electric rooftop unit with 120,000 Btuh natural gas heat, EconoMi$er IV and Alternate Drive.
  • Page 6 NOTE: The example model number 581BEV090180HQ designates a 7 1/2 ton 460-3-60 volt gas/electric rooftop unit with 180,000 Btuh natural gas heat and EconoMi$er IV. 581B036-150 (Stainless Steel and Low NOx) — 3 to 12 NOTE: The example model number 581BEV0601202HQ designates a 5 ton 460-3-60 volt Low NOx gas/electric rooftop unit with 120,000 Btuh natural gas heat and EconoMi$er IV.
  • Page 7 581C024-060 (Standard Efficiency) — 2 to 5 Tons NOTE: The example model number 581CEV060150HQ designates a 5 ton 460-3-60 volt gas/electric rooftop unit with 150,000 Btuh natural gas heat and EconoMi$er IV. 581C024-060 (Stainless Steel and Low NOx) — 2 to 5 Tons NOTE: The example model number 581CEV060120NHQ designates a 5 ton 460-3-60 volt Low NOx gas/electric rooftop unit with 120,000 Btuh natural gas heat and EconoMi$er IV.
  • Page 8 MODEL NUMBER NOMENCLATURE — 579F180-300 579F – Single-Package Standard-Efficiency Gas/Electric Unit Voltage Designation E – 460-3-60 P – 208/230-3-60 T – 575-3-60 Fuel and Control Type V – Natural Gas/Electric Relight Pilot Nominal Tons 180 – 15 Tons 216 – 18 Tons 240 –...
  • Page 9 MODEL NUMBER NOMENCLATURE 581A155, 180, 181 — 13 to 15 Tons 581A 581A – Single Package High Efficiency Gas/Electric Unit Voltage Designation E – 460-3-60 P – 208/230-3-60 T – 575-3-60 Fuel and Control Type V – Natural Gas/Electric Relight Pilot Nominal Tons 155 –...
  • Page 10 NOMINAL STANDARD UNIT 580F TONS UNIT NOMINAL 580F TONS LEGEND — Sound Levels (decibels) — Dry Bulb — Energy Efficiency Ratio IPLV — Integrated Part-Load Values SEER — Seasonal Energy Efficiency Ratio — Wet Bulb *Air Conditioning and Refrigeration Institute. †Applies only to units with capacity of 65,000 Btuh or less.
  • Page 11 HEATING CAPACITIES AND EFFICIENCIES (Standard Efficiency Units) — 580F036-151 (cont) 208/230/460-3-60 — SINGLE-STAGE GAS HEAT — LOW NOx UNIT INPUT OUTPUT 580F CAPACITY CAPACITY 036060N 60,000 49,000 036090N 90,000 73,000 048060N 60,000 49,000 048090N 90,000 73,000 048120N 120,000 98,000 060060N 60,000 47,000 060090N...
  • Page 12 UNIT NOMINAL 581B TONS LEGEND — Energy Efficiency Ratio IPLV — Integrated Part-Load Value SEER — Seasonal Energy Efficiency Ratio *Air-Conditioning & Refrigeration Institute. †Applies only to units with capacity of 65,000 Btuh or less. **The IPLV is not applicable to single-compressor units. NOTES: 1.
  • Page 13 HEATING CAPACITIES AND EFFICIENCIES — 581B036-150(cont) 208/230/460-3-60 — SINGLE-STAGE GAS HEAT — LOW NOx UNIT INPUT CAPACITY OUTPUT CAPACITY 581B 036060N 60,000 036090N 90,000 048060N 60,000 048090N 90,000 048120N 120,000 060060N 60,000 060090N 90,000 060120N 120,000 INPUT CAPACITY UNIT 581B 1st Stage 2nd Stage 036072...
  • Page 14: Ari Capacity Ratings

    UNIT NOMINAL 581C TONS LEGEND — Energy Efficiency Ratio SEER — Seasonal Energy Efficiency Ratio *Air-Conditioning & Refrigeration Institute. **ARI does not require EER ratings for unit with capacity below 65,000 Btuh. For these units, the EER rating at ARI standard conditions is provided for informa- tion only.
  • Page 15 HEATING CAPACITIES AND EFFICIENCIES — 581C024-060 (cont) 208/230/460-3-60 — SINGLE-STAGE GAS HEAT — LOW NOx UNIT INPUT CAPACITY OUTPUT CAPACITY 581C 1st Stage 2nd Stage 1st Stage 036060N 60,000 — 50,000 036090N 90,000 — 74,000 048060N 60,000 — 50,000 048090N 90,000 —...
  • Page 16 For entering-air temperatures below 45 F both stages of heat must be energized together to minimize condensation issues and ensure proper unit operation. Mixed air below 35 F optional stainless steel heat exchangers are recommended. AIR QUANTITY LIMITS UNIT 579F MINIMUM CFM 4500 5400...
  • Page 17 UNIT SIZE NOMINAL 580F TONS (Low Heat) UNIT SIZE NOMINAL 580F TONS (High Heat) LEGEND Bels — Sound Levels (1 bel = 10 decibels) — Dry Bulb EER — Energy Efficiency Ratio IPLV — Integrated Part-Load Values — Wet Bulb *Air Conditioning and Refrigeration Institute.
  • Page 18 UNIT NOMINAL 581A TONS 155230 180275 UNIT NOMINAL 581A TONS 155300 180360 LEGEND — Sound Levels (decibels) — Dry Bulb EER — Energy Efficiency Ratio IPLV — Integrated Part-Load Values — Wet Bulb *Air Conditioning and Refrigeration Institute. NOTES: 1. Rated in accordance with ARI Standards 360 and 270. 2.
  • Page 19 UNIT NOMINAL 581A TONS 5,500 6,000 300** 7,500 LEGEND — Dry Bulb EER — Energy Efficiency Ratio IPLV — Integrated Part-Load Values — Wet Bulb *Air Conditioning and Refrigeration Institute. †IPLV values are calculated based on control configuration T.CTL = 2 (2 Stage Y1).
  • Page 20: Options And Accessories

    ITEM 100% OA Open Two-Position Damper 25% OA Open Two-Position Damper Condenser Coil Grille Condenser Coil Hail Guard Assembly Convenience Outlet (Load Side) Copper Fins Indoor and Outdoor Coil Copper Fins Outdoor Coil E-Coat Outdoor Coil (Aluminum) E-Coat Outdoor Coil (Copper) EconoMi$er IV with Controller EconoMi$er2 (without controller) Electronic Programmable Thermostat...
  • Page 21 ITEM 25% Open Two-Position Damper Barometric Relief Damper (not for use with Horizontal Adapter Curb) Condenser Coil Hail Guard Assembly (180-240) Convenience Outlet (Load Side) Copper Fins Indoor and Outdoor Coil Copper Fins Outdoor Coil E-Coat Outdoor Coil (Aluminum) E-Coat Outdoor Coil (Copper) EconoMi$er IV with Controller EconoMi$er2 (without Controller) Electronic Programmable Thermostat...
  • Page 22 ITEM EconoMi$er IV Power Exhaust Barometric Relief Hail Guard Horizontal Kit Return Smoke Detector Supply Smoke Detector Return and Supply Smoke Detector Non-Fused Disconnect Non-Powered Convenience Outlet Outdoor Air Enthalpy Sensor Return Air Enthalpy Sensor Return Air Temperature Sensor Return Air CO Sensor Indoor Air Quality (CO ) Room Sensor...
  • Page 23: Options And Accessories

    EconoMi$er IV on 579F and 581A units is used for both vertical and horizontal return air configurations. EconoMi$er2 is available as a blanket quote control or as a field-installed accessory for horizontal and/or vertical supply return configurations.
  • Page 24 UNIT SIZE 580F NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Cu* COMPRESSOR Type Quantity No. Cylinders (per Circuit) Oil (oz) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Circuit 1 (first stage) Circuit 2 (second stage) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp...Rpm Watts Input (Total) CONDENSER COIL...
  • Page 25 UNIT SIZE 580F FURNACE SECTION Rollout Switch Cutout Temp (F)†† Burner Orifice Diameter (in..drill size) Natural Gas Liquid Propane Thermostat Heat Anticipator Setting (amps) 208/230 v and 575 Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input (Btuh) Standard Units (Stage 1/Stage 2) Low NOx Units...
  • Page 26: Physical Data

    UNIT SIZE 580F NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Cu* COMPRESSOR Type Quantity No. Cylinders (per Circuit) Oil (oz) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Circuit 1 (first stage) Circuit 2 (second stage) CONDENSER COIL Rows...Fins/in. Total Face Area (sq ft) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.)
  • Page 27 PHYSICAL DATA — 580F090,120,150 UNITS (cont) UNIT SIZE 580F FURNACE SECTION Rollout Switch Cutout Temp (F)** Burner Orifice Diameter (in..drill size) Natural Gas Liquid Propane Thermostat Heat Anticipator Setting (amps) 208/230 v and 575 Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input (Btuh) Stage 1...
  • Page 28 PHYSICAL DATA — 580F091,103,121,151 UNITS UNIT SIZE 580F NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Cu* COMPRESSOR Type Quantity No. Cylinders (per Circuit) Oil (oz) (each compressor) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Circuit 1 (first stage) Circuit 2 (second stage) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.)
  • Page 29 PHYSICAL DATA — 580F091,103,121,151 UNITS (cont) UNIT SIZE 580F FURNACE SECTION Rollout Switch Cutout Temp (F)** Burner Orifice Diameter (in..drill size) Natural Gas Liquid Propane Thermostat Heat Anticipator Setting (amps) 208/230 v and 575 Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input (Btuh) Stage 1...
  • Page 30 BASE UNIT DIMENSIONS — 580F036-072 a48-8195...
  • Page 31: Base Unit Dimensions

    BASE UNIT DIMENSIONS — 580F073 a48-8196...
  • Page 32 BASE UNIT DIMENSIONS — 580F090,120,150 a48-8197...
  • Page 33 BASE UNIT DIMENSIONS — 580F091,103,121,151 a48-8198...
  • Page 34: Accessory Dimensions

    ROOF CURB UNIT SIZE ACCESSORY 1′-2″ CRRFCURB001A01 [356] CRBTMPWR001A01 580F 036-073 2′-0″ CRBTMPWR002A01 CRRFCURB002A01 [610] CRBTMPWR003A01 CRBTMPWR004A01 ACCESSORY DIMENSIONS — 580F D ALT CONNECTOR DRAIN PKG. ACCY. HOLE ″ ″ 1′-9 1′-4″ [551] [406] [44.5] Roof Curb ACCESSOR POWER CONTROL ″...
  • Page 35 D ALT CONNECTOR DRAIN PKG. ACCY. HOLE CRBTMPWR001A01 CRBTMPWR002A01 ″ ″ ″ 2′-8 1′-10 CRBTMPWR003A01 [827] [583] [44.5] CRBTMPWR004A01 ACCESSORY DIMENSIONS — 580F (cont) ACCESSORY POWER CONTROL POWER ″ [19] NPT ″ ″ [31.7] [19] NPT ″ ″ ″ [19] NPT [12.7] NPT [12.7] NPT [12.7] NPT...
  • Page 36: Selection Procedure

    SELECTION PROCEDURE (with 580F060 example) I DETERMINE COOLING AND HEATING REQUIRE- MENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity (TC)... 55,000 Btuh Sensible Heat Capacity (SHC) ... . 40,000 Btuh Required Heating Capacity.
  • Page 37: Performance Data

    580F036 (3 TONS) Temp (F) 900/0.11 Air Entering Condenser (Edb) 42.8 38.9 20.0 24.5 2.91 2.81 40.8 36.9 19.4 23.7 3.14 3.01 38.7 34.9 18.6 22.9 3.35 3.21 36.5 32.8 17.8 22.1 3.55 3.41 34.3 30.7 17.0 21.3 3.76 3.60 580F048 (4 TONS) Temp (F) 1200/0.12...
  • Page 38 580F072 (6 TONS) Temp (F) 1800/0.06 Air Entering Condenser (Edb) 86.6 80.0 42.2 52.3 5.48 5.33 84.1 77.4 41.4 51.3 6.17 6.00 81.6 74.7 40.6 50.3 6.86 6.67 78.4 71.8 39.4 49.2 7.60 7.39 75.1 68.7 38.1 47.9 8.36 8.14 580F073 (6 TONS) Temp (F) 1800/0.06...
  • Page 39 580F091 (7 TONS) Temp (F) 2250/0.10 Air Entering Condenser (Edb) 105.8 97.6 50.9 63.6 6.34 6.05 101.1 92.9 49.4 62.0 6.80 6.51 96.6 87.7 47.8 59.9 7.26 6.96 91.0 82.1 45.9 57.9 7.70 7.37 85.2 76.0 43.9 55.4 8.13 7.79 580F103 (8 TONS) Temp (F)
  • Page 40 580F121 (10 TONS) Temp (F) 3000/0.095 Air Entering Condenser (Edb) 138.2 127.0 68.0 84.1 8.37 8.07 132.3 121.7 65.5 81.9 8.92 8.63 126.3 115.7 63.3 79.8 9.54 9.24 120.2 106.5 61.5 76.2 10.23 9.87 117.1 99.8 60.5 73.7 10.51 10.13 580F150 (12 TONS) Temp (F)
  • Page 41 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS 580F036 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE) Airflow 208 V (Cfm) Watts 0.49 0.21 1000 0.42 0.23 1100 0.37 0.24 1200 0.33 0.26 1300 0.27 0.27 1400 0.20 0.29 1500 0.16 0.30 LEGEND —...
  • Page 42 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE) Airflow 208 V (Cfm) Watts 1200 0.68 0.41 1300 0.61 0.42 1400 0.53 0.45 1500 0.45 0.47 1600 0.36 0.49 1700 0.26 0.52 1800 0.15 0.54 1900 0.04...
  • Page 43 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F060 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 V 230,460,575 V (Cfm) Watts 1500 0.69 0.67 1.01 0.71 1600 0.49 0.70 0.85 0.74 1700 0.29 0.73 0.70 0.77 1800 0.09 0.75 0.54...
  • Page 44 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 1500 0.42 1600 0.49 1700 0.57 1800 0.65 1900 0.75 2000 0.86 2100 1035 0.98 2200 1075 1.11 2300 1115 1.25 1110 2400 1155 1.40...
  • Page 45 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F072,073 (6 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 1800 0.65 1900 1007 0.75 2000 1048 0.85 2100 1090 0.97 2200 1131 1.09 2300 1173 1.23 1091 2400 1215 1.38 1223 2500 1258 1.54...
  • Page 46 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F090,091 (7 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2250 0.54 0.57 2300 0.63 2400 2500 0.69 0.72 2550 0.76 2600 0.83 2700 2800 0.90 0.98 2900 1.07 3000 1.16 1085 3100 3200 1.26...
  • Page 47 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F090,091 (7 TONS) — ALTERNATE MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2250 0.54 0.57 2300 0.63 2400 0.69 2500 0.72 2550 0.76 2600 2700 0.83 2800 0.90 2900 0.98 3000 1.07 3100 1.16 1085 1.26 1176...
  • Page 48 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F090,091 (7 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2250 0.54 0.57 2300 0.63 2400 2500 0.69 0.72 2550 0.76 2600 0.83 2700 2800 0.90 0.98 2900 1.07 3000 1.16 1085 3100 3200 1.26...
  • Page 49 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F103 (8 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2550 0.72 2600 0.76 2700 0.83 2800 0.90 2900 0.98 3000 1.07 3100 1.16 1085 3200 1.26 1176 3300 1.36 1272 3400 1.47 1374 3500...
  • Page 50 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F103 (8 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2550 0.72 2600 0.76 2700 0.83 2800 0.90 2900 0.98 3000 1.07 3100 1.16 1085 3200 1.26 1176 3300 1.36 1272 3400 1.47 1374 3500...
  • Page 51 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F120 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3000 0.75 3100 0.81 3200 0.88 3300 0.95 3400 1.03 3500 1.11 3600 1.20 1050 3700 1.29 1129 3800 1.38 1212 3900 1.48 1299 4000...
  • Page 52 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F120 (10 TONS) — ALTERNATE MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3000 0.75 3100 0.81 3200 0.88 3300 0.95 3400 1.03 3500 1.11 3600 1.20 1050 3700 1.29 1129 3800 1.38 1212 3900 1.48 1299 4000...
  • Page 53 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F120 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3000 0.75 3100 0.81 3200 0.88 3300 0.95 3400 1.03 3500 1.11 3600 1.20 1050 3700 1.29 1129 3800 1.38 1212 3900 1.48 1299 4000...
  • Page 54 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F121 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3000 0.77 3100 0.83 3200 0.90 3300 0.98 3400 1.06 3500 1.15 1005 3600 1.23 1084 3700 1.33 1167 3800 1.43 1254 3900 1.53 1345...
  • Page 55 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F121 (10 TONS) — ALTERNATE MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3000 0.77 3100 0.83 3200 0.90 3300 0.98 3400 1.06 3500 1.15 1005 3600 1.23 1084 3700 1.33 1167 3800 1.43 1254 3900 1.53 1345...
  • Page 56 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F121 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3000 0.77 3100 0.83 3200 0.90 3300 0.98 3400 1.06 3500 1.15 1005 3600 1.23 1084 3700 1.33 1167 3800 1.43 1254 3900 1.53 1345...
  • Page 57 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F150,151 (12 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3700 1.36 1266 3800 1.46 1361 3900 1.57 1460 4000 1.68 1563 4100 1.79 1672 4200 1.92 1786 4300 2.04 1906 4400 2.18 2031 4500...
  • Page 58 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 580F150,151 (12 TONS) — ALTERNATE MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3700 1.36 1266 3800 1.46 1361 3900 1.57 1460 4000 1.68 1563 4100 1.79 1672 4200 1.92 1786 4300 2.04 1906 4400 2.18 2031 4500...
  • Page 59 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS 580F036 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE) Airflow 208 V (Cfm) Watts 0.54 0.21 1000 0.49 0.23 1100 0.43 0.24 1200 0.39 0.26 1300 0.33 0.27 1400 0.26 0.29 1500 0.21 0.30 LEGEND —...
  • Page 60 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE) Airflow 208 V (Cfm) Watts 1200 0.75 0.41 1300 0.68 0.42 1400 0.60 0.45 1500 0.51 0.47 1600 0.42 0.49 1700 0.32 0.52 1800 0.21 0.54 1900 0.09...
  • Page 61 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F060 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208V 230, 460, 575 V (Cfm) Watts 1500 0.74 0.67 1.06 1600 0.54 0.70 0.90 1700 0.34 0.73 0.75 1800 0.14 0.75 0.59 1900 —...
  • Page 62 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 1500 0.40 1600 0.46 1700 0.54 1800 0.62 1900 0.71 2000 0.82 2100 1024 0.93 2200 1064 1.05 2300 1105 1.18 1050 2400 1146 1.33...
  • Page 63 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F072,073 (6 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 1800 0.63 1900 0.73 2000 1001 0.84 2100 1043 0.96 2200 1085 1.09 2300 1127 1.23 1092 2400 1169 1.38 1229 2500 1212 1.55 1378...
  • Page 64 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F090,091 (7 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2250 0.52 0.55 2300 0.60 2400 2500 0.66 0.69 2550 0.73 2600 0.80 2700 2800 0.87 0.95 2900 1.03 3000 1.12 1046 3100 3200 1.22...
  • Page 65 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F090,091 (7 TONS) — ALTERNATE MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2250 0.52 0.55 2300 0.60 2400 2500 0.66 0.69 2550 0.73 2600 0.80 2700 2800 0.87 0.95 2900 1.03 3000 1.12 1046 3100 3200 1.22...
  • Page 66 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F090,091 (7 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2250 0.52 0.55 2300 0.60 2400 2500 0.66 0.69 2550 0.73 2600 0.80 2700 2800 0.87 0.95 2900 1.03 3000 1.12 1046 3100 3200 1.22...
  • Page 67 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F103 (8 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2550 0.69 2600 0.73 2700 0.80 2800 0.87 2900 0.95 3000 1.03 3100 1.12 1046 3200 1.22 1135 3300 1.32 1228 3400 1.42 1328 3500...
  • Page 68 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F103 (8 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2550 0.69 2600 0.73 2700 0.80 2800 0.87 2900 0.95 3000 1.03 3100 1.12 1046 3200 1.22 1135 3300 1.32 1228 3400 1.42 1328 3500...
  • Page 69 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F120,121 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3000 0.72 3100 0.78 3200 0.85 3300 0.92 3400 1.00 3500 1.08 3600 1.16 1019 3700 1.25 1097 3800 1.34 1179 3900 1.44 1266 4000...
  • Page 70 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F120,121 (10 TONS) — ALTERNATE MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3000 0.72 3100 0.78 3200 0.85 3300 0.92 3400 1.00 3500 1.08 3600 1.16 1019 3700 1.25 1097 3800 1.34 1179 3900 1.44 1266 4000...
  • Page 71 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F120,121 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3000 0.72 3100 0.78 3200 0.85 3300 0.92 3400 1.00 3500 1.08 3600 1.16 1019 3700 1.25 1097 3800 1.34 1179 3900 1.44 1266 4000...
  • Page 72 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F150,151 (12 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3700 1.19 1106 3800 1.27 1185 3900 1.36 1269 4000 1.45 1357 4100 1.55 1449 4200 1.66 1545 4300 1.76 1646 4400 1.88 1751 4500...
  • Page 73 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 580F150,151 (12 TONS) — ALTERNATE MOTOR (BELT DRIVE)* AIRFLOW (Cfm) Watts 3700 1.19 1106 3800 1.27 1185 3900 1.36 1269 4000 1.45 1357 4100 1.55 1449 4200 1.66 1545 4300 1.76 1646 4400 1.88 1751 4500...
  • Page 74 RATING 60 Hz (dB) 036-072 091, 103 NOTE: Indoor sound power is available in Bryant’s Electronic Catalog program (ECAT) for specific operating parameters. ACCESSORY/FIOP ECONOMIZER IV AND ECONOMI$ER2 STATIC PRESSURE* (in. wg) — 580F036-073 COMPONENT Vertical EconoMi$er IV and EconoMi$er2...
  • Page 75 *As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, the input rate should be reduced at higher altitudes. †Orifices are available through your local Bryant distributor. PERFORMANCE DATA (cont) MOTOR PULLEY TURNS OPEN...
  • Page 76 5000 4000 3000 2000 1000 2500 2000 1500 1000 0.13 POWER EXHAUST POWER EXHAUST DESCRIPTION PART NO. CRPWREXH030A01 Power Exhaust System (208/230-1-60) CRPWREXH021A01 Power Exhaust System (460-3-60) CRPWREXH022A01 Power Exhaust System (208/230-1-60) CRPWREXH023A01 Power Exhaust System (460-3-60) HORIZONTAL — MOUNTED IN RETURN DUCTWORK POWER EXHAUST POWER EXHAUST DESCRIPTION PART NO.
  • Page 77 2500 2000 1500 1000 2500 2000 1500 1000 OPTIONAL POWER EXHAUST POWER REQUIREMENTS AMPS AT UNIT 230 V SIZE (2 Fans 230 VAC Running) 1.40 Amps at 580F036-073 60 Hz 15.0 amps 15.0 amps 15.0 amps 3.04 Amps at 580F090-151 60 Hz LEGEND MOCP —...
  • Page 78 EVAPORATOR-FAN UNIT 580F MOTOR Standard Alternate High Static Standard Alternate High Static Standard Alternate High Static Standard 072,073 High Static Standard, Alternate 090,091 High Static Standard High Static Standard 120,121 Alternate High Static Standard 150, 151 Alternate LEGEND BHP — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors can be utilized with confidence.
  • Page 79: Electrical Data

    UNIT SIZE NOMINAL CONV 580F V-PH-Hz TYPE OUTLET 208/230-3-60 HIGH (3 Ton) 460-3-60 HIGH 575-3-60 HIGH 208/230-3-60 HIGH (4 Ton) 460-3-60 HIGH 575-3-60 HIGH LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration — Indoor (Evaporator) Fan Motor —...
  • Page 80 UNIT SIZE NOMINAL CONV 580F V-PH-Hz TYPE OUTLET 208/230-3-60 HIGH (5 Ton) 460-3-60 HIGH 575-3-60 HIGH 208/230-3-60 HIGH 460-3-60 (6 Ton) HIGH 575-3-60 HIGH 208/230-3-60 HIGH 460-3-60 (6 Ton) HIGH 575-3-60 HIGH 208/230-3-60 HIGH 460-3-60 Ton) HIGH 575-3-60 HIGH 208/230-3-60 HIGH 460-3-60 Ton)
  • Page 81 UNIT SIZE NOMINAL CONV 580F V-PH-Hz TYPE OUTLET 208/230-3-60 HIGH 460-3-60 Ton) HIGH 575-3-60 HIGH 208/230-3-60 HIGH 460-3-60 (10 Ton) HIGH 575-3-60 HIGH 208/230-3-60 HIGH 460-3-60 (10 Ton) HIGH 575-3-60 HIGH LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration —...
  • Page 82: Electrical Data

    UNIT SIZE NOMINAL CONV 580F V-PH-Hz TYPE OUTLET 208/230-3-60 HIGH 460-3-60 Ton) HIGH 575-3-60 HIGH 208/230-3-60 HIGH 460-3-60 Ton) HIGH 575-3-60 HIGH LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration — Indoor (Evaporator) Fan Motor — Locked Rotor Amps —...
  • Page 83: Typical Wiring Schematics

    TYPICAL WIRING SCHEMATICS — 580F036-151 CIRCUIT VOLTS MFG. PT. NO. BREAKER POTTER & BRUMFIELD 24 V W2BX-1024-3.2 Heinemann Airpax 460-3-60 (150,151 Std) CF3-Z228-41 219-3-2600-486 LEGEND — Contactor, Compressor — Capacitor — Circuit Breaker — Compressor Lockout COMP — Compressor Motor EQUIP —...
  • Page 84 TYPICAL WIRING SCHEMATICS — 580F036-151 (cont) a48-7910 LEGEND IAQ — Indoor Air Quality — Low Ambient Lockout Device POT — Potentiometer OAT — Outdoor-Air Temperature RAT — Return-Air Temperature 500 OHM RESISTOR NOTE 1 NOTE 2 50HJ540573 ACTUATOR ASSEMBLY SENSOR 4 - 20 mA DIRECT DRIVE ACTUATOR NOTES:...
  • Page 85: Typical Wiring Schematics

    TYPICAL WIRING SCHEMATICS — 580F (cont) 460V YEL BLU TRAN4 SECONDARY 120V 600V TRAN4 SECONDARY 120V Convenience Outlet (Optional) — Sizes 580F036-151 FIELD POWER SUPPLY a48-7463 NOTE: Use copper conductors only. Non-Fused Disconnect (Optional) — Sizes 580F036-151 C2 FOR 008-014 UNITS TRAN4 SECONDARY 120V...
  • Page 86 TYPICAL PIPING AND WIRING — 580F036-151 48-983 Vertical Discharge Ducting NO.1 CONVENIENCE OUTLET a48-6307 NO.2 NEC — National Electrical Code Horizontal Discharge Ducting...
  • Page 87 UNIT SIZE 581B NOMINAL CAPACITY OPERATING WEIGHT (lb) Unit COMPRESSOR Quantity Oil (oz) REFRIGERANT TYPE Operating Charge (lb-oz) Standard Unit Unit With Perfect Humidity Dehumidification Package CONDENSER FAN Quantity...Diameter (in.) Nominal Cfm Motor Hp...Rpm Watts Input (Total) CONDENSER COIL Standard Unit Rows...Fins/in.
  • Page 88 UNIT SIZE 581B FURNACE SECTION Rollout Switch Cutout Temp (F)† Burner Orifice Diameter (in..drill size)** Natural Gas — Std Liquid Propane — Alt†† Thermostat Heat Anticipator Setting (amps) 208/230/460 v First Stage Second Stage Gas Input (Btuh) First Stage/Second Stage (3-phase units) Efficiency (Steady State) (%) Temperature Rise Range Manifold Pressure (in.
  • Page 89 UNIT SIZE 581B NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit COMPRESSOR Quantity Oil (oz) (each compressor) REFRIGERANT TYPE Operating Charge (lb-oz) Standard Unit Circuit 1 (first stage) Circuit 2 (second stage) Unit With Perfect Humidity Dehumidification Package Circuit 1 (first stage) Circuit 2 (second stage) CONDENSER FAN Quantity...Diameter (in.)
  • Page 90 UNIT SIZE 581B FURNACE SECTION Rollout Switch Cutout Temp (F)† Burner Orifice Diameter (in..drill size)** Natural Gas — Std Liquid Propane — Alt†† Thermostat Heat Anticipator Setting (amps) Stage 1 Stage 2 Gas Input (Btuh) Stage 1 Stage 2 Efficiency (Steady State) (%) Temperature Rise Range Manifold Pressure (in.
  • Page 91 BASE UNIT DIMENSIONS — 581B036-072 a48-8199...
  • Page 92 BASE UNIT DIMENSIONS — 581B090-150 a48-8200...
  • Page 93 ACCESSORY DIMENSIONS — 581B036-072 a48-8201...
  • Page 94 ACCESSORY DIMENSIONS — 581B090-150 a48-8202...
  • Page 95: Selection Procedure

    SELECTION PROCEDURE (With 581B048 Example) I DETERMINE COOLING AND HEATING REQUIRE- MENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity (TC) ..44,600 Btuh Sensible Heat Capacity (SHC)... . 32,000 Btuh Required Heating Capacity .
  • Page 96 581B036 (3 TONS) Temp (F) 900/0.14 Air Ent Condenser (Edb) 41.9 38.7 35.7 20.4 25.2 29.7 2.19 2.16 2.12 40.7 37.5 34.5 19.9 24.7 29.2 2.46 2.42 2.39 39.3 36.1 33.1 19.5 24.1 28.4 2.75 2.71 2.66 37.7 34.6 31.7 18.8 23.5 27.8...
  • Page 97 581B072 (6 TONS) Temp (F) 1800/0.05 Air Ent Condenser (Edb) 86.7 80.7 74.4 43.0 53.7 63.8 4.58 4.46 4.33 84.1 78.2 72.0 42.0 52.6 62.7 5.10 4.97 4.85 81.3 75.3 69.2 41.0 51.4 61.4 5.65 5.52 5.39 77.9 72.0 66.1 39.7 50.2 60.0...
  • Page 98 581B120 (10 TONS) Temp (F) 3000/0.03 Air Ent Condenser (Edb) 140.3 129.4 115.0 65.6 82.2 7.35 7.21 7.12 137.7 125.3 110.0 65.0 81.2 8.29 8.13 8.02 133.8 120.7 103.0 63.9 79.6 9.33 9.16 8.98 128.7 115.4 96.5 62.3 77.6 89.4 10.46 10.28 10.00...
  • Page 99 COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION 581B036 (3 TONS) — SUBCOOLING MODE Temp (F) Air Ent Condenser (Edb) 41.3 17.5 2.19 38.6 15.2 2.46 35.9 13.0 2.74 33.8 10.9 3.05 31.8 3.40 28.7 3.78 581B036 (3 TONS) — HOT GAS REHEAT MODE Temp (F) 62.5 Wet Bulb Air Ent...
  • Page 100 COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B048 (4 TONS) — SUBCOOLING MODE Temp (F) 1200/0.17 Air Ent Condenser (Edb) 52.9 47.5 22.7 28.4 2.87 2.86 49.2 43.8 19.8 25.5 3.26 3.25 45.8 40.1 17.2 22.5 3.71 3.68...
  • Page 101 COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B060 (5 TONS) — SUBCOOLING MODE Temp (F) 1500/0.08 Air Ent Condenser (Edb) 69.9 62.7 29.0 36.9 3.61 3.55 65.9 59.1 25.3 34.0 4.05 3.97 61.9 55.2 21.6 31.1 4.53 4.43...
  • Page 102 COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B072 (6 TONS) — SUBCOOLING MODE Temp (F) 1800/0.05 Air Ent Condenser (Edb) 82.6 75.6 36.0 44.8 4.60 4.52 78.2 71.6 31.4 41.2 5.16 5.03 73.8 67.4 27.0 37.6 5.75 5.60...
  • Page 103 COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B090 (7 TONS) — SUBCOOLING MODE TEMP (F) AIR ENT CONDENSER (Edb) 98.4 44.5 5.05 94.2 39.7 5.74 89.9 34.8 6.42 84.6 30.0 7.26 79.2 25.2 8.10 72.8 20.1 9.10 581B090 (7...
  • Page 104 COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B102 (8 TONS) — SUBCOOLING MODE Temp (F) 2550/0.08 Air Ent Condenser (Edb) 114.1 104.1 49.8 64.2 5.57 5.46 107.3 98.4 42.2 58.3 6.32 6.30 101.9 92.4 35.4 51.9 7.06 7.13...
  • Page 105 COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B120 (10 TONS) — SUBCOOLING MODE Temp (F) 3000/0.03 Air Ent Condenser (Edb) 134.3 122.5 111.4 60.0 76.1 7.03 6.84 127.6 115.4 104.6 51.5 68.8 7.96 7.86 120.9 108.3 43.0 61.5...
  • Page 106 COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont) 581B150 (12 TONS) — SUBCOOLING MODE Temp (F) 3750/0.08 Air Ent Condenser (Edb) 156.3 144.2 66.6 87.6 9.28 8.98 147.6 136.2 58.7 80.0 10.29 9.93 138.9 128.2 50.8 72.3 11.29 10.87...
  • Page 107 Using the fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor fail- ure. Unit warranty will not be affected. 5. Use of a field-supplied motor may affect wire size. Contact your Bryant representative for details. Watts 0.37 0.43 0.50...
  • Page 108 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 1200 0.26 1300 0.31 1400 0.36 1500 0.42 1600 0.49 1700 0.57 1800 0.66 1900 0.75 1014 2000 0.85 1049 581B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont) Airflow (Cfm) Watts...
  • Page 109 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — SINGLE-PHASE UNITS Airflow (Cfm) Watts 1500 0.42 1600 0.49 1004 1700 0.57 1040 1800 0.65 1077 1900 1007 0.75 1115 2000 1048 0.85 1153 2100 1090 0.97...
  • Page 110 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 1500 0.42 1600 0.49 1004 1700 0.57 1040 1800 0.65 1077 1900 1007 0.75 1115 2000 1048 0.85 1153 2100 1090 0.97 1191 2200 1131...
  • Page 111 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B072 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 1800 0.63 1900 1008 0.72 2000 1049 0.82 2100 1091 0.93 2200 1133 1.05 2300 1176 1.18 1047 2400 1218 1.32 1170 2500 1261 1.47...
  • Page 112 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B090 (7 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2250 0.54 0.57 2300 0.63 2400 0.69 2500 2550 0.72 0.76 2600 0.83 2700 0.90 2800 0.98 2900 1.07 3000 1.16 1085 3100 1.26 1176...
  • Page 113 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B090 (7 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2250 0.54 0.57 2300 0.63 2400 0.69 2500 2550 0.72 0.76 2600 0.83 2700 0.90 2800 0.98 2900 1.07 3000 1.16 1085 3100 1.26 1176...
  • Page 114 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B102 (8 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2500 0.50 2600 0.55 2700 0.60 2800 0.66 2900 0.72 3000 0.79 3100 0.85 3200 0.93 3300 1.00 3400 1.09 1012 3500 1.17 1092 3600...
  • Page 115 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B102 (8 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2500 0.50 2600 0.55 2700 0.60 2800 0.66 2900 0.72 3000 0.79 3100 0.85 3200 0.93 3300 1.00 3400 1.09 1012 3500 1.17 1092 3600...
  • Page 116 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B120 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3000 0.79 3100 0.85 3200 0.93 3300 1.00 3400 1.09 1012 3500 1.17 1092 3600 1.26 1177 3700 1.36 1266 3800 1.46 1361 3900 1.57...
  • Page 117 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B120 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3000 0.79 3100 0.85 3200 0.93 3300 1.00 3400 1.09 1012 3500 1.17 1092 3600 1.26 1177 3700 1.36 1266 3800 1.46 1361 3900 1.57...
  • Page 118 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581B150 (12 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3700 1.36 1266 3800 1.46 1361 3900 1.57 1460 4000 1.68 1563 4100 1.79 1672 4200 1.92 1786 4300 2.04 1906 4400 2.18 2031 4500...
  • Page 119 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS 581B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 0.14 1000 0.16 1100 0.20 1200 0.23 1300 0.28 1400 0.33 1500 0.38 581B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont) Airflow (Cfm) Watts 1019...
  • Page 120 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 1200 0.23 1300 0.28 1400 0.33 1500 0.38 1600 0.45 1700 0.52 1800 0.59 1900 0.68 2000 0.77 1006 581B048 (4 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont) Airflow (Cfm) Watts...
  • Page 121 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — SINGLE-PHASE UNITS Airflow (Cfm) Watts 1500 0.39 1600 0.46 1700 0.54 1800 0.63 1900 0.73 2000 1001 0.84 2100 1043 0.96 2200 1085 1.09 2300 1127 1.23...
  • Page 122 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 1500 0.39 1600 0.46 1700 0.54 1800 0.63 1010 1900 0.73 1047 2000 1001 0.84 1085 2100 1043 0.96 1123 2200 1085 1.09 1162 2300...
  • Page 123 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B072 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 1800 0.64 1010 1900 0.73 1046 2000 0.84 1083 2100 1032 0.95 1120 2200 1073 1.07 1158 2300 1114 1.21 1074 1196 2400 1155 1.36...
  • Page 124 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B090 (7 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2250 0.52 2300 0.55 0.60 2400 0.66 2500 0.69 2550 2600 0.73 0.80 2700 0.87 2800 0.95 2900 1.03 3000 1.12 1046 3100 1.22 1135...
  • Page 125 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B090 (7 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2250 0.52 2300 0.55 0.60 2400 0.66 2500 0.69 2550 2600 0.73 0.80 2700 0.87 2800 0.95 2900 1.03 3000 1.12 1046 3100 1.22 1135...
  • Page 126 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B102 (8 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2500 0.45 2600 0.50 2700 0.54 2800 0.59 2900 0.64 3000 0.70 3100 0.76 3200 0.82 3300 0.88 3400 0.95 3500 1.03 3600 1.10 1030...
  • Page 127 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B102 (8 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 2500 0.45 2600 0.50 2700 0.54 2800 0.59 2900 0.64 3000 0.70 3100 0.76 3200 0.82 3300 0.88 3400 0.95 3500 1.03 3600 1.10 1030...
  • Page 128 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B120 (10 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3000 0.70 3100 0.76 3200 0.82 3300 0.88 3400 0.95 3500 1.03 3600 1.10 1030 3700 1.19 1106 3800 1.27 1185 3900 1.36 1269 4000...
  • Page 129 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B120 (10 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3000 0.70 3100 0.76 3200 0.82 3300 0.88 3400 0.95 3500 1.03 3600 1.10 1030 3700 1.19 1106 3800 1.27 1185 3900 1.36 1269 4000...
  • Page 130 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581B150 (12 TONS) — STANDARD MOTOR (BELT DRIVE)* Airflow (Cfm) Watts 3700 1.19 1106 3800 1.27 1185 3900 1.36 1269 4000 1.45 1357 4100 1.55 1449 4200 1.66 1545 4300 1.76 1646 4400 1.88 1751 4500...
  • Page 131 45/47 *As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, the input rate should be reduced at higher altitudes. †Orifices are available through your local Bryant distributor. ELEVATION MAXIMUM HEATING VALUE (Btu/ft...
  • Page 132 69.3 71.5 74.7 71.1 73.3 76.9 69.9 72.5 78.2 NOTE: The indoor sound power is available in Bryant’s Electronic Catalog program (ECAT) for specific operating parameters. EVAPORATOR-FAN MOTOR EFFICIENCY UNIT SIZE 581B EFFICIENCY% 036,048 74/84* 090,102 bhp (746) motor efficiency...
  • Page 133 PERFORMANCE DATA (cont) 0.35 0.25 0.15 0.05 1000 3000 2000 Airflow (cfm) 3 ton 4 & 5 ton 6 ton Perfect Humidity™ Adaptive Dehumidification Coil Pressure Drop (Subcooling and Reheat Modes of Operation) 5000 4000 3000 2000 1000 VERTICAL POWER EXHAUST PERFORMANCE STATIC PRESSURE (in.
  • Page 134 PERFORMANCE DATA (cont) 2500 2000 1500 1000 a48-6309 STATIC PRESSURE (in. wg) HORIZONTAL POWER EXHAUST PERFORMANCE 2500 2000 1500 1000 0.05" 0.15" Static Pressure (in. wg) BAROMETRIC RELIEF CAPACITY 0.1" 0.2" 0.3" Static Pressure (in. wg) OUTDOOR AIR DAMPER LEAKAGE Horizontal EconoMi$er IV and EconoMi$er2 Performance Data (581B036-150) a48-6224...
  • Page 135 EVAPORATOR-FAN MOTOR PERFORMANCE — STANDARD MOTOR UNIT UNIT 581B VOLTAGE 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 090,102 208/230 208/230 LEGEND Bhp — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence.
  • Page 136 POWER EXHAUST POWER EXHAUST DESCRIPTION PART NO. CRPWREXH030A01 Power Exhaust System (208/230-1-60) CRPWREXH021A01 Power Exhaust System (460-3-60) CRPWREXH022A01 Power Exhaust System (208/230-1-60) CRPWREXH023A01 Power Exhaust System (460-3-60) POWER EXHAUST| POWER EXHAUST DESCRIPTION PART NO. CRPWREXH028A01 Horizontal Power Exhaust (208/230-1-60) CRPWREXH029A01 Horizontal Power Exhaust (460-3-60) *Single or three phase rooftop unit.
  • Page 137: Electrical Data

    UNIT SIZE NOMINAL CONV 581B V-PH-Hz TYPE OUTLET 208/230-1-60 208/230-3-60 HIGH 460-3-60 (3 Tons) HIGH 575-3-60 HIGH 208/230-1-60 208/230-3-60 HIGH 460-3-60 (4 Tons) HIGH 575-3-60 HIGH 208/230-1-60 208/230-3-60 HIGH 460-3-60 (5 Tons) HIGH 575-3-60 HIGH 208/230-3-60 HIGH 460-3-60 HIGH (6 Tons) 575-3-60 HIGH 208/230-3-60...
  • Page 138: Electrical Data

    UNIT SIZE NOMINAL CONV IFM TYPE 581B V-PH-Hz OUTLET 208/230-3-60 HIGH 460-3-60 HIGH Tons) 575-3-60 HIGH 208/230-3-60 HIGH 460-3-60 HIGH (10 Tons) 575-3-60 HIGH 208/230-3-60 460-3-60 Tons) 575-3-60 LEGEND CONV — Convenience Outlet — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration —...
  • Page 139: Typical Wiring Schematics

    TYPICAL WIRING SCHEMATICS — 581B a48-8233 SIZES 036-150 (581B090, 460-3-60 Shown)
  • Page 140 TYPICAL WIRING SCHEMATICS — 581B (cont) a48-7910 LEGEND IAQ — Indoor Air Quality — Low Ambient Lockout Device POT — Potentiometer OAT — Outdoor-Air Temperature RAT — Return-Air Temperature 500 OHM RESISTOR NOTE 1 NOTE 2 50HJ540573 ACTUATOR ASSEMBLY DIRECT DRIVE ACTUATOR NOTES: 1.
  • Page 141 TYPICAL WIRING SCHEMATICS — 581B (cont) 460V YEL BLU TRAN4 SECONDARY 120V 600V TRAN4 SECONDARY 120V Convenience Outlet (Optional) — Sizes 581B036-150 FIELD POWER SUPPLY a48-7463 NOTE: Use copper conductors only. Non-Fused Disconnect (Optional) — Sizes 581B036-150 C2 FOR 008-014 UNITS TRAN4 SECONDARY 120V...
  • Page 142 TYPICAL PIPING AND WIRING — 581B036-150 48-983 Vertical Discharge Ducting NO.1 CONVENIENCE a48-6307 OUTLET NO.2 NEC — National Electrical Code Horizontal Discharge Ducting...
  • Page 143 3. Bryant rooftop evaporator fan motors smaller than 5 hp are specifically designed for Bryant and are rated in maximum continuous Bhp or maximum con- tinuous watts. The motors do not have a horsepower rating on the nameplate.
  • Page 144 GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont) 2. Dual compressor models (size 090-150) shall have face-split type evaporator coil (circuit no. 1 on bottom). 3. Testing: a. Evaporator and condenser coils shall be qualified to UL 1995 burst test at 2,200 psi. b.
  • Page 145 2. Evaporator-fan motor shall have permanently lubri- cated bearings and inherent automatic-reset thermal overload protection. Evaporator motors are designed specifically for Bryant and do not have conventional horsepower (HP) ratings listed on the motor name- plate. Motors are designed and qualified in the “air- over”...
  • Page 146 GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont) t. Remote Minimum Position Control — A field- installed accessory remote potentiometer allows the outdoor air damper to be opened or closed beyond the minimum position in the occupied mode for modified ventilation. 3.
  • Page 147 GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont) 23. Return Air Enthalpy Sensor (EconoMi$er IV or EconoMi$er2): The return air enthalpy sensor shall be used with the EconoMi$er IV or EconoMi$er2 device. When used in conjunction with an outdoor air enthalpy sensor, the EconoMi$er IV or EconoMi$er2 device will pro- vide differential enthalpy control.
  • Page 148 UNIT SIZE 581C NOMINAL CAPACITY (tons) OPERATING WEIGHT(lb) Base Unit** COMPRESSOR Quantity Oil (oz) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Standard Unit Unit With Perfect Humidity Adaptive Dehumidification System CONDENSER FAN Quantity...Diameter (in.) Nominal Cfm Motor Hp...Rpm Watts Input (Total) CONDENSER COIL Rows...Fins/in.
  • Page 149 UNIT SIZE 581C FURNACE SECTION Rollout Switch Cutout Temp(F)† Burner Orifice Diameter (in...drill size)** Natural Gas—Std* Liquid Propane—Alt†† Thermostat Heat Anticipator Setting (amps) 208/230/460/575v First Stage Second Stage Gas Input (Btuh) First Stage/Second Stage Efficiency (Steady State ) (%) Temperature Rise Range Manifold Pressure (in.wg) Natural Gas—Std Liquid Propane—Alt††...
  • Page 150 BASE UNIT DIMENSIONS — 581C024-060...
  • Page 151 COOLING CAPACITIES — 581C024-060 STANDARD UNITS 581C024 (2 Tons) Temp (F) Air Entering Evaporator -- CFM/BF Air Ent 600/0.12 Condenser Air Entering Evaporator -- Ewb (F) (Edb) 22.6 24.3 26.7 21.7 19.5 16.4 1.18 1.19 1.21 21.3 25.7 20.5 12.7 1.36 1.37 1.38...
  • Page 152 COOLING CAPACITIES — 581C024-060 STANDARD UNITS (cont) 581C048 (4 Tons) Temp (F) Air Entering Evaporator -- CFM/BF Air Ent 1200/0.05 1600/0.07 Condenser Air Entering Evaporator -- Ewb (F) (Edb) 46.3 51.1 55.7 48.8 39.9 33.8 27.1 46.3 CMP 2.36 2.37 2.38 2.37 42.9...
  • Page 153 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS 581C (2 Tons) - STANDARD MOTOR (BELT DRIVE) AIRFLOW (Cfm) 0.08 0.09 0.13 1000 0.15 LEGEND — Brake Horsepower Watts — Input Watts to Motor *Motor drive range: 680 to 1044 rpm. All other rpms require field- supplied drive.
  • Page 154 581C036 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont) Airflow (Cfm) Watts 1016 0.51 1080 1000 1041 0.59 1104 1100 1066 0.68 1129 1200 1093 0.77 1155 1300 1119 0.87 1181 1400 1147 0.98 1208 1500 1175 1.09 1086 1235 LEGEND —...
  • Page 155 581C048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont) Airflow (Cfm) Watts 1200 1093 0.77 1155 1300 1119 0.87 1181 1400 1147 0.98 1208 1500 1175 1.09 1086 1235 1600 1204 1.21 1207 1263 1700 1233 1.34 1336 1292 1800 1262 1.48 1473...
  • Page 156 581C060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — THREE-PHASE UNITS (cont) Airflow (Cfm) Watts 1500 1312 1.07 1380 1600 1342 1.18 1047 1411 1700 1374 1.30 1153 1441 1800 1406 1.43 1268 1473 1900 1438 1.57 1391 1504 2000 1471 1.72 1523...
  • Page 157 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS 581C024 (2Tons) AIRFLOW (Cfm) 0.08 0.08 0.09 0.09 0.12 0.13 0.14 1000 0.15 0.16 LEGEND — Brake Horsepower Watts — Input Watts to Motor *Motor drive range: 680 to 1044 rpm. All other rpms require field- supplied drive.
  • Page 158 581C036 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont) Airflow (Cfm) Watts 1019 0.64 1084 1000 1042 0.70 1107 1100 1065 0.77 1130 1200 1089 0.84 1153 1300 1113 0.92 1177 1400 1138 1.01 1000 1201 1500 1163 1.10 1092 1226 LEGEND —...
  • Page 159 581C048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont) Airflow (Cfm) Watts 1200 1089 0.84 1153 1300 1113 0.92 1177 1400 1138 1.01 1000 1201 1500 1163 1.10 1092 1226 1600 1189 1.20 1191 1252 1700 1216 1.31 1299 1277 1800 1242 1.42...
  • Page 160 581C060 (5 TONS) — STANDARD MOTOR (BELT DRIVE)* — THREE-PHASE UNITS (cont) Airflow (Cfm) Watts 1500 1247 0.98 1320 1600 1270 1.07 1342 1700 1295 1.17 1040 1365 1800 1321 1.28 1137 1390 1900 1348 1.40 1243 1415 2000 1377 1.53 1359 1442...
  • Page 161 FAN RPM AT MOTOR PULLEY SETTING WITH STANDARD MOTOR* — 581C024-060 UNIT 581C 1044 1008 1185 1144 1460 1425 *Approximate fan rpm shown (standard motor/drive). FAN RPM AT MOTOR PULLEY SETTING WITH HIGH-STATIC MOTOR* — 581C030-060 UNIT 581C 1455 1423 1392 1455 1423...
  • Page 162 EPACT-compliant energy-efficient motor. Variable-speed motors are exempt from EPACT compliance requirements. There- fore, the indoor fan motors for Bryant 581C024-060 units are exempt from these requirements. 1000...
  • Page 163 *As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. †Orifices available through your Bryant distributor. PERFORMANCE DATA — 581C ALTITUDE COMPENSATION* — 581C024-060...
  • Page 164 VERTICAL ECONOMI$ER IV AND ECONOMI$ER2 PERFORMANCE DATA Power Exhaust Part No. CRPWREXH021A01 Power Exhaust System (460-3-60) CRPWREXH030A01 Power Exhaust System (208/230-1-60) Power Exhaust Part No. CRPWREXH028A01 Power Exhaust System (208/230-1-60) CRPWREXH029A01 Power Exhaust System (460-3-60) * Single or three phase rooftop unit. PERFORMANCE DATA —...
  • Page 165 UNIT RATING 581C (decibels) 024-048 LEGEND ARI — Air Conditioning and Refrigeration Institute NOTE: Indoor sound power is available in Bryant’s Electronic Catalog Program (ECAT) for specific operating parameters. VOLTAGE UNIT NOMINAL RANGE IFM TYPE SIZE V-PH-Hz 208/ 230-1-60 (2 tons)
  • Page 166 VOLTAGE UNIT NOMINAL IFM TYPE RANGE SIZE V-PH-Hz 208/230-1-60 208/230-3-60 460-3-60 (4 tons) 575-3-60 Perfect Humidity 208/230-1-60 208/230-3-60 460-3-60 (5 tons) 575-3-60 Perfect Humidity LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration — Indoor (Evaporator) Fan Motor —...
  • Page 167: Typical Wiring Schematics

    — Contactor, Compressor — Capacitor — Compressor Lockout COMP — Compressor Motor EQUIP — Equipment — Freeze Up Protection Thermostat — Fuse — Ground — High-Pressure Switch — Hall-Effect Sensor — Ignitor — Induced-Draft Motor — Indoor Fan Contactor — Indoor Fan Motor —...
  • Page 168: Typical Wiring Schematics

    NOTE 1 NOTE 3 50HJ540573 ACTUATOR ASSEMBLY DIRECT DRIVE ACTUATOR NOTES: 1. Switch on actuator must be in run position for economizer to operate. 2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sensor or HH57A077 enthalpy sensor.
  • Page 169: Typical Piping And Wiring

    TYPICAL PIPING AND WIRING — 581C 024-060 VERTICAL DISCHARGE DUCTING HORIZONTAL DISCHARGE DUCTING NO.1 CONVENIENCE OUTLET NO.2 NEC — National Electrical Code...
  • Page 170 The color of this pre-painted steel is referred to as “American Sterling,” a gray color. Bryant’s paint specification for this color is PH184. Color: American Sterling, this gray color is to match federal standard 595a, #26231.
  • Page 171 GUIDE SPECIFICATIONS — 581C024-060 (cont) 2. Testing: a. Evaporator and condenser coils shall be quali- fied to UL 1995 burst test at 2,200 psi. b. Evaporator and condenser coils shall be leak tested to 150 psig and pressure tested to 400 psig.
  • Page 172 M. Special Features: Certain features are not applicable when the features designated * are specified. For assistance in amending the specifications, contact your local Bryant Sales Office. 1. Roof Curbs (Horizontal and Vertical): a. Formed galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight.
  • Page 173 GUIDE SPECIFICATIONS — 581C024-060 (cont) 3. Manual Outdoor-Air Damper: Manual damper package shall consist of damper, birdscreen, and rainhood which can be preset to admit up to 50% outdoor air for year round ventila- tion. *4. 100% Two-Position Damper: a. Two-position damper package shall include sin- gle blade damper and motor.
  • Page 174 GUIDE SPECIFICATIONS — 581C024-060 (cont) For the EconoMi$er2, the power exhaust shall be controlled by the or third party controls. 23. Outdoor Air Enthalpy Sensor (EconoMi$er IV or EconoMi$er2): The outdoor air enthalpy sensor shall be used with the EconoMi$er IV or EconoMi$er2 device to pro- vide single enthalpy control.
  • Page 175 **The 579F300 units requires 2-in. industrial-grade filters capable of handling face velocities of up to 625 ft/min (such as American Air Filter no. 5700 or equivalent). NOTE: The 579F units have a low-pressure switch (standard) located on the suc- tion side.
  • Page 176: Physical Data

    **The 579F300 units requires 2-in. industrial-grade filters capable of handling face velocities of up to 625 ft/min (such as American Air Filter no. 5700 or equiva- lent). NOTE: The 579F units have a low-pressure switch (standard) located on the suc- tion side. OPERATING AND RIGGING WEIGHTS...
  • Page 177 BASE UNIT DIMENSIONS — 579F180,216 a48-7338...
  • Page 178 BASE UNIT DIMENSIONS — 579F240,300 a48-7339...
  • Page 179 ACCESSORY DIMENSIONS — 579F180-300 a48-7928...
  • Page 180 ACCESSORY DIMENSIONS — 579F180-300 (cont) NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated transition duct. The pressure drop through the adapter curb is negligible. For horizontal return applications: The power exhaust and barometric relief dampers must be installed in the return air duct. Horizontal Supply/Return Adapter Installation (579F180-300) 2'-1 5/8"...
  • Page 181: Accessory Dimensions

    ACCESSORY DIMENSIONS (cont) LEGEND K.O. — Knockout a48-4184 Factory-Installed Convenience Outlet a48-4185 Factory-Installed Non-Fused Disconnect...
  • Page 182: Selection Procedure

    SELECTION PROCEDURE (With 579F180 Example) I DETERMINE COOLING AND HEATING REQUIRE- MENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity ....170,000 Btuh Sensible Heat Capacity ....111,000 Btuh Required Heating Capacity.
  • Page 183: Performance Data

    Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (h total capacity (Btuh) – 4.5 x cfm Where: h = Enthalpy of air entering evaporator coil PERFORMANCE DATA — 579F COOLING CAPACITIES Evaporator Air Quantity — Cfm 4500 Evaporator Air — Ewb (F)/BF 67/0.20 72/0.19 76/0.24...
  • Page 184 (h total capacity (Btuh) – 4.5 x cfm Where: h = Enthalpy of air entering evaporator coil PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) Evaporator Air Quantity — Cfm 7500 Evaporator Air — Ewb (F)/BF 58/0.52 62/0.41...
  • Page 185 (h total capacity (Btuh) – 4.5 x cfm Where: h = Enthalpy of air entering evaporator coil PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) Evaporator Air Quantity — Cfm 5400 Evaporator Air — Ewb (F)/BF 67/0.18 72/0.16...
  • Page 186 (h total capacity (Btuh) – 4.5 x cfm Where: h = Enthalpy of air entering evaporator coil PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) Evaporator Air Quantity — Cfm 9000 Evaporator Air — Ewb (F)/BF 58/0.53 62/0.40...
  • Page 187 (h total capacity (Btuh) – 4.5 x cfm Where: h = Enthalpy of air entering evaporator coil PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) Evaporator Air Quantity — Cfm 6,000 Evaporator Air — Ewb (F)/BF 67/0.19 72/0.17...
  • Page 188 (h total capacity (Btuh) – 4.5 x cfm Where: h = Enthalpy of air entering evaporator coil PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) Evaporator Air Quantity — Cfm 10,000 Evaporator Air — Ewb (F)/BF 58/0.52 62/0.40...
  • Page 189 (h total capacity (Btuh) – 4.5 x cfm Where: h = Enthalpy of air entering evaporator coil PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) Evaporator Air Quantity — Cfm 7,000 Evaporator Air — Ewb (F)/BF 67/0.12 72/0.12...
  • Page 190 (h total capacity (Btuh) – 4.5 x cfm Where: h = Enthalpy of air entering evaporator coil PERFORMANCE DATA — 579F (cont) COOLING CAPACITIES (cont) Evaporator Air Quantity — Cfm 11,250 Evaporator Air — Ewb (F)/BF 58/0.47 62/0.30...
  • Page 191 Alternate high-static drive range for the 216 size is 1069 to 1287. Alternate high- static drive range for the 240 size is 1193 to 1458 rpm. Other rpms require a field- supplied drive. PERFORMANCE DATA — 579F (cont) FAN PERFORMANCE — 579F180-300 UNITS Available External Static Pressure (in. wg)
  • Page 192 460 v) or 1159 to 1429 (575 v). Alternate high-static drive range is 1227 to 1550 (208/230 v and 460 v only). Other rpms require a field-supplied drive. PERFORMANCE DATA — 579F (cont) FAN PERFORMANCE — 579F180-300 UNITS (cont) Available External Static Pressure (in. wg)
  • Page 193 Unit warranty will not be affected. 5. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details.
  • Page 194 (ft) Low Heat 0-3,000 3,000- 7,000 7,000- 9,000 9,000-10,000 above 10,000 *Includes a 4% input reduction per each 1,000 feet. †Orifices available through your Bryant distributor. PERFORMANCE DATA — 579F (cont) ELEVATION (ft) 0-2,000 High Heat 2,001-3,000 3,001-4,000 4,001-5,000 5,001-6,000...
  • Page 195 (60 Hz) 88 dB 88 dB 95 dB 95 dB NOTE: Indoor sound power is available in Bryant’s Electronic Catalog program (ECAT) for specific operating parameters. ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 579F180-300 COMPONENT EconoMi$er IV and EconoMi$er2 LEGEND FIOP — Factory-Installed Option *The static pressure must be added to external static pressure.
  • Page 196 Energy Policy Act of 1992 (EPACT) effective October 24, 1997. NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi- ciency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997. PERFORMANCE DATA — 579F (cont) EVAPORATOR-FAN MOTOR DATA MAXIMUM MAXIMUM...
  • Page 197: Electrical Data

    VOLTAGE NOMINAL UNIT RANGE VOLTAGE No. 1 579F (3 Ph, 60 Hz) RLA LRA 208/230 28.8 14.7 (15 Tons) 10.8 208/230 30.1 15.5 (18 Tons) 12.1 208/230 37.8 17.2 (20 Tons) 12.4 208/230 41.0 21.8 (25 Tons) 17.3 LEGEND — Full Load Amps HACR —...
  • Page 198: Typical Wiring Schematics

    TYPICAL WIRING SCHEMATICS — 579F (579F240, 208/230 V Shown) a48-7929...
  • Page 199 7. Number(s) indicates the line location of used contacts. A bracket over (2) numbers signifies a single-pole, double-throw contact. An underlined number signifies a normally closed contact. A plain (no line) number signifies a normally open contact. TYPICAL WIRING SCHEMATICS — 579F (579F240, 208/230 V Shown) (cont)
  • Page 200 TYPICAL WIRING SCHEMATICS — 579F (cont) LEGEND — Ambient Limit OA — Outdoor Air ECB — Economizer Control Board OAS — Outdoor Air Sensor — Indoor Air RAS — Return Air Sensor IAQ — Indoor Air Quality SAT — Supply Air Temperature...
  • Page 201 TYPICAL WIRING SCHEMATICS — 579F (cont) a48-6005 NOTES: 1. If the Non-Fused Disconnect Service Option is ordered for these units, the Non-Fused Disconnect will be factory-installed. 2. The Disconnect takes the place of TB-1 as shown on the unit wiring diagram label and the component arrangement label.
  • Page 202: Typical Piping And Wiring

    TYPICAL PIPING AND WIRING — 579F180-300 (579F180 Shown) LEGEND b48-1258 NEC — National Electrical Code...
  • Page 203 UNIT 580F NOMINAL CAPACITY (tons) OPERATING WEIGHT Unit EconoMi$er IV COMPRESSOR/MANUFACTURER Quantity...Model (Ckt 1, Ckt 2) Capacity Stages (%) Number of Refrigerant Circuits Oil (oz) (Ckt 1, Ckt 2) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Circuit 1* Circuit 2 CONDENSER COIL Rows...Fins/in.
  • Page 204: Physical Data

    UNIT 580F FURNACE SECTION Rollout Switch Cutout Temp (F)† Burner Orifice Diameter (in..drill size) Natural Gas Thermostat Heat Anticipator Setting (amps) 208/230, 575 v Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input Stage 1 Stage 2 Efficiency (Steady-State) (%) Temperature Rise Range Manifold Pressure (in.
  • Page 205 BASE UNIT DIMENSIONS — 580F180, 210 a48-8203...
  • Page 206 BASE UNIT DIMENSIONS — 580F240 a48-8204...
  • Page 207 BASE UNIT DIMENSIONS — 580F300 a48-8205...
  • Page 208 ACCESSORY DIMENSIONS — 580F180-240 a48-6314...
  • Page 209 ACCESSORY DIMENSIONS — 580F300 a48-7456...
  • Page 210 NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated transition duct. The pressure drop through the adapter curb is negligible. For horizontal return applications: The power exhaust and barometric relief dampers must be installed in the return air duct. Horizontal Supply/Return Adapter Installation (580F180-240) 2'-1 5/8"...
  • Page 211 ACCESSORY DIMENSIONS — 580F (cont) LEGEND K.O. — Knockout a48-4184 Factory-Installed Convenience Outlet a48-4185 Factory-Installed Non-Fused Disconnect (180-300)
  • Page 212: Selection Procedure

    SELECTION PROCEDURE (With 580F240 Example) I DETERMINE COOLING AND HEATING REQUIRE- MENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity ....230,000 Btuh Sensible Heat Capacity (SHC) ... 170,000 Btuh Required Heating Capacity.
  • Page 213: Performance Data

    580F180 (15 TONS) Temp (F) 4,500/0.010 Air Entering Condenser (Edb) 175.7 191.8 210.9 145.5 123.0 99.9 14.0 14.4 15.0 168.8 185.1 203.0 141.7 119.8 97.1 15.2 15.6 16.1 161.8 177.5 194.4 138.7 116.8 93.9 16.4 16.9 17.4 154.6 169.3 185.3 133.9 113.6 90.7...
  • Page 214 580F240 (20 TONS) Temp (F) 6,000/0.04 Air Entering Condenser (Edb) 16.7 17.4 18.1 18.1 18.7 19.5 19.4 20.2 20.9 20.9 21.5 22.3 22.5 23.1 23.8 23.2 23.8 24.6 580F300 (25 TONS) Temp (F) 7,000/0.05 Air Entering Condenser (Edb) 18.0 18.3 18.9 19.6 20.0...
  • Page 215 580F180275* Airflow (Cfm) Watts 4500 1307 1.53 4800 1384 1.62 5100 1465 1.72 5700 1911 2.24 6000 2164 2.54 6300 2439 2.86 6600 2737 3.21 6900 3057 3.59 1013 7200 3401 3.99 1047 7500 1022 3770 4.42 1081 580F180275* (cont) Airflow (Cfm) Watts...
  • Page 216 580F180360* Airflow (Cfm) Watts 4500 1307 1.53 4800 1384 1.62 5100 1571 1.84 5700 2054 2.41 6000 2329 2.73 6300 2628 3.08 6600 2951 3.46 1023 6900 1000 3298 3.87 1059 7200 1038 3672 4.31 1095 7500 1077 4072 4.78 1131 580F180360* (cont) Airflow...
  • Page 217 580F210275 (18 TONS)* Airflow (Cfm) Watts 5,500 2.27 1908 6,000 2.72 2287 6,500 3.22 2710 7,000 3.78 3177 7,500 4.39 3690 1038 8,000 1038 5.06 4251 1093 8,500 1096 5.78 4859 1148 9,000 1154 6.56 5517 1204 9,500 1213 7.40 6224 1260 10,000...
  • Page 218 580F240275 (20 TONS)* Watts 6,000 2607 3.09 6,500 3030 3.59 7,000 3488 4.14 1001 7,500 3982 4.72 1055 8,000 1056 4512 5.35 1111 8,500 1116 5077 6.02 1167 9,000 1175 5678 6.74 1224 9,500 1235 6315 7.49 1282 10,000 1295 6988 8.29 1340...
  • Page 219 580F240360 (20 TONS)* Watts 6,000 2752 3.26 6,500 3201 3.80 7,000 3687 4.37 1049 7,500 1054 4211 5.00 1109 8,000 1117 4773 5.66 1168 8,500 1180 5373 6.37 1229 9,000 1244 6011 7.13 1290 9,500 1308 6687 7.93 1352 10,000 1372 7401 8.78...
  • Page 220 Unit warranty will not be affected. 5. Use of a field-supplied motor may affect wire size. Contact your Bryant rep- resentative for details.
  • Page 221 88 dB 88 dB 94 dB 94 dB LEGEND Bels — Sound Levels (1 bel = 10 decibels) NOTE: Indoor sound power is available in Bryant’s Electronic Catalog program (ECAT) for specific operating parameters. PERFORMANCE DATA (cont) ELEVATION 2,001-3,000 3,001-4,000...
  • Page 222 ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 580F180-300 COMPONENT EconoMi$er IV and EconoMi$er2 LEGEND FIOP — Factory-Installed Option *The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts. UNIT 580F 180†...
  • Page 223: Electrical Data

    VOLTAGE NOMINAL UNIT RANGE VOLTAGE No. 1 580F (3 Ph, 60 Hz) 208/230 32.1 16.4 208/230 30.1 15.5 518 632.5 12.1 208/230 19.2 13.8 80.0 208/230 187.2 253 20.7 517.5 632.5 LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration —...
  • Page 224: Typical Wiring Schematics

    LEGEND — Adjustable Heat Anticipator — Contactor, Compressor — Capacitor — Circuit Breaker — Cooling Compensator — Crankcase Heater — Compressor Lockout COMP — Compressor Motor — Control Relay — Dummy Terminal EQUIP — Equipment — Freeze Protection Thermostat — Fuse —...
  • Page 225 TYPICAL WIRING SCHEMATICS — 580F (cont) a48-7877 — Ambient Limit ECB — Economizer Control Board — Indoor Air — Indoor Air Quality 500 OHM RESISTOR NOTE 1 NOTE 2 50HJ540573 ACTUATOR ASSEMBLY DIRECT DRIVE ACTUATOR LEGEND OAT — Outdoor Air Temperature Sensor NOTES: 1.
  • Page 226: Typical Wiring Schematics

    TYPICAL WIRING SCHEMATICS — 580F (cont) a48-6005 NOTES: 1. If the Non-Fused Disconnect Service Option is ordered for these units, the Non-Fused Disconnect will be factory-installed. 2. The Disconnect takes the place of TB-1 as shown on the unit wiring diagram label and the component arrangement label. Non-Fused Disconnect (Optional) —...
  • Page 227: Typical Piping And Wiring

    TYPICAL PIPING AND WIRING — 580F180-300 LEGEND NEC — National Electrical Code b48-1258...
  • Page 228 UNIT 581A NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* EconoMi$er IV EconoMi$er2 Roof Curb† Hot Gas Reheat Dehumidification Package COMPRESSOR Quantity...Model (Ckt 1, Ckt 2) Number of Refrigerant Circuits Loading (% of full capacity) Crankcase Heater Watts Oil (oz) (Ckt 1, Ckt 2) REFRIGERANT TYPE Expansion Device...
  • Page 229 UNIT 581A NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Al/Al COMPRESSOR Quantity Number of Refrigerant Circuits Oil (ounces) Ckt A...Ckt B...Ckt C REFRIGERANT TYPE Expansion Device Operating Charge (lb) Circuit A Circuit B Circuit C CONDENSER FAN Nominal Cfm (Total, all fans) Quantity...Diameter (in.) Motor Hp...Rpm Watts Input (Total)
  • Page 230: Physical Data

    EVAPORATOR FAN DATA — 581A210-300 VERTICAL SUPPLY/RETURN UNITS 581A LOW RANGE Motor Hp Motor Nominal RPM Maximum Continuous Bhp Maximum Continuous Watts Motor Frame Size Motor Shaft Diameter (in.) Fan Rpm Range Motor Pulley Min. Pitch Diameter (in.) Motor Pulley Max. Pitch Diameter (in.) Blower Pulley Pitch Diameter (in.) Blower Pulley Shaft Diameter (in.) Blower Pulley Type...
  • Page 231 UNIT 581A *Base unit weight does not include electric heaters, copper coils, economizer, power exhaust, barometric relief or crating. See Options and Accessories table below for more information. NOTE: For 155 and 180 unit sizes add 75 lb (34 kg) for domestic crating. For export crating add 500 lb (227 kg). OPTIONS AND ACCESSORIES —...
  • Page 232 BASE UNIT DIMENSIONS — 581A155,180 a48-8219...
  • Page 233 BASE UNIT DIMENSIONS — 581A210-300 a48-8206...
  • Page 234 ACCESSORY DIMENSIONS — 581A155,180 a50-5670...
  • Page 235: Accessory Dimensions

    NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated transition duct. The pressure drop through the adapter curb is negligible. For horizontal return applications: The power exhaust and barometric relief dampers must be installed in the return air duct. Horizontal Supply/Return Adapter Installation (581A155,180) 2'-1 5/8"...
  • Page 236 ACCESSORY DIMENSIONS (cont) a48-4184 Factory-Installed Convenience Outlet a48-6126 Factory-Installed Non-Fused Disconnect...
  • Page 237: Accessory Dimensions

    ACCESSORY DIMENSIONS — 581A210-300 a48-8234...
  • Page 238: Selection Procedure

    I DETERMINE COOLING AND HEATING REQUIRE- MENTS AT DESIGN CONDITIONS. Given: Required Gross Cooling Capacity (TC) ..... . 168,000 Btuh Gross Sensible Heat Capacity (SHC) .
  • Page 239 581A155 (12 Tons) Temp (F) 3600/0.01 Air Ent Cond 92.9 7.56 7.65 7.74 8.01 8.33 90.6 8.58 8.67 8.97 9.26 89.7 9.02 9.18 9.45 87.4 10.1 10.2 10.3 10.6 10.9 11.4 11.4 11.5 11.8 12.2 82.4 12.7 12.8 12.8 13.2 13.5 79.8 14.2...
  • Page 240 581A180 (15 Tons) Temp (F) 4500/0.01 Air Ent Cond 180.5 184.6 188.7 203.5 219.9 233.7 180.5 172.4 159.4 132.3 104.7 9.41 9.49 9.58 9.87 10.19 10.47 10.78 9.58 176.7 180.5 184.4 215.1 227.8 176.7 155.8 129.4 102.4 10.5 10.57 10.64 10.96 11.35 11.62 11.95 10.68 10.72 10.76 11.06 11.45 11.72 12.04 10.85 10.87 10.89 11.17 11.55 11.82 12.13 174.7 177.5 174.7 167.2 11.07 11.14...
  • Page 241: Performance Data

    581A210 (18 Tons) Temp (F) 5400/0.05 Air Ent Cond 10.2 10.3 10.4 10.6 10.8 11.4 11.5 11.5 11.8 12.1 12.2 12.2 12.5 12.7 13.5 13.5 13.6 13.8 14.1 15.1 15.4 15.7 16.6 16.7 16.7 17.3 18.4 18.4 18.4 18.8 19.1 20.2 20.3 20.3...
  • Page 242 581A240 (20 Tons) Temp (F) 6,000/0.04 Air Ent Cond 11.5 11.6 11.7 12.4 13.1 13.2 13.3 13.6 13.9 14.1 14.5 14.9 15.6 15.7 15.8 16.2 16.6 17.4 17.5 17.6 18.1 18.6 19.3 19.4 19.5 20.6 21.3 21.4 21.5 22.7 23.5 23.5 23.6 24.2...
  • Page 243 581A300 (25 Tons) Temp (F) 7,500/0.05 Air Ent Cond 15.5 15.7 15.9 16.5 17.3 17.2 17.3 18.7 17.9 18.1 18.2 18.8 19.5 19.8 19.9 20.6 21.2 22.1 22.2 22.3 22.8 23.4 24.9 25.1 25.4 25.9 28.1 28.2 28.3 28.6 31.6 31.7 31.7 32.4...
  • Page 244 COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION 581A181 (15 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE Temp (F) 4500/0.02 Air Entering Condenser (Edb) 10.4 10.6 10.7 10.9 11.7 11.9 12.1 12.3 12.7 12.9 13.1 13.3 14.1 14.2 14.4 14.7 15.5...
  • Page 245 COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) 581A181 (15 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C ON Temp (F) 4500/0.12 Air Entering Condenser (Edb) 10.7 10.7 10.8 11.8 11.8 11.8 12.9 13.0 13.0 14.0 14.1...
  • Page 246 COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) 581A210 (18 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C OFF Temp (F) 5400/0.03 Air Entering Condenser (Edb) 10.3 10.3 10.3 –2 –8 –12 11.1 11.1 11.1 581A210 (18 TONS) UNIT WITH HOT GAS REHEAT —...
  • Page 247 COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) 581A240 (20 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B AND C OFF Temp (F) 6000/0.04 Air Entering Condenser (Edb) –4 –9 –14 581A240 (20 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C OFF Temp (F) 6000/0.04 Air Entering...
  • Page 248 COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) 581A300 (25 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE Temp (F) 7000/0.042 Air Entering Condenser (Edb) 16.4 17.0 17.6 18.2 16.7 17.9 18.7 19.3 19.9 18.5 20.0 20.8 21.4 22.1 20.7 22.0...
  • Page 249 See Evaporator Fan Motor Data tables for more information. 3. Fan performance is identical for horizontal discharge applications using Bryant horizontal adapter curb. Available External Static Pressure (in. wg) Watts Watts 1.07...
  • Page 250 See Evaporator Fan Motor Data tables for more information. 3. Fan performance is identical for horizontal discharge applications using Bryant horizontal adapter curb. Available External Static Pressure (in. wg) Watts Watts 1027 1.13...
  • Page 251 5180. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Evaporator Fan Motor Data tables for more information. 2. Fan performance is identical for horizontal discharge applications using Bryant horizontal adapter curb. Watts Watts 1822 2.14...
  • Page 252 5180. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Evaporator Fan Motor Data tables for more information. 2. Fan performance is identical for horizontal discharge applications using Bryant horizontal adapter curb. Watts Watts 1893 2.22...
  • Page 253 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A210 (18 TONS) (Low Heat Units)* Airflow (Cfm) Watts 3500 0.68 4000 0.89 4500 1.14 5000 1243 1.43 5500 1536 1.77 6000 1871 2.15 6500 2250 2.59 7000 2676 3.08 7500 3150 3.62 8000 3676 4.23...
  • Page 254 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A210 (18 TONS) (Medium Heat Units)* Airflow (Cfm) Watts 3500 0.70 4000 0.92 4500 1029 1.18 5000 1297 1.49 5500 1606 1.85 6000 1961 2.26 6500 2363 2.72 7000 2815 3.24 7500 3320 3.82 8000 3879...
  • Page 255 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A210 (18 TONS) (High Heat Units)* Airflow (Cfm) Watts 3500 0.70 4000 0.92 4500 1029 1.18 5000 1297 1.49 5500 1606 1.85 6000 1961 2.26 6500 2363 2.72 7000 2815 3.24 7500 3320 3.82 8000 3879...
  • Page 256 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A240 (20 TONS) (Low Heat Units)* Airflow (Cfm) Watts 5,000 1276 1.47 5,500 1579 1.82 6,000 1925 2.21 6,500 2317 2.67 7,000 2758 3.17 7,500 3250 3.74 8,000 3795 4.36 8,500 4394 5.05 9,000 5051 5.81...
  • Page 257 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A240 (20 TONS) (Medium Heat Units)* Airflow (Cfm) Watts 5,000 1329 1.53 5,500 1648 1.90 6,000 2013 2.32 6,500 2428 2.79 7,000 2895 3.33 7,500 3415 3.93 8,000 3992 4.59 8,500 4628 5.32 9,000 5325 6.12...
  • Page 258 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A240 (20 TONS) (High Heat Units)* Airflow (Cfm) Watts 5,000 1329 1.53 5,500 1648 1.90 6,000 2013 2.32 6,500 2428 2.79 7,000 2895 3.33 7,500 3415 3.93 8,000 3992 4.59 8,500 4628 5.32 9,000 5325 6.12...
  • Page 259 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A300 (25 TONS) (Low Heat Units)* Airflow (Cfm) Watts 6,500 2,468 2.84 7,000 2,942 3.38 7,500 3,468 3.99 8,000 4,045 4.65 8,500 4,677 5.38 9,000 5,364 6.17 1042 9,500 1033 6,108 7.03 1090 10,000 1079 6,911...
  • Page 260 FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) 581A300 (25 TONS) (Medium Heat Units)* Airflow (Cfm) Watts 6,500 2,600 2.99 7,000 3,115 3.58 7,500 3,690 4.24 8,000 4,326 4.98 8,500 5,029 5.78 1026 9,000 1033 5,799 6.67 1076 9,500 1085 6,640 7.64 1128 10,000...
  • Page 261 Unit warranty will not be affected. 5. Use of a field-supplied motor may affect wire size. Contact your Bryant representative for details. 6. Field-supplied drive requires changing belt and motor pulley to meet desired airflow. See application data or contact your local Bryant representative for details.
  • Page 262 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A210 (18 TONS) (Low Heat Units)* Airflow (Cfm) Watts 3,500 1064 1.22 4,000 1402 1.61 4,500 1802 2.07 5,000 2264 2.60 5,500 2794 3.21 6,000 1003 3047 3.50 6,500 1079 3812 4.38 7,000 1155 4697 5.40...
  • Page 263 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A210 (18 TONS) (Medium Heat Units)* Airflow (Cfm) Watts 3,500 1105 1.27 4,000 1454 1.67 4,500 1866 2.15 5,000 2343 2.69 5,500 2889 3.32 6,000 1019 3177 3.65 6,500 1096 3973 4.57 7,000 1173 4894 5.63...
  • Page 264 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A210 (18 TONS) (High Heat Units)* Airflow (Cfm) Watts 3,500 1105 1.27 4,000 1454 1.67 4,500 1866 2.15 5,000 2343 2.69 5,500 2889 3.32 6,000 1019 3177 3.65 6,500 1096 3973 4.57 7,000 1173 4894 5.63...
  • Page 265 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A240 (20 TONS) (Low Heat Units)* Airflow (Cfm) Watts 3,500 1082 1.24 4,000 1426 1.64 4,500 1831 2.11 5,000 2301 2.65 5,500 2838 3.26 6,000 1013 3113 3.58 6,500 1089 3893 4.48 7,000 1166 4798 5.52...
  • Page 266 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A240 (20 TONS) (Medium Heat Units)* Airflow (Cfm) Watts 3,500 1123 1.29 4,000 1479 1.70 4,500 1897 2.18 5,000 2383 2.74 5,500 2937 3.38 6,000 1029 3249 3.74 6,500 1106 4061 4.67 7,000 1184 5003 5.75...
  • Page 267 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A240 (20 TONS) (High Heat Units)* Airflow (Cfm) Watts 3,500 1123 1.29 4,000 1479 1.70 4,500 1897 2.18 5,000 2383 2.74 5,500 2937 3.38 6,000 1029 3249 3.74 6,500 1106 4061 4.67 7,000 1184 5003 5.75...
  • Page 268 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A300 (25 TONS) (Low Heat Units)* Airflow (Cfm) Watts 6,500 2,658 3.06 7,000 3,208 3.69 7,500 3,827 4.40 8,000 4,518 5.20 8,500 1012 5,284 6.08 1034 9,000 1069 6,127 7.05 1090 9,500 1127 7,050 8.11 1146...
  • Page 269 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A300 (25 TONS) (Medium Heat Units)* Airflow (Cfm) Watts 6,500 2,730 3.14 7,000 3,294 3.79 7,500 3,929 4.52 8,000 4,637 5.33 8,500 1029 5,421 6.24 1052 9,000 1087 6,285 7.23 1108 9,500 1145 7,231 8.32 1165...
  • Page 270 FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) 581A300 (25 TONS) (High Heat Units)* Airflow (Cfm) Watts 6,500 2,730 3.14 7,000 3,294 3.79 7,500 3,929 4.52 8,000 4,637 5.33 8,500 1029 5,421 6.24 1052 9,000 1087 6,285 7.23 1108 9,500 1145 7,231 8.32 1165...
  • Page 271 0-3,000 3,000- 7,000 7,000- 9,000 9,000-10,000 above 10,000 *Includes a 4% input reduction per each 1,000 feet. †Orifices available through your Bryant dealer. ALTITUDE COMPENSATION — 581A155,180 (LP Gas Units) LIQUID PROPANE ORIFICE SIZE ELEVATION (ft) Low Heat and High Heat...
  • Page 272 ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 581A155,180 COMPONENT EconoMi$er IV LEGEND FIOP — Factory-Installed Option INDOOR SOUND DATA (TOTAL UNIT) — 581A155,180 SOUND A-WEIGHTED UNIT 581A RATING-dB (60 Hz) EVAPORATOR FAN MOTOR PERFORMANCE — 581A155,180 UNIT 581A NOMINAL HP (Standard Motor) (Optional Motor) LEGEND BHP —...
  • Page 273 (decibels) 155,180 210, 240 LEGEND ARI — Air Conditioning and Refrigeration Institute NOTE: Indoor sound power is available in Bryant’s Electronic Catalog Program (ECAT) for specific operating parameters. FAN RPM AT MOTOR PULLEY SETTINGS* — 581A210-300 581A DRIVE Low Range Vertical...
  • Page 274 EVAPORATOR FAN MOTOR SPECIFICATIONS — 581A210-300 UNIT DRIVE ORIENTATION 581A Vertical High Vertical Horizontal High Horizontal Vertical High Vertical Horizontal High Horizontal Mid-Low Vertical Mid-High Vertical Mid-Low Horizontal Mid-High Horizontal LEGEND BHP — Brake Horsepower BkW — Brake Kilowatts ACCESSORY/FIOP STATIC PRESSURE (in. wg) — 581A210-300 COMPONENT 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,500 12,000 Economizer...
  • Page 275: Electrical Data

    VOLTAGE NOMINAL UNIT RANGE VOLTAGE No. 1 581A (3 Ph, 60 Hz) 208/230 20.7 (Standard 10.0 IFM) 208/230 20.7 (Optional IFM) 10.0 208/230 32.1 16.4 12.0 LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration — Indoor (Evaporator) Fan Motor —...
  • Page 276 ELECTRICAL DATA — 581A210-300 WITHOUT CONVENIENCE OUTLET COMPRESSOR VOLTAGE NOMINAL RANGE UNIT VOLTAGE No. 1 No. 2 581A (3 Ph, 60 Hz) 208/230 16.7 16.7 208/230 22.4 22.4 10.7 10.7 208/230 47.1 47.1 19.6 19.6 15.8 15.8 LEGEND — Full Load Amps MCA —...
  • Page 277: Electrical Data

    ELECTRICAL DATA — 581A210-300 WITH OPTIONAL CONVENIENCE OUTLET COMPRESSOR VOLTAGE NOMINAL RANGE UNIT VOLTAGE No. 1 No. 2 581A (3 Ph, 60 Hz) 208/230 16.7 16.7 208/230 22.4 22.4 10.7 10.7 208/230 47.1 47.1 19.6 19.6 15.8 15.8 LEGEND — Full Load Amps MCA —...
  • Page 278: Typical Wiring Schematics

    TYPICAL WIRING SCHEMATICS — 581A a48-7474 581A155, 460-3-60 Shown LEGEND — Adjustable Heat Anticipator — Contactor, Compressor — Capacitor — Circuit Breaker — Cooling Compensator — Crankcase Heater — Compressor Lockout COMP — Compressor Motor — Control Relay — Damper Motor —...
  • Page 279: Typical Wiring Schematics

    a48-7877 — Ambient Limit ECB — Economizer Control Board — Indoor Air — Indoor Air Quality 500 OHM RESISTOR NOTE 1 NOTE 2 50HJ540573 ACTUATOR ASSEMBLY DIRECT DRIVE ACTUATOR LEGEND OAT — Outdoor Air Temperature Sensor NOTES: 1. Switch on actuator must be in run position for economizer to operate. 2.
  • Page 280 TYPICAL PIPING AND WIRING — 581A (581A155 Shown) LEGEND NEC — National Electrical Code b48-1258...
  • Page 281: Guide Specifications (155-300 Size Units)

    GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS PACKAGED ROOFTOP ELECTRIC COOLING UNIT WITH GAS HEAT — CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 13 AND 15 TONS (581A), 15 TO 25 TONS (579F, 580F), NOMINAL (COOLING) 230,000 TO 360,000 BTUH, NOMINAL (INPUT...
  • Page 282 GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont) 3. Burners shall be of the in-shot type constructed of aluminum-coated steel. 4. All gas piping shall enter the unit at a single location. 5. Gas piping shall be capable of being routed through the roof curb directly into unit.
  • Page 283 GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont) 2. Roof Curbs (Horizontal and Vertical): a. Formed of 16-gage galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight. b. Permits installing and securing ductwork to curb prior to mounting unit on the curb.
  • Page 284 GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont) 11. Low-Ambient Kits: When used, allows units to operate at lower outdoor ambient temperatures. Sizes 155, 180, 210/216, and 300 will operate down to 10 F. Size 240 will operate down to 25 F.
  • Page 285 HVAC GUIDE SPECIFICATIONS SIZE RANGE: 18 TO 25 TONS NOMINAL (COOLING) 250,000 TO 400,000 BTUH, NOMINAL (INPUT HEATING) BRYANT MODEL NUMBERS: 581A PART 1 — GENERAL 1.01 SYSTEM DESCRIPTION Unit is an outdoor rooftop mounted, electrically controlled heating and cooling unit utilizing scroll hermetic compres- sors with crankcase heaters for cooling duty and gas com- bustion heat for heating duty.
  • Page 286 GUIDE SPECIFICATIONS — 581A210-300 UNITS (cont) 3. Optional pre-coated aluminum-fin coils shall have a durable epoxy-phenolic coating to provide protection in mildly corrosive coastal environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube.
  • Page 287 Certain features are not applicable when the features designated * are specified. For assistance in amending the specifications, contact your local Bryant Sales Office. 1. Full Perimeter Roof Curbs (Horizontal and Vertical): a. Formed of 14-gage galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight.
  • Page 288 GUIDE SPECIFICATIONS — 581A210-300 UNITS (cont) 11. Non-Fused Disconnect Switch: Switch shall be factory-installed, internally mounted, NEC and UL approved. Non-fused switch shall pro- vide unit power shutoff. Shall be accessible from out- side the unit and shall provide power off lockout capability.
  • Page 289: Controls

    OPERATING SEQUENCE, SIZE 024-151 UNITS Cooling, Units Without Economizer — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor-fan contactor (IFC) and compressor contactor are energized and indoor-fan motor, compressor, and outdoor fan starts. The outdoor-fan motor runs continuously while unit is cooling. For units with 2 stages of cooling, if the thermostat calls for a second stage of cooling by energizing Y2, compressor contac- tor no.
  • Page 290 Heating, Units Without Economizer — When the thermostat calls for heating, power is sent to W on the IGC (integrated gas unit controller) board. An LED (light-emitting diode) on the IGC board will be on during normal operation. A check is made to ensure that the rollout switch and limit switch are closed.
  • Page 291 When the thermostat is satisfied and W1 and W2 are deener- gized, the IFM continues to run and the economizer damper then moves to the minimum position. Units With Hot Gas Bypass Dehumidification Package — When thermostat calls for cooling, terminals G and Y1 and Y2 and the compressor contactors C1 and C2 are energized.
  • Page 292 If field-installed accessory CO sensors are connected to the EconoMi$er IV control, a demand controlled ventilation strategy will begin to operate. As the CO level in the zone increases above the CO set point, the minimum position of the damper will be increased proportionally.
  • Page 293: Application Data

    Wiring of Outdoor-Air Thermostat 12. MOTOR DATA — Due to Bryant’s internal unit design (draw-thru over the motor), air path, and specially designed motors, the full horsepower (maximum continuous bhp) listed in the Physical Data tables and the notes following each Fan Performance table can be utilized with extreme confidence.
  • Page 294 CONCENTRIC DUCT DISTRIBUTION NOTE: Do not drill in this area, damage to basepan may result in water leak. c. E-COATED ALUMINUM FIN coils undergo a precisely controlled scientific process that bonds an impermeable epoxy coating to the specially prepared fin coil surface. E-Coating produces a smooth, consistent coating that is less brittle, more resilient and more durable than previ- ous postcoating processes.
  • Page 295 b. CONTROL FEATURES — The EconoMi$er IV controller provides superior functionality for rooftop unit operation. EconoMi$er IV control features are included as follows: Remote Minimum Position — The EconoMi$er IV con- troller can be used with a field-supplied and field- installed remote minimum position control switch that will enable and disable the EconoMi$er IV to open or close the damper beyond the minimum position for modified...
  • Page 296 CONTROL CONTROL POINT CURVE APPROX. °F (°C) AT 50% RH 73 (23) 70 (21) 67 (19) 63 (17) APPROXIMATE DRY BULB TEMPERATURE— °F (°C) ECONOMI$ERIV WITH OUTDOOR AIR APPLICATION Outdoor Air Dry Bulb None. The outdoor air dry bulb sensor is factory installed. Differential Dry Bulb Single Enthalpy Differential Enthalpy...
  • Page 298 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Copyright 2007 Bryant Heating & Cooling Systems Printed in U.S.A. 3/07 Catalog No. PDS580F-36-4...