WARNING
HEATPUMP
R
Y
C
CONDENSER
R
YCON
COM
NOTES:
1.) Y ENABLES HI SPD FAN COOLING
2.) E ENABLES LO SPD FAN HEATING
W2 ENABLES LO SPD FAN HEATING
W2 AND OT2 CLOSED ENABLES HI SPD FAN HEATING
3.) 0T2 PJ2 MUST BE CUT FOR THIS CONFIGURATION
4.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION.
5.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT.
STAT OPENS ON HUMIDITY RISE.
HEATPUMP - 2 STG EMHT 2 STG AUX - 1 OUTDOOR T'STAT
HEATPUMP
R
Y
C
O
W2
HEATPUMP
CONDENSER
R
YCON
COM
O
W2
NOTES:
1.) Y ENABLES HI SPD FAN COOLING
2.) E ENABLES LO SPD FAN HEATING
W2 AND OT1 CLOSED ENABLES LO SPD FAN HEATING
W2 AND OT2 CLOSED ENABLES HI SPD FAN HEATING
3.) OT1 PJ4 AND 0T2 PJ2 MUST BE CUT
FOR THIS CONFIGURATION
4.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION.
5.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT.
STAT OPENS ON HUMIDITY RISE.
HEATPUMP - 2 STG EMHT 2 STG AUX - 2 OUTDOOR T'STATS
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING.
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO
MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
OUTDOOR
THERMOSTAT
O
W2
HEATPUMP
O
W2
ED
E\W1 W/W2
CONDENSER
R
YCON
COM
PLEASE REFER
TO MANUAL
FOR PROPER
DIP SWITCH
(CFM)
CONFIGURATION.
1st STAGE AUX HEAT ENABLED BY ROOM T'STAT
2ND STAGE AUX ENABLED BY ROOM T'STAT AND OUTDOOR T'STAT
OT1
OT2
ED
OTC
OT1
OT2
OUTDOOR
E\W1
W/W2
CONDENSER
R
YCON
COM
PLEASE REFER
TO MANUAL
FOR PROPER
DIP SWITCH
(CFM)
CONFIGURATION.
NO AUX HEAT IN HEATPUMP MODE UNTIL OUTDOOR T'STAT CLOSES
ROOM
THERMOSTAT
E
O
C
R
G
Y
W2
THERMOSTATS
O
OTC
OT1
OT2
C
R
Y1
G
Y/Y2
OUTDOOR
HEATPUMP
O
W2
ED
Y1
W1
W2
C
R
HEATER
24 VAC
W1
W2
OT1
OT2
HUM
2nd STAGE HEATER
1st STAGE HEATER
ROOM
THERMOSTAT
E
W2
O
C
R
G
Y
THERMOSTATS
O
OTC
OT1
OT2
C
R
Y1
G
OUTDOOR
HEATPUMP
O
W2
ED
Y1
W1
W2
C
R
HEATER
24 VAC
W1
W2
OT1
OT2
HUM
2nd STAGE HEATER
1st STAGE HEATER
4
HUMIDISTAT
(OPTIONAL)
SEE NOTE 5
HUMIDISTAT
HUM
REMOVE
PRODUCTION
WIRE Y1 - O
HUMIDISTAT
(OPTIONAL)
SEE NOTE 5
HUMIDISTAT
Y/Y2
HUM
REMOVE
PRODUCTION
WIRE Y1 - O