SECTION 5 - COMMISSIONING

PRECAUTIONS FOR THE USE OF WATER

Staining and corrosion of the tubes in the evaporator,
absorber and condenser depends on the quality of the
water used as chilled / hot water and cooling water. As
a result, water quality must be checked periodically to
prevent problems. If water quality is not controlled and
maintained properly, premature tube failure can result.
Causes of bad water quality include:
• polluted seawater
• brackish water
• polluted underground water
• cooling tower located near a chimney or in dirty
air
Be sure to analyze the chilled / hot water,
and the cooling water within one month
after commissioning.
Install strainers of 10 mesh and above to the chilled /
hot water and cooling water inlets.
Shut off valves will be installed in the chilled / hot wa-
ter, cooling water inlets and outlets. Be sure the valves
are completely open when supplying water. If not,
the water flow can become turbulent (at the shut off
valves) and damage the water chamber case and tubes.
When you need to temporarily reduce the quantity of
the chilled / hot water and cooling water use the valves
installed at the outlet line to make adjustments.
56
FORM 155.35-ICOM2.EN.CE/GB (1018)
When the flow rate change of the chilled / hot water
is controlled (if the flow rate change function is in-
stalled), the load change speed is limited.
• The load change condition to limit the chilled / hot
water temperature at the outlet is ±0.5 °C: 1.5% of
the minimum/maximum.
• The critical load change condition to prevent an
overcooling trip of the chiller-heater is 5% of the
minimum/maximum.
CHILLED / HOT WATER OUTLET
TEMPERATURE CONTROLLER
The chilled / hot water outlet temperature control-
ler (23A) is located on the sequencer. It controls the
chilled / hot water outlet temperature.

LIQUID LEVEL GAUGES

Liquid level gauges are used to check the condition of
the chiller-heater components.
TABLE 15 - LIQUID LEVEL GAUGES (SIGHT
GLASS)
LIQUID LEVEL
SYMBOL
GAUGE NAME
Refrigerant overflow
monitoring level gauge
Refrigerant tank level
gauge
Absorber level gauge
HT-GEN level gauge
LT-GEN level gauge
DATE: 10/30/2018
FUNCTION
Checks refrigerant
LG5
overflow level
Checks lower limit of
LG4
refrigerant tank level
Checks lower limit of
LG1
absorber
Checks condition
LG3
of solution in high-
temperature generator
Checks condition
LG2
of solution in low-
temperature generator
JOHNSON CONTROLS