HOT INSULATION AND COLD INSULATION
PROCEDURE
The installation of insulation is out of
scope. The customer is responsible for
performing the work.
The recommended materials and their thickness for hot
insulation and cold insulation are shown in the table
below.
4. Use a bonding agent, iron wire, iron band, or other
appropriate materials to adhere the hot insulation
and cold insulation materials. Never rivet them.
Johnson Controls does not recommend the use of
welding pins.

TABLE 1 - INSULATING MATERIAL AND THICKNESS

HOT INSULATION
Material
Rock wool or glass wool
Thickness
50 mm

TABLE 2 - POINTS REQUIRING HOT OR COLD INSULATION

POINT REQUIRING
HOT INSULATION
Exhaust gas flue duct
Heat exchanger
High temperature generator
Low temperature generator
Point carrying Hot Insulation label
JOHNSON CONTROLS
SECTION 3 – HANDLING, STORAGE, INSTALLATION AND REASSEMBLY
5. Make sure that the outer covering, flanged parts,
6. The points that require hot insulation or cold insu-
7. The casing of the absorber and condenser water
8. For the high temperature generator, install the in-
EXHAUST GAS INSULATION
Fineflex B10 blanket (Tombo #5615
equivalency product)
150 mm
POINT REQUIRING
COLD INSULATION
Evaporator shell
Evaporation water changer casing
Refrigerant spray piping
Point carrying Cold Insulation label
and evaporator water chamber casing can be eas-
ily removed to facilitate servicing.
lation are shown in Figure 10 on page 36.
chamber does not require insulation. If you use
insulation, make sure it can be easily removed.
sulation so that the front, sides, and rear insula-
tion can be removed separately. In addition, make
sure that the insulation around the exhaust gas in-
let and the outlet inspection windows can be eas-
ily removed.
COLD INSULATION
Polyurethane foam, polystyrene
foam, or glass wool
50 mm
POINT THAT MUST NOT BE
HEAT-INSULATED
Sight glass
Valve manipulator
Pressure gauge
Relay insertion hole
• Exhaust gas inlet temperature sensor
• Exhaust gas damper radiation fins
3
35