Endress+Hauser Profi Bus Levelflex M FMP40 Operating Instructions Manual

Endress+Hauser Profi Bus Levelflex M FMP40 Operating Instructions Manual

Guided level-radar
Table of Contents

Advertisement

Quick Links

Operating Instructions
Levelflex M FMP40
Guided Level-Radar
BA00243F/00/EN/13.10
71120269
Valid as of software version:
01.04.zz

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Profi Bus Levelflex M FMP40

  • Page 1 Operating Instructions Levelflex M FMP40 Guided Level-Radar BA00243F/00/EN/13.10 71120269 Valid as of software version: 01.04.zz...
  • Page 2 An overview of all device functions can be found on → ä 108. The operating manual BA00245F/00/EN "Description of Instrument Functions" provides an extensive description of all device functions, which can be found on the enclosed CD-ROM. The Operating Instructions can also be found on our homepage: www.endress.com Endress+Hauser...
  • Page 3: Table Of Contents

    Quick wiring guide ......34 Contact addresses of Endress+Hauser ... 99 Connecting the measuring unit .
  • Page 4: Safety Instructions

    Operating Manual. Strict compliance with the installation instructions and ratings as stated in this Additional documentation is mandatory. • Ensure that all personnel are suitably qualified. • Observe the specifications in the certificate as well as national and local regulations. Endress+Hauser...
  • Page 5: Notes On Safety Conventions And Symbols

    Temperature resistance of the connection cables t >85°C States, that the connection cables must be resistant to a temperature of at least 85 °C. Safety Instruction For Safety Instructions refer to the manual for the appropriate device version. Endress+Hauser...
  • Page 6: Identification

    2.1.1 Nameplate The following technical data are given on the device nameplate: Order No Designation according to Directive 94/9/EC (see Order Information) and designation of protection ENDRESS+HAUSER Made in Germany Serial number LEVELFLEX-M D-79689 Maulburg Order Code: Ser.-No.: IP68 / NEMA 6P...
  • Page 7 DN80 PN25/40 B1, 316L flange EN1092-1 (DIN2527 C) DN80 PN25/40, AlloyC22 >316L flange EN1092-1 (DIN2527) DN100 PN10/16 B1, 316L flange EN1092-1 (DIN2527 C) DN100 PN10/16, AlloyC22 >316L flange EN1092-1 (DIN2527) DN100 PN25/40 B1, 316L flange EN1092-1 (DIN2527 C) DN100 PN25/40, AlloyC22 >316L flange EN1092-1 (DIN2527) Endress+Hauser...
  • Page 8 M T12 Alu, coated IP68; gland M20 + OVP N T12 Alu, coated IP68; thread G1/2 + OVP T12 Alu, coated IP68; thread NPT1/2+OVP Q T12 Alu, coated IP68; plug M12 + OVP T12 Alu, coated IP68; plug 7/8" + OVP F23 316L IP68; gland M20 Endress+Hauser...
  • Page 9 N EN10204-3.1 material, NACE MR0175 (316L wetted parts) inspection certificate GL/ABS marine certificate Special version, TSP-No. to be spec. Marking: Tagging (TAG), see additional spec. Bus adress, see additional spec. FMP40- Complete product designation OVP = overvoltage protection Endress+Hauser...
  • Page 10: Scope Of Delivery

    The device complies with the applicable standards and regulations as listed in the EC declaration of conformity and thus complies with the statutory requirements of the EG directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
  • Page 11: Mounting

    When using an aramid fibre seal and a process pressure of 40 bar: 140 Nm Maximum permissible torque: 450 Nm When using an aramid fibre seal and a process pressure of 40 bar: 25 Nm Maximum permissible torque: 45 Nm Endress+Hauser...
  • Page 12: Incoming Acceptance, Transport, Storage

    Do not lift the measuring device by its probe rod in order to transport it. 3.2.3 Storage Pack the measuring device so that is protected against impacts for storage and transport. The original packing material provides the optimum protection for this. The permissible storage temperature is -40 °C to +80 °C. Endress+Hauser...
  • Page 13: Installation Conditions

    Levelflex M FMP40 PROFIBUS PA Mounting Installation conditions 3.3.1 Dimensions Housing dimensions 65 (2.56) 78 (3.07) max. 110 (4.33) ENDRESS+HAUSER F12 housing (Aluminium) 85 (3.35) mm (in) L00-F12xxxx-06-00-00-en-001 max. 100 (4.33) 94 (3.7) 65 (2.56) 78 (3.07) ENDRESS+HAUSER T12 housing (Aluminium) 85 (3.35)
  • Page 14 M20 on 6 mm/0.24” rope ø42,4/1.67” (on 1½” thread or flange) ø22/0.87” (on 4 mm/ 0.16” rope) ø45 / ø75 ø30/1.18” (on 6 mm/0.24” rope) ø45 Option 80, feature “B, D, F, H“ ø75 Option 80, feature “C, E, G, I“ L00-FMP4xxxx-06-00-00-en-007 Endress+Hauser...
  • Page 15: Installation

    The weight is then refixed to the rope: • Reapply screw locking fluid (we recommend Loctite L00-FMP4xxxx-17-00-00-en-044 type 243) to the setscrews and screw into place. • When doing so, observe the following torques: – 4 mm rope: 5 Nm – 6 mm rope: 15 Nm Endress+Hauser...
  • Page 16 Tighten with the – G3/4" : 25 Nm hexagonal nut only – G1-1/2" : 140 Nm L00-FMP4xxxx-17-00-00-en-057 • Levelflex functions in metal, concrete and plastic silos. When installing inmetal silos, take care to ensure goodmetallic contact between the processconnection and silo. Endress+Hauser...
  • Page 17 This is particularly important if a flange was not used. Re-insert the probe if necessary. • Screw the flange to the counterflange on the nozzle. L00-FMP4xxxx-17-00-00-en-059 Note! Before full accuracy is obtained the probe rope must hang fully extended. Endress+Hauser...
  • Page 18 B Metal 100 mm for smooth walls Plastic 100 mm, min. 300 mm to metallic components outside of the tank Concrete 0.5 m/20", otherwise the max. possible measuring range is reduced Distance to protruding internals min. 300 mm. Endress+Hauser...
  • Page 19 See "Ordering structure", → ä 6. Centering disk for rod probes: • d = 45 mm (DN50 (2")) • d = 75 mm (DN80 (3") + DN100 (4")) Tightening torque 15 Nm + 5 Nm L00-FMP4xxxx-17-00-00-en-068 Endress+Hauser...
  • Page 20 " Caution! Before welding the probe into the vessel, it must be grounded by a low-resistive connection. If this is not possible, the electronics as well as the HF module must be disconnected. Otherwise the electronics may be damaged. Endress+Hauser...
  • Page 21 Rod probes Probe rod Sleeve bored tight to ensure electrical contact between the rod and sleeve! Short metal pipe e.g. welded in place Ø 17...18 mm Ground the probe when welding the sleeve! Ø <26 mm L00-FMP4xxxx-17-00-00-en-055 Coax probes L00-FMP4xxxx-17-00-00-en-054 Endress+Hauser...
  • Page 22 ≥ 100 mm metal metal tube ø80...150 mm Extension rod / Centering (see accessories) L00-FMP4xxxx-17-00-00-en-008 Strong dust generation can lead to build-up behind the center washer. This can cause an interference signal. For other installation possibilities please contact Endress+Hauser. Endress+Hauser...
  • Page 23 12 m silo diameter 12 m silo diameter 9 m silo diameter 9 m silo diameter 6 m silo diameter 6 m silo diameter 3 m silo diameter 3 m level [m] level [m] L00-FMP40xxx-05-00-00-en-006 L00-FMP40xxx-05-00-00-en-005 Endress+Hauser...
  • Page 24 • Installation and possible fixing as with bulk solids. • Any distance from wall, as long as occasional contact is prevented. • When installing in tanks with a lot of internals or internals situated close to the probe: Use a coax probe. L00-FMP4xxxx-17-00-00-yy-021 Endress+Hauser...
  • Page 25 100 mm longer than the lower disposal. • It must be ensured that the probe does not come into contact with the side wall. Where necessary, use a centering disk at the lower end of the probe ("Type of Probe:", → ä 8) L00-FMP4xxxx-17-00-00-yy-023 Endress+Hauser...
  • Page 26 • Bypass pipe and stilling well (only for liquids): for viscosities of up to 500 cSt, a bypass pipe, stilling well or a coax probe can be used to prevent interference. L00-FMP4xxxx-17-00-00-xx-002 Endress+Hauser...
  • Page 27 ≥ 1cm/m of the rope length. Reliable, earthed mounting Reliable, isolated mounting Mounting-kit isolated (see accessories) Mounting and contact with a bolt 4mm-rope: M14 6mm-rope: M20 L00-FMP4xxxx-17-00-00-en-027 Endress+Hauser...
  • Page 28 • There must be no open space between the tank wall and the probe. • If measuring externally, an automatic probe length determination and a two point linearisation must be performed in order to compensate for the time-of-flight change caused by the plastic wall. Endress+Hauser...
  • Page 29 250 mm (10"), therefore, a special flange with a "horn adaptor" must be fitted. Nozzles with nominal diameters greater than DN250 (10") should be avoided. If the rope probe is strongly deflected: use an extension rod/centering HMP40, additionaly. max. ~150 mm DN200 (8") DN250 (10") L00-FMP4xxxx-17-00-00-de-026 Endress+Hauser...
  • Page 30 • The insulation may not exceed beyond the points labelled "MAX" in the drawing. Process connection with adapter Process connection with flange G¾, G1½, ¾NPT or 1½NPT DN40 to DN200 tank insulation tank insulation max. 150° C (302° F) max. 150° C (302° F) L00-FMP40xxx-17-00-00-en-003 L00-FMP40xxx-17-00-00-en-002 Endress+Hauser...
  • Page 31 (→ ä 18) and the following points: • After mounting, the housing can be turned 350°, in order make access to the display and the connection compartment easier. • The max. measuring range is reduced to 34 m. Ø 60,3 Ø 76 L00-FMP4xxxx-17-00-00-de-014 Endress+Hauser...
  • Page 32 • Wall and pipe bracket is contained in the scope of delivery and already mounted. • Follow installation instructions, → ä 18 • Mount housing on a wall or pipe as shown in the diagram. wall ENDRESS+HAUSER Levelflex M 4xø8,5 ENDRESS+HAUSER...
  • Page 33: Post-Installation Check

    • Does the measuring device correspond to the measuring point specifications such as process temperature/pressure, ambient temperature, measuring range, etc.? • Are the measuring point number and labeling correct (visual check)? • Is the measuring device adequately protected against rain and direct sunlight (→ ä 86)? Endress+Hauser...
  • Page 34: Wiring

    " Before connection please note the following: PROFIBUS devices are marked on the nameplate (1). The voltage is determined by the PROFIBUS standard and the Caution! ENDRESS+HAUSER Made in Germany LEVELFLEX-M desired safety concept. (see chapter 4.3). D-79689 Maulburg Order Code: Ser.-No.:...
  • Page 35 Levelflex M FMP40 PROFIBUS PA Wiring Wiring in T12 housing " Before connection please note the following: ENDRESS+HAUSER PROFIBUS devices are marked on the nameplate (1). The LEVELFLEX M IP65 voltage is determined by the PROFIBUS standard and the Order Code:...
  • Page 36 " ● PROFIBUS devices are marked on the nameplate (1). The voltage is determined by the PROFIBUS standard and the desired safety concept. (see chapter 4.3). Caution! ENDRESS+HAUSER Made in Germany LEVELFLEX-M D-79689 Maulburg Order Code: ● Connect potential matching line to transmitter earth terminal Ser.-No.:...
  • Page 37: Connecting The Measuring Unit

    9 V to 32 V Lift-off voltage There may be additional restrictions for devices with an explosion protection certificate. Refer to the notes in the appropriate Safety Instructions (XA). 4.2.6 Current consumption Max. 11 mA for the range of voltages given above. Endress+Hauser...
  • Page 38: Recommended Connection

    • Is the cable gland tight? • Is the M12 connector screwed tight? • Is the housing cover screwed tight? • If auxiliary power is available: Is the device ready for operation and is the liquid crystal display visible? Endress+Hauser...
  • Page 39: Operation

    (e.g. "medium property (003)") ➜ 5) Press ) once return to previous function (e.g. "tank shape (002)") ➜ Press ) twice return to Group selection 6) Press ) to return to Measured value display L00-FMP4xxxx-19-00-00-en-001 Endress+Hauser...
  • Page 40 The third digit numbers the individual functions within the function group: → • basic setup • tank properties • medium property • process cond. Here after the position is always given in brackets (e.g. "tank properties" (002)) after the described function. Endress+Hauser...
  • Page 41: Display And Operating Elements

    Display Headline Position indicator ENDRESS + HAUSER Symbol Main value Bargraph Unit – Selection list Function groups -> Functions HOME F000 F001 F002 F003 F004 ... FG00 FG01 FG02 Help text FG03 FG04 FG05 Envelope FG06 curve FG07 L00-FMRxxxxx-07-00-00-en-007 Endress+Hauser...
  • Page 42 Contrast settings of the LCD. Hardware lock / unlock After a hardware lock, an operation of the device via display or communication is not possible! The hardware can only be unlocked via the display. An unlock parameter must be entered to do so. Endress+Hauser...
  • Page 43: Local Operation

    It is not possible to unlock the hardware by communication. All parameters can be displayed even if the device is locked. ⇒ ENDRESS + HAUSER press simultaneous – ⇓ ⇓ The LOCK_SYMBOL appears on the LCD Endress+Hauser...
  • Page 44 There is no need to change these parameters under normal circumstances and consequently, they are protected by a special code known only to the Endress+Hauser service organization. Please contact Endress+Hauser if you have any questions.
  • Page 45 • sep. character (096) • end of probe (030) • unlock parameter (0A4) • level/ullage (040) • application pa (0A8) • linearisation (041) • tag no (0C0) • customer unit (042) A complete “basic setup" (00) must be activated. Endress+Hauser...
  • Page 46: Display And Acknowledging Error Messages

    • The "diagnostics" (0A) function group can display current errors as well as the last errors that occurred. • If several current errors occur, use to page through the error messages. • The last occurring error can be deleted in the "diagnostics" (0A) function group with the function "clear last error" (0A2). Endress+Hauser...
  • Page 47: Profibus Pa Communication

    Ex ia IIC according to the FISCO model). The bus power is supplied by the segment coupler. On-site as well as remote operation are possible. For detailed information on the PROFIBUS PA standard refer to Operation Instructions BA034S/00/EN and the standards EN 50170/ DIN 19245 (PROFIBUS PA) and EN 50020 (FISCO model). Endress+Hauser...
  • Page 48 DIP-switches 1 to 7 according to the following table: Switch No. Value in position "OFF" Value in Position "ON" The new address becomes valid 10 seconds after switching. It results a new device restart. Endress+Hauser...
  • Page 49 ID number 0x152D (hex) = 5421 (dec). Source of supply • Internet (ftp-Server): ftp://194.196.152.203/pub/communic/gsd/Levelflex_m.EXE • CD-ROM with GSD files for all Endress+Hauser devices. Order-Code: 50097200 • GSD library of the PROFIBUS User Organisation (PNO):http: //www.PROFIBUS.com Directory structure The files are oranized in the folowing strucutre: Levelflex_M/PA/Profile3/Revision1.0/...
  • Page 50 This is a value which can be transferred from the PLC to the Levelflex M in order to be shown on the display. FREE PLACE This module must be applied during configuration (see below), if the 2nd cyclic value or the display value are not to appear in the data telegram. Endress+Hauser...
  • Page 51 Die Output-Daten von der SPS für das Display am Gerät haben folgende Struktur: Index Data Access Format/Remarks Input Data 0, 1, 2, 3 Display value write 32 bit floating point number (IEEE-754) Status code for Display value write see "Status codes" Endress+Hauser...
  • Page 52 89 Hex GOOD LOW_LIM (alarm active) 8A Hex GOOD HI_LIM (alarm active) 8D Hex GOOD LOW_LOW_LIM (alarm active) 8E Hex GOOD HI_HI_LIM (alarm active) If a status other than "GOOD" is sent to the device, the display indicates an error. Endress+Hauser...
  • Page 53 If the application program is badly designed, however, this limit can be reached quickly, and the RAM will fail The Levelflex M supports MS2AC communication with two SAP´s. The Levelflex M does not support MS1AC communication. Endress+Hauser...
  • Page 54 Operation Levelflex M FMP40 PROFIBUS PA 5.5.6 Slot/index tables Device Management Parameter Endress+Hauser Slot Index Size Type Read Write Storage Matrix (CW II) [bytes] Class Directory object Array of constant header UNSIGNED16 Composite list Array of constant directory entries UNSIGNED16...
  • Page 55 Levelflex M FMP40 PROFIBUS PA Operation Parameter Endress+Hauser Slot Index Size Type Read Write Storage Matrix (CW II) [bytes] Class LO LO Limit FLOAT static 44-45 HI HI Alarm DS-39* dynamic HI Alarm DS-39* dynamic LO Alarm DS-39* dynamic LO LO Alarm...
  • Page 56 UNSIGNED8 static input value FLOAT+U8+U8 dynamic Select Main value UNSIGNED8 dynamic PA profile revision OSTRING constant Endress+Hauser specific level transducer block Parameter Endress+Hauser Slot Index Size Type Read Write Storage Matrix (CW II) [bytes] Class Standard parameter...
  • Page 57 Levelflex M FMP40 PROFIBUS PA Operation Parameter Endress+Hauser Slot Index Size Type Read Write Storage Matrix (CW II) [bytes] Class In safety dist. V1H6 UNSIGNED8 static Reset self holding V1H7 UNSIGNED8 static Operating mode V1H8 UNSIGNED8 static Brocken probe det.
  • Page 58 Operation Levelflex M FMP40 PROFIBUS PA Parameter Endress+Hauser Slot Index Size Type Read Write Storage Matrix (CW II) [bytes] Class Format display V6H4 UNSIGNED8 static No. decimals V6H5 UNSIGNED8 static Sep. character V6H6 UNSIGNED8 static Display test V6H7 UNSIGNED8 static...
  • Page 59 Thereby the new unit also becomes effective at the output. " Caution! If a linearisation has been carried out, it must be confirmed by the "Set unit to bus" (062) function in order to become effective at the digital output. Endress+Hauser...
  • Page 60 Endress+Hauser operating program The operating program FieldCare is an Endress+Hauser Plant Asset Management Tool based on FDT technology. You can use Field-Care to configure all your Endress+Hauser devices, as well as devices from other manufacturers that support the FDT standard.
  • Page 61 Levelflex M FMP40 PROFIBUS PA Operation Signal analysis via envelope curve L00-FMP4xxxx-20-00-00-en-007 Tank linearization L00-fmp-Ixxx-20-00-00-en-041 Endress+Hauser...
  • Page 62: Commissioning

    Select the basic unit (this message appears the first time the device is switched on) ⇓ The current measured value is displayed ⇓ After is pressed, you reach the group selection This selection enables you to perform the basic setup Endress+Hauser...
  • Page 63: Basic Setup

    F = full calibr. (= span) UB = upper blocking distance setting in 006 setting in 059 D = distance (distance flange / product) SD = safety distance display in 0A5 setting in 015 = level linearisation display in 0A6 extended calibr. L00-FMP4xxxx-19-00-00-en-031 Endress+Hauser...
  • Page 64 • If the power supply fails, all preset and parameterised values remain safely stored in the EEPROM. • All functions are described in detail, as is the overview of the operating menu itself, in the manual "BA00245F - Description of Instrument Functions" on the enclosed CD-ROM. Endress+Hauser...
  • Page 65: Basic Setup With The Vu331

    (see installation in plastic containers). When using a metallic surface at the process connection, the "standard" option is sufficient! Note! In principle the employment of a metallic surface area should be preferred at the process connection! Endress+Hauser...
  • Page 66 – Cellulose spray 35 m (1378") 35 m (1378") – Salt – Isocyanate, aniline – Metallic powder – Aqueous solutions > 7 – Carbon black – Alcohols 35 m (1378") 35 m (1378") – Coal – Ammonia Endress+Hauser...
  • Page 67 The signal from the probe end is positive if the attachment is grounded. Selection: • free • tie down isol. • tie down gnd. If using a metallic centering of probe end. Endress+Hauser...
  • Page 68 When entering the empty value for a linearisation, please use the "empty calibration" instead of the automatically determined probe length. Selection: • length ok • too short • too long After selection "length too short" or "length too long", the calculation of the new value need approx. 10 s. Endress+Hauser...
  • Page 69 F max = E – upper blocking distance L00-FMP4xxxx-14-00-06-en-009 Note! The usable measuring range lies between the upper blocking distance and the probe end. The values for empty distance "E" and span "F" can be set independently of this. Endress+Hauser...
  • Page 70 The following options are available for selection: Selection: • distance = ok • dist. too small • dist. too big • dist. unknown • manual • probe free distance too small distance = ok L00-FMP4xxxx-14-00-06-en-010 Endress+Hauser...
  • Page 71 Function "start mapping" (053) ⇒ ENDRESS + HAUSER – This function is used to start the interference echo mapping up to the distance given in "range of mapping" (052). Selection: • off: no mapping is carried out • on: mapping is started Endress+Hauser...
  • Page 72 ENDRESS + HAUSER – ⇓ After 3 s, the following message appears Note! After the basic setup, an evaluation of the measurement with the aid of the envelope curve ("envelope curve" (0E) function group) is recommended (→ ä 75). Endress+Hauser...
  • Page 73: Blocking Distance

    Within the upper and lower blocking distance, a reliable measurement can not be guaranteed. For stilling well applications The upper blocking distance (UB) is preset to 100 mm when the "bypass/pipe" parameter has been selected in the "tank properties" (002) function. Endress+Hauser...
  • Page 74 L00-FMP4xxxx-05-00-00-en-001 L00-FMP4xxxx-05-00-00-en-002 Note! Please reenter the blocking distance in the function group "extended calibr." (05) function "upper block.dist" (059) when installing the device in a high nozzle: upper blocking distance (UB) = nozzle height (H) + 50 mm. L00-FMP4xxxx-14-00-06-xx-001 Endress+Hauser...
  • Page 75: Envelope Curve With Vu331

    – Note! If the envelope curve mode is active on the display, the measured values are updated in a slower cycle time. Thus, it is advisable to leave the envelope curve mode after the measuring point has been optimised. Endress+Hauser...
  • Page 76: Function "Envelope Curve Display" (0E3)

    Difference curve = envelope curve - mapping (empty curve) The mapping (empty curve) should be a good representation of the probe and the empty tank or silo. Ideally, only the signals from the medium being measured remain in the difference curve. Endress+Hauser...
  • Page 77 - vertical zoom (4 steps) L00-FMPxxxxx-07-00-00-en-004 Horizontal-Zoom-Modus Press , to switch to the envelope curve navigation. You are then in Horizontal Zoom mode. Either is displayed. You now have the following options: • increases the horizontal scale. • decreases the horizontal scale. L00-FMPxxxxx-07-00-00-xx-001 Endress+Hauser...
  • Page 78 The set increases and shifts are retained. Only when you reactivate the "recording curve"(0E2) function does the Levelflex use the standard display again. ⇒ ENDRESS + HAUSER – ⇓ After 3 s, the following message appears Endress+Hauser...
  • Page 79: Basic Setup With The Endress+Hauser Operating Program

    Levelflex M FMP40 PROFIBUS PA Commissioning Basic setup with the Endress+Hauser operating program To carry out the basic setup with the operating program, proceed as follows: • Start the operating program and establish a connection. • Select the "basic setup" function group in the navigation window.
  • Page 80 • Enter the application parameters (see chapter basic setup with "VU331"): – Tank properties – Medium properties – Process properties l00-fmp4xxxx-20-00-00-en-002 Basic setup step 3/6: • Enter the application parameters (see chapter basic setup with "VU331"): – End of probe l00-fmp4xxxx-20-00-00-en-003 Endress+Hauser...
  • Page 81 • Enter the application parameters (see chapter basic setup with "VU331"): – Probe length – Probe – Probe length – Determine length l00-fmp4xxxx-20-00-00-en-004 Basic setup step 5/6: • Enter the application parameters (see chapter basic setup with "VU331"): – Empty calibration – Full calibration l00-fmp4xxxx-20-00-00-en-005 Endress+Hauser...
  • Page 82 Signal analysis via envelope curve After the basic setup, it is recommended to evaluate the measurement with the aid of the envelope curve. L00-FMP4xxxx-20-00-00-en-007 Note! In the event of severe interference echoes, installing the Levelflex at another point can optimize the measurement routine. Endress+Hauser...
  • Page 83 Level echoes are indicated as positive signals in the envelope curve. Interference echoes can be both positive (e.g. reflections from internals) and negative (e.g. nozzles). The envelope curve, the map and the differential curve are used for the evaluation. Level echoes are searched for in the differential curve. Endress+Hauser...
  • Page 84 -500.00 0.00 0.20 0.40 0.60 0.80 1.00 Differential curve = Envelope curve Mapping L00-FMP40xxx-05-00-00-en-025 6.8.2 User-specific applications (operation) For details of setting the parameters of user-specific applications, see separate documentation BA00245F/00/EN "Description of Instrument Functions" on the enclosed CD-ROM. Endress+Hauser...
  • Page 85: Maintenance

    Repairs The Endress+Hauser repair concept assumes that the measuring devices have a modular design and that customers are able to undertake repairs themselves ("Spare Parts", → ä 97). Please contact Endress+Hauser Service for further information on service and spare parts.
  • Page 86: Accessories

    Accessories Levelflex M FMP40 PROFIBUS PA Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the Levelflex M. Weather protection cover A Weather protection cover made of stainless steel is recommended for outdoor mounting (order code: 543199-0001). The shipment includes the protective cover and tension clamp.
  • Page 87: Remote Display And Operation Fhx40

    Additional option: Basic version Mounting bracket, pipe 1"/ 2" Special version, TSP-No. to be spec. FHX40 - Complete product designation For connection of the remote display FHX40 use the cable which fits the communication version of the respective device. Endress+Hauser...
  • Page 88: Centering Disks

    The centering disk is suitable for probes with a rod diameter of 0.63 in (also coated rod probes) and can be used in pipes from DN40 (1½") upto DN50 (2"). See also Operating Instructions BA00378F/00/EN. • Measuring range: -200 °C to +150 °C Order-no. 71069065 Endress+Hauser...
  • Page 89: Commubox Fxa291

    Accessories Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field devices with CDI interface (= Endress+Hauser Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to TI00405C/07/EN. Note! For the device you need the "ToF Adapter FXA291" as an additional accessory.
  • Page 90: Extension Rod / Centering

    DN80 / 3", inside-d.= 76-78mm, PPS DN100 / 4", inside-d.= 100-110mm, PPS DN150 / 6", inside-d.= 152-164mm, PPS DN200 / 8", inside-d.= 210-215mm, PPS DN250 / 10", inside-d.= 253-269mm, PPS Special version, TSP-No. to be spec. HMP40- Complete product designation Endress+Hauser...
  • Page 91: Isolated Tie Down

    M8 DIN580 for 4 mm rope D = 25 mm at M10 DIN580 for 6 mm rope L00-FMP4xxxx-17-00-00-en-036 8.10 Proficard For the connection of a Laptop to PROFIBUS. 8.11 Profiboard For the connection of a Personal Computer to PROFIBUS. Endress+Hauser...
  • Page 92: Trouble-Shooting

    Ready Communication ok? terminator function Check screening (see BA Section EMC interference? Communication ok? Ready 'Connection’) Contact Endress+Hauser Service Communication via Service adapter Not ok Check configuration Correct configuration Communication ok? Ready does not function of COM port on PC...
  • Page 93: System Error Messages

    A251 Feedthrough Lost contact in the process feedthrough Replace process feedtrough Endress+Hauser...
  • Page 94 E651 level in safety distance - risk level in safety distance alarm will disappear as soon as level of overspill leaves safety distance A671 linearisation ch1 not linearisation table is in edit mode activate linearisation table complete, not usable Endress+Hauser...
  • Page 95: Application Errors

    If the device is configured to Hold by loss of noise level during the Repeat once more empty calibr. after turn on the echo the output is set to any value/current. initialisation phase to (005). power supply high. Caution! Before conformation change with to the edit mode. Endress+Hauser...
  • Page 96 (slope incorrect. properties selected → 100% error in the entire Calibration not possible. → measuring range) Selection expected → Select standard → Thresholds too high 2.) actual 1.) actual t → L00-FMP4xxxx-19-00-00-en-030 Medium properties Select lower medium properties. incorrect. Endress+Hauser...
  • Page 97: Spare Parts

    Select the required spare parts (You may also use the overview drawing on the right side of the screen.) When ordering spare parts, always quote the serial number indicated on the nameplate. As far as necessary, the spare parts also include replacement instructions. Endress+Hauser...
  • Page 98: Return

    Levelflex M FMP40 PROFIBUS PA Return The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g. for repair or calibration: • Remove all residue which may be present. Pay special attention to the gasket grooves and crevices where fluid may be present.
  • Page 99: Software History

    52011932 52011936 • Operating menu extended BA243F/00/en/11.06 52011932 BA243F/00/en/03.09 71074791 BA00243F/00/EN/13.10 71120269 Contact addresses of Endress+Hauser Contact addresses can be found on our homepage: www.endress.com/worldwide. If you have any questions, please do not hesitate to contact your Endress+Hauser representative. Endress+Hauser...
  • Page 100: Technical Data

    • 2-wire electronics: 1 s Influence of ambiente The measurements are carried out in accordance with EN 61298-3: temperature • digital output: – average T : 0.6 mm/10 K, max. ±3.5 mm over the entire temperature range -40 °C to +80 °C Endress+Hauser...
  • Page 101 / metallic wall, e.g. plastiv, and in wooden silos. • Interference emission to EN 61326 - x series, electrical equipment Class A. • Interference Immunity: the measured value can be affected by strong electromagnetic fields. Endress+Hauser...
  • Page 102 • Elongation through temperature increase from 30 °C to 150 °C: 2 mm / m rope length 6 mm rope: • Elongation through tension: at max. permitted tensile load (30 KN): 13 mm / m rope length • Elongation through temperature increase from 30 °C to 150 °C: 2 mm / m rope length Endress+Hauser...
  • Page 103 See "Ordering structure", → ä 6. Process connection See "Ordering structure", → ä 6. Seal See "Ordering structure", → ä 6. Probe Endress+Hauser...
  • Page 104 The measuring system meets the legal requirements of the applicable EC guidelines. These are listed in the corresponding EC Declaration of Conformity together with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. WHG. See "Ordering structure", → ä 6 (ZE00256F/00/DE).
  • Page 105 F23 316L IP68 gland M20 F23 316L IP68 thread G1/2 F23 316L IP68 thread NPT1/2 F23 316L IP68 Plug M12 F23 316L IP68 Plug 7/8" 1) Housing F12/F23/T12-OVP: In combination with electronics B, D or F supply intrinsically safe. * In preparation Endress+Hauser...
  • Page 106 This additional documentation can be found on our product pages on www.endress.com • Technical Information (TI00358F/00/EN) • Safety Manual "Functional safety manual" (SD00174F/00/EN) • Certificate "Allgemeine bauaufsichtliche Zulassung" (ZE00256F/00/DE) • Guideline for planning and commissioning (BA034S/04/EN). • Brief operating instructions (KA01039F/00/EN) Endress+Hauser...
  • Page 107 Levelflex M FMP40 PROFIBUS PA Technical data Endress+Hauser...
  • Page 108: Appendix

    + sw-no. serial no. system parameter profile version Note! The default values of the parameters are typed in boldface. L00-FMP4xxxx-19-00-01-en-007 Endress+Hauser...
  • Page 109 . point , comma detection window measured dist. measured level application par. not modified modified reset distance unit download mode L00-FMP4xxxx-19-00-02-en-007 Endress+Hauser...
  • Page 110: Patents

    This product may be protected by at least one of the following patents. Further patents are pending. • US 5,661,251 i EP 0 780 664 • US 5,827,985 i EP 0 780 664 • US 5,884,231 i EP 0 780 665 • US 5,973,637 i EP 0 928 974 Endress+Hauser...
  • Page 111 Levelflex M FMP40 PROFIBUS PA Appendix Endress+Hauser...
  • Page 112 Appendix Levelflex M FMP40 PROFIBUS PA Endress+Hauser...
  • Page 113: Index

    Nameplate ........6 Endress+Hauser...
  • Page 114 Levelflex M FMP40 PROFIBUS PA Index Endress+Hauser...
  • Page 115 Erklärung zur Kontamination und Reinigung Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA# clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
  • Page 116 www.endress.com/worldwide BA00243F/00/EN/13.10 71120269 CCS/FM+SGML 6.0/ProMoDo 71120269...

This manual is also suitable for:

Levelflex m fmp40

Table of Contents